mars 7602-457 Communicating Programmable Thermostat Instruction Manual

Installation Manual - 7602-457 Communicating, Programmable Thermostat  
VARIABLE SPD INTERNAL  
PUMP CONFIGURATION  
LOOP OPTION  
SINGLE  
FIXED  
PUMP CONTROL  
HEATING STAGE 1  
COOLING STAGE 2  
60%  
75%  
COOLING STAGE 1  
COOLING STAGE 2  
50%  
70%  
Or  
PREVIOUS  
SELECT  
3.5  
VALVE CONFIGURATION  
Congure temperature differentials at the thermostat for  
vFlow™ units with a motorized modulating valve.  
Adjust the Valve Conguration settings using the up/down  
arrow buttons. Press the center button to select each item.  
Heating Delta T (default stored in control) –  
valid range: 4 to 12ºF (in 1ºF increments)  
Cooling Delta T (default stored in control) –  
valid range: 9 to 20ºF (in 1ºF increments)  
Two  
connections  
on DXM2  
board to allow  
for multi-unit  
installation  
NOTE 1: Minimum and Maximum degree values are shown  
only when the control is congured with the appropriate  
values.  
NOTE 2: Refer to section 3.6.3 for multi-unit conguration  
instructions.  
MODULATING VALVE  
CONFIGURATION  
OFF POSITION  
0.0  
3.6.1 MULTI-UNIT AIRFLOW SELECTION  
VALVE CONTROL DELTA T  
In section 3.1, when an installer selects “Airfl ow  
Selection” from the System Confi guration menu, the  
installer may choose the unit to confi gure by the last 4  
digits of its serial number from the following screen.  
HEATING DELTA T  
COOLING DELTA T  
7 F  
10 F  
MAXIMUM HEAT LWT  
MINIMUM COOL LWT  
80 F  
40 F  
AIRFLOW SELECTION  
PREVIOUS  
SELECT  
TT026  
TT026  
TT038  
S N - - - - - 1 2 3 4  
S N - - - - - 5 6 7 8  
S N - - - - - 9 0 1 2  
For certain commercial multi-unit applications, the modulating  
valve can be kept slightly open by choosing an off position  
value between 3.3-4.0.  
NOTE: Off position 0.0 means that the value is fully closed  
when the unit is not operating.  
PREVIOUS  
SELECT  
3.6  
MULTI-UNIT CONFIGURATION  
If multiple units are connected to one ATC thermostat upon  
unit start-up, the thermostat will automatically register the  
serial numbers of all units connected to it.  
NOTE: Multiple units may be connected directly to the ATC  
thermostat or connected to one another in series, as shown  
by the gure below.  
9
GeneralDetails
Namemars 7602-457 Communicating Programmable Thermostat Instruction Manual
MakeMARS
LanguageEnglish
FiletypePDF (Download)
File size0.49 MB
Download PDF