Danfoss KPU 19 Thermostat Installation Guide
Installation Guide
Thermostat
Type KPU 19
Application
Thermostat bulb types
KPU 19 thermostats are used for
temperature regulation in refrigeration,
freezing, air conditioning, ventilating
and heating systems.
Remote bulb
Air coil/room sensor
Important
KPU 19 thermostats are fitted with
Single-Pole Double-Throw (SPDT)
or Single-Pole Single-Throw (SPST)
contact system.
The KPU 19 thermostat is designed
only for use as a temperature
regulating operating control. It is
the responsibility of the installer
to verify that other necessary
safety controls are installed and
functioning properly as intended
by the original equipment
The standard KPU 19 enclosure is rated
NEMA ~ 1.
NEMA ~ 1 is obtained when the
thermostat is mounted on a flat surface
with all unused holes covered.
manufacturer or system design.
Product specification
Regulating
Differential
Capillary
tube length temperature temperature
Max. bulb
Ambient
Bulb size
Contact
type
Reset
type
range
[°F]
Type
Code no.
∆T [°F]
[in.]
x 4 1/2
[in.]
[°F]
[°F]
3
KPU 19
KPU 19
-30 – 80
3.6 – 12.6
/
120
140
SPDT
Auto.
Auto.
060L2150
060L2151
-31 – 140
8
8
SPST (close
on temp. rise)
3
-30 – 80
-30 – 80
3.6 – 12.6
3.6 – 12.6
/
x 4 1/2
80
140
140
-31 – 140
-31 – 140
Air coil /
Room sensor
KPU 19
-
SPDT
Auto.
060L2152
Dimensions [in.]
Cover
Scale Plate
Mounting Hole
0.63 0.59
DIFF.
Diff. Adjusting
Knob
0.14
Terminal Screw
Capillary Tube
0.27
Grounding Screw
1.7
Conduit Rubber
2.12
DKRCC.PI.CA0.F2.22 | 1
© Danfoss | DCS (az) | 2018.10
| General | Details |
|---|---|
| Name | Danfoss KPU 19 Thermostat Installation Guide |
| Make | Danfoss |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.78 MB |

Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide

Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide

Danfoss UT 72-UT 73 Universal Thermostat Installation Guide

Danfoss ECtemp 530 Electronic Thermostat Installation Guide

Danfoss 014G0251 Eco Radiator Thermostat User Guide

Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide

Danfoss RET230P Electronic Thermostat Instruction Manual

Danfoss RET1000 Series Electronic Thermostat User Guide

Danfoss CET B-RF Wireless Electronic Hot Water Cylinder Thermostat Installation Guide

Danfoss KPU 19 Thermostat Installation Guide Overview
Summary of Contents
- Page 1: Installation guide for KPU 19 thermostat outlines its application in temperature regulation for various systems. KPU 19 thermostats are used for refrigeration, freezing, air conditioning, ventilating, and heating systems. The thermostat is fitted with SPDT or SPST contact systems. It is designed solely for temperature regulating control, with the installer responsible for additional safety controls. The standard enclosure is rated NEMA ~ 1, achieved when mounted on a flat surface with unused holes covered. Product specifications include regulating differential, capillary tube length, and contact type. The KPU 19 model has a temperature range of -30 to 80 °F and a maximum bulb ambient temperature of 140 °F. Different models include variations in contact type and reset type. Dimensions and mounting details are provided for proper installation. The document includes specific codes for different KPU 19 models.
- Page 2: Installation Select an accessible location for the thermostat to avoid damage. Mount the KPU 19 on a bracket or flat surface to ensure proper operation. Use only the provided mounting holes and avoid making additional holes. Fastening at position “B” may cause housing deformation and malfunction. The thermostat and sensing bulb can be mounted in any position. Fast changes in measured temperature will cause lag in thermostat readings. Install the thermostat where harmful environmental conditions are minimized. Avoid denting or deforming the bulb to prevent damage. Protect the capillary tube from vibration and damage. Wiring All wiring should conform to the National Electrical Code and local regulations. Use only copper wire and the terminal screws furnished in the terminal block. Disconnect the power supply before making any wiring connections. Do not exceed the thermostat’s specified electrical ratings. The terminal block and grounding screw are accessible after removing the front cover.
- Page 3: Wiring options For cooling unit For heating unit Cut-out on temperature decrease Cut-out on temperature increase Contact function Example for application and wiring Adjustment Determination of differential Adjust the thermostat to settings specified by the manufacturer of the controlled equipment.
- Page 4: Setting example (SPDT type) Set at 41 °F for temp. decrease and 50 °F for temp. increase. Upper Switch Point (USP): 50 °F Lower Switch Point (LSP): 41 °F Differential of 9 °F is equivalent to the indication 4 set on the Differential Adjustment Knob. Enclosed accessories include a sensor clamp for bulb fastening and a blinding sticker to cover the hole after dial knob removal. After setting, install the cover and supply power for checking the actual switching points. Calculate the differential between USP and LSP (Differential = USP – LSP; 50 °F - 41 °F = 9 °F). Scale values are indicative only. It is often necessary to use a thermometer when setting working points.