mars 7602-457 Communicating Programmable Thermostat Instruction Manual

Installation Manual - 7602-457 Communicating, Programmable Thermostat  
ѥꢀCAUTION! ѥ  
3.4  
PUMP CONFIGURATION  
vFlow™ vs internal ow control pump can be controlled either  
through temperature differential (Delta T) or can be set to  
specic speed (xed; % of full speed for each heat and cool  
stage).  
CAUTION! This is a Commercial option only and does not  
alter Residential unit operation.  
OPTION SELECTION  
MOTORIZED VALVE  
OFF  
5
Can be congured for either single pumping or parallel  
pumping.  
Congure temperature differentials at the thermostat for  
vFlow™ units with an internal ow control pump.  
COMPRESSOR ASCD  
Adjust the Pump Conguration settings using the up/down  
arrow buttons. Press the center button to select each item.  
Heating Delta T (default stored in control) –  
valid range: 4 to 12ºF (in 1ºF increments)  
Cooling Delta T (default stored in control) –  
valid range: 9 to 20ºF (in 1ºF increments)  
PREVIOUS  
NEXT  
3.3  
UNIT CONFIGURATION  
Adjust the Unit Conguration settings including Heat  
Pump Family, Heat Pump Size, Blower Type, and Loop  
Conguration using the up/down arrow buttons. Press the  
center button to select each item.  
Maximum Heat LWT (valid range based on specic model;  
refer to model IOM). Minimum Cool LWT (valid range based  
on specic model; refer to model IOM).  
Heat Pump Family (default stored in control) –  
valid range: TE, TY, TES, TEP, TRT, TSM  
NOTE: Refer to section 3.6.3 for multi-unit conguration  
instructions.  
Heat Pump Size (default stored in control) –  
valid range: depends on Heat Pump Family setting  
Blower Type (default stored in control) – valid  
range: NO BLOWER, 2-SPD PSC, COM ECM-V,  
1-SPD PSC, 2-SPD CTM, PWM ECM, VFD  
Loop Cong (default stored in control) – valid  
range: Other, VS PUMP, MOD VALVE  
VARIABLE SPD INTERNAL  
PUMP CONFIGURATION  
LOOP OPTION  
PARALLEL  
DELTA T  
PUMP CONTROL  
HEATING DELTA T  
COOLING DELTA T  
7 F  
10 F  
Airow, pump and valves can be congured from ‘System  
Conguration’ screen.  
MAXIMUM HEAT LWT  
MINIMUM COOL LWT  
80 F  
40 F  
Select ‘VS PUMP’ when applying an internal variable speed  
ow controller with other ow controllers on a single loop in  
parallel.  
PREVIOUS  
SELECT  
NOTE: Refer to section 3.6.3 for multi-unit conguration  
instructions.  
To control vs pump by xed speed, select ‘Pump Control’,  
press , use down arrow to select ‘Fixed’, and press to  
save.  
UNIT CONFIGURATION  
CURRENT CONFIG  
HEAT PUMP FAMILY  
HEAT PUMP SIZE  
BLOWER TYPE  
TE026  
TE  
Default stored in control. Valid range: 15% - 90% (in 1%  
increments)  
Heating Stage 1  
Heating Stage 2  
Cooling Stage 1  
Cooling Stage 2  
026  
ECM  
If Loop Option is set to ‘PARALLEL’, valid range changes to  
50-90% (in 1% increments).  
LOOP CONFIG  
VS PUMP  
Equivalent Model Numbers  
Heat Controller Climate Master  
SELECT OPTION  
PREVIOUS  
SAVE  
HE-Series  
TZ  
HZ-Series  
TE  
HZS-Series  
TES  
TC  
HB-Series 0.5-5T  
HB-Series 7-25T  
HKV-Series  
TL  
TL  
HRC-Series  
TRC  
8
GeneralDetails
Namemars 7602-457 Communicating Programmable Thermostat Instruction Manual
MakeMARS
LanguageEnglish
FiletypePDF (Download)
File size0.49 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

mars 7602-457 Communicating Programmable Thermostat Instruction Manual