mars 7602-457 Communicating Programmable Thermostat Instruction Manual
Installation Manual - 7602-457 Communicating, Programmable Thermostat
7.5
SMART HEAT STAGING
9.0 Service Mode
When there is auxiliary heating demand, Smart Heat Staging
defines the minimum amount of time to wait before activating
auxiliary heating. If you find that the thermostat is operating
auxiliary heating equipment too quickly/slowly, this setting
allows for adjustment to correct the temperature algorithm.
SERVICE MODE
MANUAL OPERATION
CONTROL DIAGNOSTICS
DIPSWITCH CONFIG
FAULT HISTORY
Adjust the Smart Heat Staging setting using the up/down
arrow buttons. Press the center button to save changes.
•
Smart Heat Staging (default Off): options: OFF,
5 – 120 minutes (in 5 minute increments)
CLEAR FAULT HISTORY
SELECT OPTION
PREVIOUS
7.6
ELECTRIC HEAT LOCKOUT
SELECT
Electric heat lockout keeps electric heat turned off if the
outdoor temperature is above the specified temperature so
as only to use electric heat when necessary.
9.1
MANUAL OPERATION
Manual Operation mode allows the service personnel to
manually command operation for any of the thermostat
outputs, blower speed, as well as pump speed or valve
position to help troubleshoot specific components.
Adjust the Electric Heat Lockout setting using the up/down
arrow buttons. Press the center button to save changes.
•
Electric Heat Lockout (default Off): options:
OFF, 5 – 60°F (in 5°F increments)
NOTE 1: The ECM Airflow adjustment will not be present if the
connected communicating control (DXM2) is not configured for
ECM (section 3.3).
NOTE: An outdoor temperature sensor must be installed for
this feature to work.
NOTE 2: The Pump Speed adjustment will not be present
if the connected communicating control (DXM2) is not
configured for Pump (section 3.3).
8.0 Demand Reduction Configuration
Demand Reduction is activated by an input signal at the unit
control board to reduce the electric load while peak utility
rates are high. The Demand Reduction Configuration mode
selects which of the available unit control inputs is to be
used as the activation signal. While a physical input signal is
present at the selected input, the thermostat will implement
load reduction by limiting operation or capacity. Refer to
section 5.6.9 in the user manual (part number 97B0055N02)
for more details on Demand Reduction.
NOTE 3: The Valve Position adjustment will not be present if
the connected communicating control (DXM2) is configured for
Valve (section 3.1).
NOTE 4: If multiple units are connected to one thermostat,
refer to section 9.6
MANUAL OPERATING MODE
Y1
Y2
W
O
COMM OUTPUT
COMM OUTPUT
COMM OUTPUT
COMM OUTPUT
COMM OUTPUT
COMM OUTPUT
COMM OUTPUT
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0
Adjust the Demand Reduction Configuration setting using
the up/down arrow buttons. Press the center button to save
changes.
G
•
No Demand Reduction (default) – Demand
Reduction operating mode will not be activated by
a DXM2 input.
H
DH
ECM AIRFLOW
PUMP SPEED
TEST MODE
0%
•
DXM2 Inputs – Assigns a DXM2 input to activate
Demand Reduction operating mode.
OFF
SELECT OPTION
PREVIOUS
INSTALLER SETTINGS
SELECT
THERMOSTAT CONFIG
SYSTEM CONFIG
ACCESSORY CONFIG
INPUT DEALER INFO
HUMIDITY CONFIG
9.2
CONTROL DIAGNOSTICS
Control Diagnostics mode allows the service personnel to
view the status of all physical inputs, switches, temperature
sensor readings, as well as the operational status of the
pump at the thermostat.
TEMPERATURE CONTROL
DEMAND REDUCTION CNFG
SERVICE MODE
SETPOINT LIMITS
RESTORE DEFAULTS
Navigate between diagnostic screens using the left/right
arrow buttons.
DXM2
3.3
C 1.0
7602-457
SELECT OPTION
PREVIOUS
12
| General | Details |
|---|---|
| Name | mars 7602-457 Communicating Programmable Thermostat Instruction Manual |
| Make | MARS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.49 MB |