DEVI 532 Electronic Thermostat Installation Guide
DEVIreg™ 532
1.1 Technical Speciꢀcations
Operation voltage
220-240 V~, 50 Hz
Max 0.25 W
Standby power
consumption
Relay:
Resistive load
Inductive load
Max 15 A / 3450 W @ 230 V
cos φ= 0.3 max 1 A
Sensing units
NTC 15 kOhm at 25 °C
Sensing values:
0 °C
25 °C
42 kOhm
15 kOhm
6 kOhm
50 °C
Hysteresis
0.4 °C
Ambient temperature
-10 to +30 °C
5 °C -
Frost protection
temperature
Temperature range
5-35 °C room temperature
20-50 °C ꢀoor temperature
limiter - default 35 °C
1 x 4 mm² or 2 x 2,5 mm²
75 °C
Cable speciꢁcation max
Ball pressure temperature
Pollution degree
2 (domestic use)
4