COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual

2.3.2 Mounting the Baseplate on the Wall  
2.4 Wiring and Connections  
Turn off power of the HVAC system at  
the main power panel or on the  
controlled-system itself to avoid any  
electrical shock or damage to the  
system.  
WARNING  
2.4.1 Wiring Guide - Conventional Systems  
(24VAC)  
Figure 2-3 - Baseplate (Back view)  
Single Transformer System:  
To fix the baseplate on a wall, pass the wires through the  
opening of the baseplate, and use either 2x self-taping screws  
and dry-wall anchors, or regular 6-32 machine screws to  
attach on a standard single-gang electrical junction  
box (2” x 4”).  
Table 2-5 - Single Transformer System  
2H / 2C System with 1 Transformer  
R
24VAC Power Supply  
Shorting  
Jumper  
Do not over-tighten the screws when  
attaching the baseplate on a wall as  
physical damage may occur.  
Rc  
24VAC Power Supply for Y1,Y2  
CAUTION  
C
Y1  
Y2  
W1  
W2  
G
24VAC Power Supply Common  
Cool Stage 1, relay output  
Cool Stage 2, relay output  
Heat Stage 1, relay output  
Heat Stage 2, relay output  
Fan Control, relay output  
Keep the thermostat housing and  
vents clean and free of any debris to  
avoid malfunction of the device.  
CAUTION  
2.3.3 Wires and Electrical Connection  
Once the baseplate is affixed on the wall, proceed with the  
wiring connections to the terminal block. Please refer to  
Section 2.4, Wiring and Connections for configuration and  
signals definition.  
Dual Transformer System:  
Table 2-6 - Dual Transformer System  
2H / 2C System with 2 Transformers  
R
Rc  
C
24VAC Power Supply  
24VAC Power Supply for Y1, Y2  
24VAC Power Supply Common  
Cool Stage 1, relay output  
Cool Stage 2, relay output  
Heat Stage 1, relay output  
Heat Stage 2, relay output  
Fan Control, relay output  
Y1  
Y2  
W1  
W2  
G
Figure 2-4 - Baseplate with Terminal Blocks Labels  
For systems with only one stage, second stage terminals (Y2, W2) can be left  
floating (open).  
026-1739 R4 Programmable Touchscreen Thermostat  
4
©2024 Copeland LP.  
GeneralDetails
NameCOPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
MakeCopeland
LanguageEnglish
FiletypePDF (Download)
File size0.72 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual

COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual