DEVIreg 316 Electronic Thermostat Installation Guide
| General | Details |
|---|---|
| Name | DEVIreg 316 Electronic Thermostat Installation Guide |
| Make | DEVI |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.3 MB |

DEVI 140F1143 Electronic Intelligent Timer Thermostat Installation Guide

DEVIreg Electronic Intelligent Timer Thermostat Installation Guide

DEVI 330 Electronic Thermostat Installation Guide

DEVI 532 Electronic Thermostat Installation Guide

DEVI 140F1161 Intelligent Electronic Timer Controlled Thermostat Installation Guide

DEVIreg 130 Electronic Thermostat Installation Guide

DEVI 140F1064 Touch Electronic Intelligent Timer Thermostat Installation Guide

DEVI 530M Electronic Thermostat Installation Guide

DEVI 610 Electronic Thermostat Installation Guide

DEVI 316 Electronic Thermostat Installation Guide

DEVIreg 316 Electronic Thermostat Installation Guide Overview
Summary of Contents
- Page 1: Installation guide for DEVIreg™ 316 electronic thermostat.
- Page 2: The English language is used for the original instructions. Other languages are a translation of the original instructions.
- Page 3: The thermostat has a button to adjust the temperature setting with a scale from -10°C to +50°C. An LED indicator shows standby periods and heating periods (red light). Technical specifications include operation voltage of 220 - 240V~, 50Hz and max 0.25W standby power consumption. Relay specifications indicate a maximum of 16A / 3680W @ 230V for resistive load and cos φ= 0.3 max 1A for inductive load. Sensing units use NTC 15 kOhm at 25 °C with specific sensing values for 0 °C, 25 °C, and 50 °C. Hysteresis ranges from 0 ° to 6 °C. The ambient temperature lowering in economy periods has a temperature range of -10 °C to +45 °C. Minimum temperature range is -10 °C to +5 °C. Cable specification maximum is 1 x 4 mm² or 2 x 2.5 mm². Ball pressure temperature is 75 °C. Installation guide is provided.
- Page 4: DEVIreg™ 316 Pollution degree: 2 (domestic use) Storage temperature: -20 °C to +65 °C Protection class: Class II Dimensions: 86 x 36 x 58 mm Weight: 180 g The product complies with the EN/IEC Standard for automatic electrical controls for household and similar use. Safety instructions: Make sure the mains supply to the thermostat is turned off before installation. IMPORTANT: When used to control a floor heating element with a wooden floor, always use a floor sensor and never set the maximum floor temperature to more than 35°C. The installation of the thermostat must be done by an authorized and qualified installer according to local regulations.
- Page 5: DEVIreg™ 316 The thermostat must be connected to a power supply via an all-pole disconnection switch. Always connect the thermostat to continuous power supply. Do not expose the thermostat to moisture, water, dust, and excessive heat. Install the thermostat in an electric cabinet with DIN rail attachment or a separate DIN attachment according to local regulation on IP classes. Do not place the thermostat in a way that it will be exposed to direct sunlight. Click the thermostat on to the DIN rail attachment. Connect the thermostat according to the connection diagram.
- Page 6: DEVIreg™ 316 The screen of the heating cable must be connected to the earth conductor of the power supply cable by using a separate connector. When you use the wire sensor for floor heating, always install the sensor in a conduit. The thermostat is designed so that the sensor circuit is galvanically separated from the high voltage part. The sensor part is regarded as a low voltage part. Night set-back Minimum temperature limiter Hysteresis When the thermostat is used to apply with either heating systems or refrigerating systems, and the requested.
- Page 7: DEVIreg™ 316 The temperature is between -10°C to +50°C. It is recommendable to adjust the hysteresis according to the requested regulating range. If the temperature is set at 18°C and the hysteresis at 3°C, the thermostat will switch on at 18°C and off at 21°C. For controlling room temperature, the hysteresis is recommended to the set point of 1°C. Minimum temperature limiter is recommended when used with snow and ice melting systems. The thermostat allows the system to heat within an upper and lower temperature range. The maximum temperature range has to be between -10°C to +50°C. The minimum temperature range has to be between -10°C to +5°C. A link between terminal 9+10 must be connected to activate the minimum temperature feature. This feature is important to avoid unnecessary energy waste in extremely cold weather.
- Page 8: DEVIreg™ 316 When the temperature drops below the minimum temperature set value, the thermostat stops heating and the LED indicator turns yellow. When the temperature exceeds the maximum temperature setting, the thermostat stops heating and both the indicator for minimum and maximum temperature disappears. Temperature set-back By connecting an external timer to terminals 4 and 6, the thermostat can be set to reduce the temperature by 0°C to 8°C. Installation guide
- Page 9: Warranty A 2-year product warranty is valid for thermostats: DEVIreg™ 316. Danfoss offers DEVIwarranty valid from the date of purchase under specific conditions. During the warranty period, Danfoss shall offer a new comparable product or repair the product if found faulty due to defective design, materials, or workmanship. The decision to repair or replace will be solely at the discretion of Danfoss. Danfoss shall not be liable for any consequential or incidental damages. The warranty is valid only if the WARRANTY CERTIFICATE is completed correctly and proof of purchase is provided. The WARRANTY CERTIFICATE must be filled in, stamped, and signed by the authorized installer. DEVIwarranty does not cover damage caused by incorrect conditions of use or installation by non-authorized electricians. All work will be invoiced in full if Danfoss inspects or repairs faults due to incorrect use or installation. The warranty explicitly excludes all claims exceeding the specified conditions.
- Page 10: Page 10
- Page 11: DEVIreg™ 316 Installation guide
- Page 12: Disposal instruction Installation guide
- Page 13: Installation guide for DEVIreg™ 316.
- Page 14: Page 14
- Page 15: Page 15