P04: PROP BAND (Proportional band)*  
This parameter allows you to adjust the proportional band in the range 1.0°C .. 8.0 °C that will be used for proportional control*  
The device, by default, has this parameter set at 2 °C.  
To set the proportional band, proceed as follows:  
1. Having selected the “PROP BAND” parameter, adjust with the “  
is saved automatically.  
“ and/or “  
“ keys the proportional band you wish to set; the setting  
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.  
P05: INTEGR TIME (Integrative time)*  
This parameter allows you to choose the integrative time in the range 0 .. 180 minutes that will be used for the proportional regulation*  
if it has been chosen to have a modulating regulation.  
If set to 0, there will be no supplementary action and there will be a P type regulation, otherwise there will be a P + I type regulation.  
The device, by default, has this parameter set at 60 min.  
To set the integrative time, proceed as follows:  
1. Selected the “INTEGR TIME” parameter, adjust with the buttons “  
saved automatically.  
“ and/or “  
“ the integrative time you want to set; the setting is  
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.  
P06: TMIN HEAT (Minimum heating temperature)  
Adjusts the minimum temperature that can be set in normal operation using the “  
programmable thermostat is set in “Heating” mode and can be set between 5.0 °C and 40.0 °C.  
The device leaves the factory with the parameter set at 5.0 °C.  
“ and “  
“, buttons when the wi-time wall  
To set the minimum temperature, proceed as follows:  
1. Having selected the “TMIN HEAT” parameter, adjust with the “  
“ and/or “  
“ keys the temperature you wish to set (obviously it  
must be a lower value than the temperature set on TMAX HEAT); the setting is saved automatically.  
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.  
P07: TMAX HEAT (Maximum heating temperature)  
Adjusts the maximum temperature that can be set in normal operation using the “  
“ and “  
“, buttons when the wi-time wall  
programmable thermostat is set in “Heating” mode and can be set between 5.0 °C and 40.0 °C.  
The device leaves the factory with the parameter set to 40.0 °C.  
To set the maximum temperature, proceed as follows:  
1. Having selected the “TMAX HEAT” parameter, adjust with the “  
“ and/or “  
“ keys the temperature you wish to set (obviously it  
must be a higher value than the temperature set on TMIN HEAT); the setting is saved automatically  
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.  
P08: TMIN COOL (Minimum cooling temperature).  
Adjusts the minimum temperature that can be set in normal operation using the “  
“ and “  
“, buttons when the wi-time wall  
programmable thermostat is set in “Cooling” mode and can be set between 5.0 °C and 40.0 °C.  
The device leaves the factory with the parameter set to 5.0 °C.  
To set the minimum temperature, proceed as follows:  
1. Having selected the “TMIN COOL” parameter, adjust the temperature you wish to set with the “  
must be a lower value than the temperature set on TMAX COOL); the setting is saved automatically.  
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.  
“ and/or “  
“ keys (obviously it  
* With proportional control, it will be necessary to read the dedicated registers with MODBUS® protocol to gain access to the proportional output.  
The relay output can be used, for example, to give consent to a circulation pump when the proportional output is greater than 0%.  
The status of the output relay is also available via MODBUS® register.  
GCW03MR001SE 040088 230922  
11  
GeneralDetails
Nameseitron Wi-Time Wall Wi-Fi Programmable Thermostat Instruction Manual
Makeseitron
LanguageEnglish
FiletypePDF (Download)
File size0.32 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
seitron TAD022 Digital Room Thermostat for Heating Cooling System Instruction Manual
seitron TAD022 Digital Room Thermostat for Heating Cooling System Instruction Manual
seitron TM 00-M Electro Mechanical Room Thermostat Instructions
seitron TM 00-M Electro Mechanical Room Thermostat Instructions
seitron 039790 WiFi WiTime Wall Programmable Thermostat User Guide
seitron 039790 WiFi WiTime Wall Programmable Thermostat User Guide
seitron DR R02M Thermostat Wireless Kit Instruction Manual
seitron DR R02M Thermostat Wireless Kit Instruction Manual
seitron KTY003 Hygge Kit Class 5 WiFi Battery Powered Programmable Thermostat User Guide
seitron KTY003 Hygge Kit Class 5 WiFi Battery Powered Programmable Thermostat User Guide
seitron TR D02B Wireless Digital Thermostat User Manual
seitron TR D02B Wireless Digital Thermostat User Manual

seitron Wi-Time Wall Wi-Fi Programmable Thermostat Instruction Manual