Honeywell T4M Programmable Modulating Thermostat Installation Guide
T4M Thermostat
Programmable Modulating Thermostat
OpenTherm Boiler
Thermostat
EN
Quick Start Installation Guide
A
B
C
Compatible with OpenTherm appliances only.
Not compatible with 230V boilers, zone valve
applications or 230V electric heating.
OpenTherm
Communication
T
T
S
S
Installation in 3 steps...
Wire the
Thermostat
Power Up
and Test
Configure
the System
Polarity free
1
2
3
OT OT
T
T
S
S
OpenTherm
Boiler
To prevent a short circuit from a loose wire -
Must be installed by a competent person.
• When using multi-core cables: Only remove enough outer
insulation to allow secure fixing of the cores into the terminal block.
To ensure your safety make sure the mains power
is switched OFF before accessing wiring.
• When using single core cables: Secure them together with
a cable tie as close as possible to the terminal block.
32318058-001 B
Wire the Thermostat
Power Up and Test
Power Up the Heating System and do a quick functional test
on the thermostat to check that it switches the boiler.
1
2
Find a suitable wall location away from draughts,
direct sunlight or other heat sources, and where cables
can be run from the boiler to the thermostat.
Press the button to increase
the temperature to maximum and
check the boiler switches on
– The heat demand icon on the
thermostat should be on.
1.2-1.5m
Now press the button to decrease
the temperature to minimum and
check the boiler switches off
– The heat demand icon on the
thermostat should also go off.
A) Separate the wallplate from
the thermostat, and using a
screwdriver open the wallplate
terminal cover to connect wires.
B) Connect wires according
to wiring diagrams and
clip the cover closed.
A
B
C
T
T
T
T
S
S
max 6mm
min 0.25mm²
max 1.5mm²
| General | Details |
|---|---|
| Name | Honeywell T4M Programmable Modulating Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.14 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell D1-528 Direct Thermostat Installation Guide

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH2510/RTH2410 Thermostat Installation Guide

Honeywell T4M Modulating Manual: Questions and Answers
Can the Honeywell T4M Modulating thermostat work with 230V boilers or zone valve applications?
No. It's compatible with OpenTherm appliances only, not with 230V boilers, zone valve OpenTherm applications, or 230V electric heating. Installation Guide, p. 1
How do I enter the advanced menu on the Honeywell T4M to configure settings?
Access the configuration menu to change parameters.
- Press and hold the two buttons together until the display changes (approximately 3 seconds).
- Use the navigation buttons to move through the parameter list.
- Use the adjustment buttons to change a parameter value.
- Press the save button to confirm, or press cancel to discard the change.
- Press the exit button to leave the advanced menu and save all changes. Installation Guide, p. 2
What does the heat demand icon on the Honeywell T4M Modulating thermostat indicate?
It shows when the thermostat is calling for heat from the boiler. It turns on when you raise the temperature and off when you lower it. Installation Guide, p. 2
What does parameter 9:LC Fail Safe mode control on the Honeywell T4M?
It determines boiler behaviour if the thermostat loses power: either off completely or on at 20% / 80% off.
| Setting | Behaviour |
|---|---|
| 0 | Boiler off |
| 1 | Boiler 20% on / 80% off |
What size wires can I use when connecting the Honeywell T4M Modulating thermostat to the boiler?
Use single or multi-core cables with a minimum cross-section of 0.25mm² and maximum of 1.5mm². Strip no more than 6mm of outer insulation from multi-core cables. Installation Guide, p. 1