3.8.7 Internal Temperature Offset  
3.8.14 Temperature Stage Difference  
Default Value: 30.74°F (-0.7°C)  
Default Value: 33.8°F (1°C)  
Temperature offset applied to the internal temperature  
measurement.  
Temperature difference between engagement of stage 1 and  
stage 2, for both heating and cooling mode.  
3.8.8 Delay Fan  
3.8.15 Compressor Min ON time  
Default Value: 60 seconds  
Default Value: 0 seconds  
Time delay before stopping the fan after heating or cooling  
stages turn off.  
Once activated by the thermostat algorithm, the compressor  
output (Yx) will be kept activated for a minimum period  
equivalent to Min ON time parameter.  
3.8.9 Temperature Filter Time (Sampling  
Rate)  
3.8.16 Compressor Min OFF time  
Default Value: 0 seconds  
Default Value: 60 seconds  
Once deactivated by the thermostat algorithm, the  
compressor output (Yx) will be kept deactivated for a  
minimum period equivalent to Min OFF time parameter.  
Temperature Filter Time is the time constant on the  
temperature measurement. (Time base for the software  
sampling, with four (4) samples required to get the  
filtered value).  
3.8.10 Temperature Hysteresis  
Default Value: 33.8°F (1°C)  
Temperature hysteresis is the temperature difference  
between activation and deactivation of an output stage (either  
the cooling or heating) during normal  
operation.  
3.8.11 Minimum Temperature Deadband  
(Read-Only)  
Default Value: 35.6°F (2°C)  
Minimum temperature deadband between heat and cool  
setpoints. This deadband feature prevents the thermostat to  
send heat and cool activation simultaneously. When the  
temperature measurement of the room is within this zone  
(between heat and cool setpoints), then no output stage is  
activated.  
3.8.12 Temperature Minimum Setpoint  
Default Value: 59°F (15°C)  
Minimum allowable temperature setpoint for a user.  
NOTE: This parameter is set through network and is not  
accessible on the display of the thermostat.  
3.8.13 Temperature Maximum Setpoint  
Default Value: 77°F (25°C)  
Maximum allowable temperature setpoint for a user.*  
026-1739 R4 Programmable Touchscreen Thermostat  
20  
©2024 Copeland LP.  
GeneralDetails
NameCOPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
MakeCopeland
LanguageEnglish
FiletypePDF (Download)
File size0.72 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual

COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual