SPECIFICATIONS  
Size  
ALL REGIONS  
024  
036  
048  
060  
Nominal Tonnage  
Sound Rating Number Range  
2
3
4
5
67-79  
3/8  
dBA  
Liquid line (OD) - in.  
Suction line (OD) - in.  
67-70  
66-76  
72-76  
Connections  
(Sweat)  
3/8  
3/8  
3/8  
3/4  
7/8  
7/8  
1-1/8  
Variable Scroll  
9 lbs. 10 oz.  
26Z72  
23.33  
22.60  
5/16  
Compressor Type  
Refrigerant  
Variable Rotary  
Variable Rotary  
Variable Rotary  
1 R-454B charge furnished  
6 lbs. 3 oz.  
26Z70  
23.63  
- - -  
6 lbs. 7 oz.  
26Z70  
23.63  
- - -  
9 lbs. 8 oz.  
26Z71  
23.63  
22.79  
5/16  
2
Indoor Unit Expansion Valve (TXV)  
Outdoor  
Coil  
Net face area - ft.2 Outer coil  
Inner coil  
Tube diameter - in.  
Rows  
5/16  
1
5/16  
1
2
Fins - in.  
HP  
22  
22  
22  
22  
Outdoor  
Fan  
1/8  
1/3  
1
/
4
1/3  
Diameter - in.  
Blades  
22  
22  
22  
26  
2
4
4
3
Cfm  
2840  
825  
130  
250  
3955  
300 - 1200  
258  
3660  
825  
4180  
300 - 1200  
201  
Rpm  
Watts  
290  
Shipping Data - lbs.  
265  
270  
270  
ELECTRICAL DATA  
Line voltage data (Volts-Phase-Hz)  
2 Maximum overcurrent protection (MOCP) amps  
3 Minimum circuit ampacity (MCA)  
208/230-1-60  
208/230-1-60  
208/230-1-60  
208/230-1-60  
25  
15  
35  
50  
60  
23.4  
15.8  
2.6  
28.7  
20.5  
1.7  
36.5  
25.7  
2.6  
Rated load amps  
Full load amps  
10.8  
0.74  
Compressor  
Fan Motor  
OPTIONAL CONTROLS - ORDER SEPARATELY  
S40 Smart Wi-Fi Thermostat  
⁴ Discharge Air Temperature Sensor  
E30 Smart Wi-Fi Thermostat  
22V24  
88K38  
20A65  
•
•
•
•
•
•
•
•
•
•
•
•
OPTIONAL ACCESSORIES - ORDER SEPARATELY  
⁵ Freezestat  
3/8 in.  
3/8 x 3/4 | 3/8 | 20 ft.  
3/8 x 3/4 | 3/8 | 30 ft.  
3/8 x 3/4 | 3/8 | 40 ft.  
3/8 x 3/4 | 3/8 | 50 ft.  
3/8 x 7/8 | 3/8 | 30 ft.  
3/8 x 7/8 | 3/8 | 40 ft.  
3/8 x 7/8 | 3/8 | 50 ft.  
3/8 x 1-1/8 | 3/8 | 50 ft.  
93G35  
89J56  
89J57  
89J58  
89J59  
89J60  
89J61  
89J62  
73P91  
•
•
•
•
•
•
Refrigerant  
Line Sets  
•
Liquid x Suction OD |  
Insulation Thickness |  
Length  
•
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.  
1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the Installation Instructions for information about line set length and  
additional refrigerant charge required.  
2 HACR type breaker or fuse.  
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.  
4 Used with the Lennox® S40 Smart Wi-Fi Thermostat for optional service diagnostics.  
5 Freezestat is recommended for low ambient operation.  
EL18KCV | 2 to 5 Ton Air Conditioner | Page 8  
GeneralDetails
NameLENNOX EL18KCV Smart Wi-Fi Communicating Thermostat User Manual
MakeLennox
LanguageEnglish
FiletypePDF (Download)
File size2.82 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
LENNOX L40 Smart Thermostat Owner’s Manual
LENNOX L40 Smart Thermostat Owner’s Manual
LENNOX S40 Smart Thermostat User Guide
LENNOX S40 Smart Thermostat User Guide

LENNOX EL18KCV Smart Wi-Fi Communicating Thermostat User Manual