seitron Wi-Time Wall Wi-Fi Programmable Thermostat Instruction Manual
P04: PROP BAND (Proportional band)*
This parameter allows you to adjust the proportional band in the range 1.0°C .. 8.0 °C that will be used for proportional control*
The device, by default, has this parameter set at 2 °C.
To set the proportional band, proceed as follows:
1. Having selected the “PROP BAND” parameter, adjust with the “
is saved automatically.
“ and/or “
“ keys the proportional band you wish to set; the setting
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.
P05: INTEGR TIME (Integrative time)*
This parameter allows you to choose the integrative time in the range 0 .. 180 minutes that will be used for the proportional regulation*
if it has been chosen to have a modulating regulation.
If set to 0, there will be no supplementary action and there will be a P type regulation, otherwise there will be a P + I type regulation.
The device, by default, has this parameter set at 60 min.
To set the integrative time, proceed as follows:
1. Selected the “INTEGR TIME” parameter, adjust with the buttons “
saved automatically.
“ and/or “
“ the integrative time you want to set; the setting is
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.
P06: TMIN HEAT (Minimum heating temperature)
Adjusts the minimum temperature that can be set in normal operation using the “
programmable thermostat is set in “Heating” mode and can be set between 5.0 °C and 40.0 °C.
The device leaves the factory with the parameter set at 5.0 °C.
“ and “
“, buttons when the wi-time wall
To set the minimum temperature, proceed as follows:
1. Having selected the “TMIN HEAT” parameter, adjust with the “
“ and/or “
“ keys the temperature you wish to set (obviously it
must be a lower value than the temperature set on TMAX HEAT); the setting is saved automatically.
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.
P07: TMAX HEAT (Maximum heating temperature)
Adjusts the maximum temperature that can be set in normal operation using the “
“ and “
“, buttons when the wi-time wall
programmable thermostat is set in “Heating” mode and can be set between 5.0 °C and 40.0 °C.
The device leaves the factory with the parameter set to 40.0 °C.
To set the maximum temperature, proceed as follows:
1. Having selected the “TMAX HEAT” parameter, adjust with the “
“ and/or “
“ keys the temperature you wish to set (obviously it
must be a higher value than the temperature set on TMIN HEAT); the setting is saved automatically
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.
P08: TMIN COOL (Minimum cooling temperature).
Adjusts the minimum temperature that can be set in normal operation using the “
“ and “
“, buttons when the wi-time wall
programmable thermostat is set in “Cooling” mode and can be set between 5.0 °C and 40.0 °C.
The device leaves the factory with the parameter set to 5.0 °C.
To set the minimum temperature, proceed as follows:
1. Having selected the “TMIN COOL” parameter, adjust the temperature you wish to set with the “
must be a lower value than the temperature set on TMAX COOL); the setting is saved automatically.
2. Press the “ “ key to select the next parameter or wait 15 sec. without pressing any key.
“ and/or “
“ keys (obviously it
* With proportional control, it will be necessary to read the dedicated registers with MODBUS® protocol to gain access to the proportional output.
The relay output can be used, for example, to give consent to a circulation pump when the proportional output is greater than 0%.
The status of the output relay is also available via MODBUS® register.
GCW03MR001SE 040088 230922
11
| General | Details |
|---|---|
| Name | seitron Wi-Time Wall Wi-Fi Programmable Thermostat Instruction Manual |
| Make | seitron |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.32 MB |

seitron TAD022 Digital Room Thermostat for Heating Cooling System Instruction Manual

seitron TM 00-M Electro Mechanical Room Thermostat Instructions

seitron 039790 WiFi WiTime Wall Programmable Thermostat User Guide

seitron DR R02M Thermostat Wireless Kit Instruction Manual

seitron KTY003 Hygge Kit Class 5 WiFi Battery Powered Programmable Thermostat User Guide

seitron TR D02B Wireless Digital Thermostat User Manual