Installation Manual - 7602-457 Communicating, Programmable Thermostat  
2.2.1  
STAGING  
2.0 Installer Menu Settings  
Adjust the staging option using the up/down arrow buttons.  
Press the center button to save changes.  
2.1  
INSTALLER MENU SETTINGS ACCESS  
Single Stage – for control of a single stage  
compressor applications  
Multi-Stage (default) – for control of multi-  
stage compressor applications  
The Installer Settings can be accessed at any time from the  
Main Operating screen by holding the up/down arrows simul-  
taneously for 5 seconds while the thermostat is in OFF Mode.  
THERMOSTAT  
CONFIGURATION  
SINGLE STAGE  
MULTI STAGE  
Installer Menu Settings Overview  
Thermostat Conguration  
System Conguration  
Airow Selection  
SELECT OPTION  
PREVIOUS  
SAVE  
Option Selection  
2.2.2  
AUXILIARY HEAT  
Unit Conguration  
Pump Conguration  
Valve Conguration  
Accessory Conguration  
Air Filter  
Adjust the Auxiliary Heat options using the up/down arrow  
buttons. Press the center button to save changes.  
Electric (default) – for control of a system with  
electric auxiliary heat  
Multi-Fuel – for control of a system with furnace  
for auxiliary heat  
No Auxiliary Heat – for control of a system with no  
auxiliary heat  
Humidier  
UV Lamp  
Air Cleaner  
Input Dealer Information  
Humidity Conguration  
Temperature Algorithm  
Demand Reduction Conguration  
Service Mode  
THERMOSTAT  
CONFIGURATION  
ELECTRIC  
Manual Operation  
Control Diagnostics  
Dipswitch Conguration  
Fault History  
MULTI FUEL  
Clear Fault History  
Restore Defaults  
NO AUXILIARY HEAT  
2.2  
THERMOSTAT CONFIGURATION  
SELECT OPTION  
PREVIOUS  
SAVE  
Upon initial power up, the communicating thermostat will  
prompt the installer for the thermostat conguration settings.  
2.2.2.1 AUXILIARY HEAT CONFIGURATION  
Select Electric Auxiliary Heat mode  
Model number and software version of thermostat and  
software version of connected DXM2 are also displayed on  
this screen.  
Auxiliary Heat to Supplement Pump  
Auxiliary Heat for Emergency Heat Only  
THERMOSTAT  
INSTALLER SETTINGS  
THERMOSTAT CONFIG  
SYSTEM CONFIG  
CONFIGURATION  
ACCESSORY CONFIG  
INPUT DEALER INFO  
HUMIDITY CONFIG  
AUXILIARY HEAT TO  
SUPPLEMENT HEAT PUMP  
TEMPERATURE CONTROL  
DEMAND REDUCTION CNFG  
SERVICE MODE  
AUXILIARY HEAT FOR  
EMERGENCY HEAT ONLY  
SETPOINT LIMITS  
RESTORE DEFAULTS  
DXM2  
3.3  
C 1.0  
SELECT OPTION  
PREVIOUS  
7602-457  
SELECT OPTION  
PREVIOUS  
SAVE  
6
GeneralDetails
Namemars 7602-457 Communicating Programmable Thermostat Instruction Manual
MakeMARS
LanguageEnglish
FiletypePDF (Download)
File size0.49 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

mars 7602-457 Communicating Programmable Thermostat Instruction Manual