Home > EPH CONTROLS > EPH CONTROLS RDT Recessed Room Thermostat Installation Guide
EPH CONTROLS RDT Recessed Room Thermostat Installation Guide
P01 Operating Mode continued
Delay Start Control (On/Off) Continued
Delay start can be reactivated by:
1. Press
2. Press
3. Press
to lower the target below the current temperature.
to confirm.
to increase the target temperature above the zone
temperature within 6°C .
4. Press to confirm.
The heating will be delayed as per the graph on page 15.
If the difference between the actual temperature and the target is 1°C
the thermostat will delay starting for circa 40 minutes.
If the difference between the actual temperature and the target is 3°C
the thermostat will delay starting for circa 24 minutes.
If the difference is 6°C or more then the thermostat will be switched on
immediately.
The time delay will change if the temperature drops from the original
calculation.
16
RDT
| General | Details |
|---|---|
| Name | EPH CONTROLS RDT Recessed Room Thermostat Installation Guide |
| Make | EPH CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.57 MB |

EPH CONTROLS eTRV-HW Smart Cylinder Thermostat User Guide

EPH CONTROLS eTRV-HW Smart Hot Water Thermostat Instruction Manual

EPH CONTROLS eTRV Smart Radiator Thermostat Instruction Manual

EPH CONTROLS CDTP2 Hardwired Room Thermostat Instruction Manual

EPH CONTROLS 20221026 RFRA – RF Room Thermostat Instruction Manual

EPH Controls CDT2-24 24V Room Thermostat Installation Guide

EPH CONTROLS RFCA RF Cylinder Thermostat Instruction Manual

EPH CONTROLS PR092K7 RF Cylinder Thermostat Instruction Manual

EPH CONTROLS COMBIPACK2 Smart Thermostat with Automation and Optimum Start Instructions

EPH CONTROLS CRT2 Room Thermostat Instruction Manual