3.5.5 Active Stage(s) Indicator  
The thermostat will show the mode is active with the number of activated output stages (see Figure 3-25), as well as the target  
temperature setpoint under the given active mode.  
Figure 3-25 - Active Stage(s) Indicator  
According to the number of output stages configured and available into the thermostat (1 to 2 stages for Cooling and Heating),  
the display will show output activation status according to the following table:  
Table 3-7 - Active Stage Output Activation Status  
Stages Configuration  
Output Activation  
Output Display (on GUI)  
0% OFF  
50% (1-stage ON)  
2-stage Configuration (Cooling, Heating)  
100% (2-stages ON)  
0% OFF  
1-stage Configuration (Cooling, Heating)  
100% (1-stage ON)  
A) BMS schedule  
3.5.6 Schedule Mode  
If a Modbus communication to the thermostat occurs, then it  
is assumed that the Building Management System (BMS)  
controls the thermostat with its own schedule.  
The thermostat can operate on either a schedule or  
unscheduled operation.  
Schedule Mode Inactive (Unscheduled Operation)  
The Schedule Mode set to Inactive is the most basic mode of  
the thermostat. The user can change the temperature  
setpoints on the display, see Section 3.1, Graphical User  
Interface (GUI). The setpoints will remain unchanged until  
the next manual update on the display or by Modbus.  
B) Back-up schedule  
If the thermostat detects a Modbus communication loss (no  
communication addressed to the thermostat during 10  
minutes or more), the internal schedule takes over to control  
the thermostat. When the internal schedule is running, the  
icon “Follow schedule” will be visible on the display  
(Figure 3-26). The text “Follow schedule” is not displayed in  
case the BMS schedule is active.  
Schedule Mode Active (Scheduled Operation)  
The Schedule Mode set to Active describes the thermostat  
behavior against a programmed schedule. To set the  
Schedule Mode to Active, send a request from the BMS to  
enable or disable the schedule. The scheduled operation  
(Active) can only be activated by the Modbus network.  
Scheduled operation can be done via the BMS schedule or  
the back-up schedule.  
Figure 3-26 - Follow Mode Activated  
13  
©2024 Copeland LP.  
026-1739 R4 Programmable Touchscreen Thermostat  
GeneralDetails
NameCOPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
MakeCopeland
LanguageEnglish
FiletypePDF (Download)
File size0.72 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual

COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual