Home > MARS > mars 7602-457 Communicating Programmable Thermostat Instruction Manual

mars 7602-457 Communicating Programmable Thermostat Instruction Manual

Installation Manual - 7602-457 Communicating, Programmable Thermostat  
NOTE 1: The Proportional Integral options require rst stage  
6.0 Humidity Conguration  
heating or cooling to be active for a minimum of 5 minutes,  
before energizing second stage when congured for multi  
stage operation.  
Congure humidity control settings (dehumidication/  
humidication).  
NOTE 2: The Differential option will activate rst stage heating  
or cooling when the temperature is more than the rst stage  
differential value (User Manual section 5.6.2.3), below or  
above the setpoint. Second stage heating or cooling will be  
activated when the temperature is more than the rst and  
second stage differential values combined (User Manual  
section 5.6.2.3), below or above the setpoint. Third stage  
heating will be activated when the temperature is more than  
the rst, second, and third stage differential values combined  
(User Manual section 5.6.2.3), below the setpoint.  
Adjust the Humidity Control settings using the up/down arrow  
buttons. Press the center button to save changes.  
Dehumidication – This logic will communicate  
a Dehumidication output when the humidity is  
greater than the setpoint (acts as a dehumidistat).  
The Dehumidication output will not be  
communicated when the humidity is below the  
setpoint.  
Humidication – This logic will communicate a  
Humidication output when the humidity is less  
than the setpoint (acts as a humidistat). When the  
Humidication output is active, the fan output will  
also be active. The Humidication output will not  
be communicated when the humidity is above the  
setpoint.  
7.2  
ANTICIPATOR  
If you nd that the thermostat is overshooting or  
undershooting the temperature setpoint value, the Anticipator  
setting allows for adjustment to correct the temperature  
algorithm. When the Anticipator value is set to a lower  
number, the thermostat becomes more sensitive and when  
the Anticipator value is raised, the thermostat becomes less  
sensitive. If the thermostat is overshooting the temperature  
setpoint, adjust the Anticipator value up to reduce thermostat  
sensitivity. If the thermostat is undershooting the temperature  
setpoint, adjust the Anticipator value down to increase  
thermostat sensitivity.  
Both – Incorporates both Dehumidication and  
Humidication logic.  
None (default) – Dehumidication  
and Humidication outputs will not be  
communicated.  
7.0 Temperature Algorithm  
TEMPERATURE CONTROL  
Adjust the Anticipator setting using the up/down arrow  
buttons. Press the center button to save changes.  
Anticipator (default 3): valid range: 1 to 9  
TEMPERATURE ALGORITHM  
ANTICIPATOR  
DIFFERENTIAL  
7.3  
DIFFERENTIAL  
CYCLES PER HOUR  
SMART HEAT STAGING  
ELECTRIC HEAT LOCKOUT  
The Differential adjustment will vary the number of degrees  
from the setpoint before a call for heating or cooling is made.  
Use this function if you nd that the thermostat is starting a  
call too soon/late or staging equipment up/down too quickly/  
slowly. For example, with a 1 ˚F 1st stage differential and  
a heating setpoint of 70˚F, your thermostat will not call for  
heating until the temperature is 69˚F.  
SELECT OPTION  
PREVIOUS  
SAVE  
7.1  
TEMPERATURE CONTROL  
Adjust the Differential setting using the up/down arrow  
buttons. Navigate between Differentials using the left/right  
arrow buttons. Press the center button to save changes.  
Congure the logic the thermostat uses to meet the  
temperature setpoints.  
Proportional Integral (default) – This logic will  
use a combination of temperature differential and  
operating time to determine the appropriate heating  
or cooling stages for operation (see NOTE 1).  
Proportional Integral (No Down Staging) – This  
logic includes the Proportional Integral logic, but  
in addition the logic keeps all active heating or  
cooling stages energized until the demand is fully  
satised (see NOTE 1).  
Differential – This logic will only use temperature  
differential to determine the appropriate heating or  
cooling stages for operation. This logic will keep  
all active heating or cooling stages energized until  
the demand is fully satised (see NOTE 2).  
7.4 CYCLES PER HOUR  
The thermostat allows the user to adjust the maximum  
number of on/off cycles per hour to maintain the desired  
indoor temperature.  
Adjust the Cycles per Hour setting using the up/down arrow  
buttons. Press the center button to save changes.  
4 (default): operation will start no sooner than 15  
minutes after the previous call was initiated  
6: operation will start no sooner than 10 minutes  
after the previous call was initiated (can provide  
tighter temperature control)  
11  
GeneralDetails
Namemars 7602-457 Communicating Programmable Thermostat Instruction Manual
MakeMARS
LanguageEnglish
FiletypePDF (Download)
File size0.49 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

mars 7602-457 Communicating Programmable Thermostat Instruction Manual