Danfoss KPU 19 Thermostat Installation Guide
Installation
Select an accessible location, where
the thermostat will not be subject
to damage. Mount the KPU 19 on a
bracket or on a completely flat surface.
Mounting on an uneven surface may
cause incorrect thermostat operation.
Use only the mounting holes provided
at the back of the metal housing.
Do not make additional holes.
Locking mounting holes must be
fastened at position A as shown in
diagram to the right.
Fastening at position “B”may result
in housing deformation and KPU 19
malfunction.
A
The KPU 19 thermostat and the
sensing bulb can be mounted in any
position.
The sensing element is filled in with
liquid expansion type charging with
no limitations in terms of temperature
at switch body (TS), temperature at
sensing bulb (TB) or temperature at
capillary tube (TC). KPU 19 can operate
in all following conditions:
Fast changes of the measured
temperature will cause thermostat
measurements lags behind actual
temperature changes in the
application. Make sure to keep
temperature variable acceleration
within 3 minutes per 1.8 °F at liquid, or
within 18 minutes per 1.8 °F at air. KPU
should be installed in a place in which
harmful environmental conditions like
radiation from sun, lamps or radiator is
minimalized.
It is recommended to install the
thermostat at a place where vibration
is 1G or less.
Important
Do not dent or deform the bulb of the
thermostat, as doing so could damage
the bulb and cause charge
TS > TB; TS < TB, TS = TB.
Taking into consideration time
constant of the thermostat it is
recommended to install KPU 19 where
temperature is not changing rapidly.
leakage.
Cooling due to the extensive air flow
might affect thermostat performance
as well.
Do not turn any other screws except
screws on the scale plate, on the micro
switch knob and on the terminal block.
General recommendations for
capillary tube and bulb installation:
1. Protect the capillary tube from
damage due to vibration.
a) When the thermostat unit is
mounted directly on the compressor,
the capillary tube must be secured to
the compressor so that both vibrate
together.
b) For mounting otherwise, form
surplus capillary tube into a loose
loop and secure the loop to the base
on which the thermostat is mounted.
3. Avoid sharp bends (with the radius
of 1/2" or less) and bending the capillary
tube at the same point several times,
as these actions can weaken the
material and increase the likelihood of
the tube cracking.
6. For thermostats with room sensor
coils, make sure that placement allows
free airflow around the coil and bulb.
At the same time, ensure that the bulb
is not exposed to drafts from doors, or
to heat radiated from the evaporator
surface. Make sure that the bulb does
not come into contact with a wall
surface. Never mount the thermostat
directly on a cold wall. Instead, mount
the unit on an insulating plate.
4. Bending of the capillary tube within
1.75" from soldering point with bulb is
not allowed.
5. Form and locate the capillary tube
away from sharp or abrasive objects
that might damage it.
7. KPU 19 sensing bulb is made of
copper, copper alloy, silver solder – do
not use it for media which are harmful
for these materials.
2. Leave a little slack in the capillary
tube to help dampen vibration.
Wiring
Note
Caution
Voltage [V]
A C
All wiring should conform to the
National Electrical Code and to
applicable local regulations.
Use only copper wire.
Use only the terminal screws furnished
in the terminal block.
P.F.
cos Ø
120
240
Amps [A]
Resistive load
1
0.5 ~ 16 0.5 ~ 8
Do not remove cover while power
is supplied as it may cause electrical
shock.
Full load
Amps
0.75 0.5 ~ 16 0.5 ~ 8
0.45 96 48
Inductive
load
Locked
rotor Amps
Do not exceed tightening torque of
10 lb. in. (1.18 Nm).
To avoid the possibility of electric
shock and damage to equipment,
disconnect the power supply before
any wiring connections are made.
Never touch current conducting (LIVE)
parts with your fingers or with tools.
Pilot duty: 125 VA; 120/240 V AC
Do not exceed the thermostat’s
specified electrical ratings.
Do not use impact driver(shock driver).
The terminal block as well as
grounding screw are accessible after
removing the front cover.
Electrical wires should be connected
through the conduit rubber or
alternatively by conduit boss.
DKRCC.PI.CA0.F2.22 | 2
© Danfoss | DCS (az) | 2018.10
| General | Details |
|---|---|
| Name | Danfoss KPU 19 Thermostat Installation Guide |
| Make | Danfoss |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.78 MB |

Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide

Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide

Danfoss UT 72-UT 73 Universal Thermostat Installation Guide

Danfoss ECtemp 530 Electronic Thermostat Installation Guide

Danfoss 014G0251 Eco Radiator Thermostat User Guide

Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide

Danfoss RET230P Electronic Thermostat Instruction Manual

Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide

Danfoss RET1000 Series Electronic Thermostat User Guide