3.8.5 Economizer Mode  
The ECONOMIZER mode is used to cool the room with fresh  
outdoor air instead of air cooled by the compressor when  
possible to save energy.  
Table 3-12 - Input In State  
INPUT INx STATE  
To allow the Economizer mode to be activated, the following  
conditions must be reached:  
Offset added to the input terminal  
when the INx STATE is LOCAL. When  
the INx STATE is REMOTE, the  
OFFSET is not used.  
The ECONOMIZER ENABLE must be enabled.  
The thermostat mode must be AUTO or COOL.  
INPUT INx  
OFFSET  
The outdoor temperature (IN2) must be below the  
ECONOMIZER CHANGEOVER SETPOINT value.  
In LOCAL state, this is the  
corresponding terminal INx value  
with the applied offset.  
In REMOTE state, this is the value  
written by the Modbus network.  
The outdoor temperature (IN2) must be below the room  
temperature.  
INPUT VALUE  
(INx)  
The Supply Air temperature (IN3) must be above the  
ECONOMIZER SUPPLY AIR TEMPERATURE SETPOINT  
value.  
CONTROL TEMPERATURE is  
updated according to a relationship  
between the thermostat internal  
temperature and the INPUT VALUE  
(IN1). The formula used to get the  
When the Economizer mode is activated, the FAN and ECO  
output relays are energized until SET POINT COOL is reached.  
CONTROL  
TEMPERATURE value is WEIGHT x IN1 +  
(1-WEIGHT) x Internal Temperature.  
Pre-occupancy Purge  
This is used by the thermostat  
algorithm (stage, economizer,  
display).  
The pre-occupancy purge is used only when the schedule is  
active. The thermostat energizes the FAN and ECO relay  
outputs a period of time before a transition from unoccupied  
to occupied. This period is determined by the ECO PRE-  
OCCUPANCY PURGE_PERIOD.  
INPUT WEIGHT Value used in the CONTROL  
IN1  
TEMPERATURE calculation.  
To allow the pre-occupancy purge to be activated, the  
following conditions must be reached:  
The ECONOMIZER ENABLE must be enabled.  
The scheduler must be enabled.  
3.8.4 Dehumidification Mode  
The ECO PRE-OCCUPANCY PURGE_PERIOD must be  
different than OFF.  
When DEHUMIDIFICATION MODE is set to ON, if the current  
humidity measure is equal or higher than the  
DEHUMIDIFICATION RH SETPOINT, the AUX output relay is  
activated. If the current humidity measure is lower than the  
DEHUMIDIFICATION RH SETPOINT, the AUX output relay is  
deactivated.  
NOTE: Note that there is no information on the status of  
the economizer on the display.  
When the DEHUMIDIFICATION MODE is set to OFF, the AUX  
output relay is always deactivated.  
NOTE: Note that there is no information on the status of  
the dehumidification on the display.  
026-1739 R4 Programmable Touchscreen Thermostat  
18  
©2024 Copeland LP.  
GeneralDetails
NameCOPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
MakeCopeland
LanguageEnglish
FiletypePDF (Download)
File size0.72 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual

COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual