COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual

3.2.1 Configuration Menu – Modbus Device  
Address  
3
Operation  
3.1 Graphical User Interface (GUI)  
The first configuration menu (see Figure 3-4) allows users to  
change the Modbus device address. Ad is shown on the right  
side of the display to indicate which parameter is being  
changed (Ad stands for Address). To change the value, press  
either the up or down arrow, and then press the check icon to  
go to the next parameter. Press CA to cancel and exit the  
configuration menu without saving any changes. To change  
values, touch either the up or down arrow, and then touch the  
check icon to go to the next parameter.  
The display of the device is used as the Graphical User  
Interface to show some of the status, setpoints and actual  
measurements such as room temperature and relative  
humidity. The display is a resistive touch-type that allows  
users to navigate and to change values that are shown on the  
display (see Figure 3-1).  
Figure 3-1 - Display With All Segments Shown  
Figure 3-4 - Modbus Address Configuration Menu  
3.2 Configuration Menu  
Table 3-1 - Modbus Device Address Range  
On the first start-up of the thermostat, the default System  
Configuration is idle. This means that the first step to get the  
device started is to configure the appropriate system  
configuration. The following menu will appear by default  
upon the first startup (Figure 3-2).  
Address Number  
Modbus Device Address  
1 to 247  
Range from 1 to 247  
3.2.2 Configuration Menu – Modbus Device  
Baud Rate  
The second configuration menu (see Figure 3-5) allows users  
to change the Modbus device baud rate. “br” is shown on the  
right side of the display to indicate which parameter is being  
changed (br stands for Baud Rate). To change the value, press  
either the up or down arrow, and then press the check icon to  
go to the next parameter. Press CA to cancel and exit the  
configuration menu without saving any changes.  
Figure 3-2 - Thermostat Display In Idle Configuration  
To access the Configuration Menu (see Figure 3-3), press the  
technician  
icon for 10 seconds. If the thermostat has been  
previously configured, to access the configuration menu from  
the main display, a technician icon should be displayed on the  
right bottom corner of the screen. The technician icon is not  
displayed automatically (Figure 3-3). To display the  
technician icon, touch on the right-bottom corner of the  
screen, and then press the technician icon  
for 10 seconds.  
Figure 3-5 - Modbus Baud Rate Configuration Menu  
Table 3-2 - Modbus Baud Rate  
Menu Option  
Corresponding Baud Rate  
Number  
0
1
9600 bps  
Figure 3-3 - Configuration Menu Access  
19200 bps (default)  
026-1739 R4 Programmable Touchscreen Thermostat  
6
©2024 Copeland LP.  
GeneralDetails
NameCOPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
MakeCopeland
LanguageEnglish
FiletypePDF (Download)
File size0.72 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual

COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual