Home > PRO1 > PRO1 T731W Wireless PTAC Non-Programmable Thermostat Installation Guide

PRO1 T731W Wireless PTAC Non-Programmable Thermostat Installation Guide

Establishing A Connection  
Establishing A Connection  
Base Module LED Information  
Establishing Communication between the thermostat &  
the base module  
The Base module’s LED is used to communicate the status of the wireless  
network.  
The Thermostat and Base module in this package are linked at our factory.  
Upon power up they will automatically begin communicating. If you wish  
to make any changes to the network such as adding or removing devices,  
please follow the instructions on this page.  
• Green Blink at 3s: Normal operating mode. All devices are connected  
and healthy.  
• Yellow Blink at 3s: Normal operating mode. One or more (but not all)  
remote devices are NOT reporting.  
How To Pair  
• Red Blink at 3s: Normal operating mode. ALL network devices are  
NOT reporting.  
On the Base module:  
• White Blink at 3s: Unpaired mode. Base module is powered but is NOT  
paired to any remotes.  
1. Press the button next to the LED.  
2. The Base module will begin double blinking pink for 2 minutes while it  
waits  
for a remote to join.  
3. Once a device joins, the LED will show green blinks and return to  
normal operating mode.  
• Blue double blink: Transmission received from a remote.  
• Purple double blink: Base module is in pairing mode waiting for a remote.  
• Green 5 quick blinks: A remote has successfully been added to the  
basemodules network.  
On the Thermostat:  
1. Press and hold the light button for 3 seconds. The LED will flash 3 times  
and pair with the base module.  
2. The Thermostat will attempt to connect to a Base module within range  
3. Once paired, the LCD will temporarilly display “PAIREDwhen it joins with  
a Base module.  
Note:  
This equipment has been tested and found to comply with the limits for a Class  
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed  
to provide reasonable protection against harmful interference in a residential  
installation. This equipment generates, uses and can radiate radio frequency  
energy and, if not installed and used in accordance with the instructions, may  
cause harmful interference to radio communications. However, there is no  
guarantee that interference will not occur in a particular installation. If this  
equipment does cause harmful interference to radio or television reception,  
which can be determined by turning the equipment off and on, the user is  
encouraged to try to correct the interference by one or more of the following  
measures:  
How To Unpair  
On the Base Module:  
1. PRESS and HOLD the button next to the LED for 6 seconds.  
2. The Base module LED will turn RED for 6 seconds.  
3. All connected devices will be deleted.  
On the Thermostat:  
1. Enter the “UNPAIRINGtech menu.  
2. Press and hold the “+button.  
3. The LCD will show “UNPAIRED.  
4. The Thermostat will no longer be connected to a network.  
• Reorient or relocate the receiving antenna.  
• Increase the separation between the equipment and receiver.  
• Connect the equipment into an outlet on a circuit different from that to  
which the receiver is connected.  
• Consult the dealer or an experienced radio/TV technician for help.  
17  
18  
Network Specifications  
Specifications  
Wireless Network Specifications  
Specifications  
Thermostat  
The thermostat will attempt to pair with the first Base module it  
“hears. Do not attempt to create more than one “pairat the same  
time in the same place.  
The display range of temperature ... 41˚F to 95˚F (5˚C to 35˚C)  
The control range of temperature.... 44˚F to 90˚F (7˚C to 32˚C)  
Load rating.................................................1 amp per terminal, 1.5 amp  
maximum all terminals combined  
Swing (cycle rate or differential) ...... Heating is adjustable from 0.2˚ to 2.0˚  
Cooling is adjustable from 0.2˚ to 2.0˚  
To ensure paring success, place the T731W/O within a few feet of  
the Base module while pairing. Once paired, the signal strength  
tech menu can be used to ensure a robust wireless connection.  
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz  
for hardwire  
Battery power from 2 AA Alkaline  
Placing either device in or around large metal objects can severely  
degrade the wireless range.  
batteries  
Operating ambient ............................... 32˚F to +105˚F (0˚C to +41˚C)  
Operating humidity .............................. 90% non-condensing maximum  
Dimensions of thermostat ................. 4.7”W x 4.4”H x 1.1”D  
Frequency ................................................ 916 MHz  
The wireless network will automatically recover in the event of a  
power loss or temporary signal loss.  
Network Capabilities  
Base Module  
Thermostat units will require up to 60 seconds to reflect changes  
in the system.  
Load rating ............................................... 1 amp per terminal, 1.5 amp  
maximum all terminals combined.  
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz  
Operating ambient ............................... 32˚F to +150˚F (0˚C to +65˚C)  
Operating humidity .............................. 90% non-condensing maximum  
Note:  
Changes or modifications not expressly approved by the manufacturer could  
void the user’s authority to operate the equipment.  
19  
20  
GeneralDetails
NamePRO1 T731W Wireless PTAC Non-Programmable Thermostat Installation Guide
MakePRO1
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PRO1 T751i Thermostat Installation Guide
PRO1 T751i Thermostat Installation Guide
PRO1 T805 Non Programmable Thermostat Instruction Manual
PRO1 T805 Non Programmable Thermostat Instruction Manual
PRO1 T701 Digital Non Programmable Thermostat Instruction Manual
PRO1 T701 Digital Non Programmable Thermostat Instruction Manual
PRO1 IAQ T721i Digital WIFI Programmable Thermostat User Manual
PRO1 IAQ T721i Digital WIFI Programmable Thermostat User Manual
PRO1 R250W Wireless System Thermostat Owner’s Manual
PRO1 R250W Wireless System Thermostat Owner’s Manual
PRO1 T725 Thermostat User Guide
PRO1 T725 Thermostat User Guide
PRO1 T755 Heat 2 Cool Dual Fuel Thermostat User Manual
PRO1 T755 Heat 2 Cool Dual Fuel Thermostat User Manual
PRO1 T771 Programmable Electronic Thermostat Instructions
PRO1 T771 Programmable Electronic Thermostat Instructions

PRO1 T731W Wireless PTAC Non-Programmable Thermostat Installation Guide