Home > EMOS > emos P5684 Capillary Sensor Thermostat User Manual

emos P5684 Capillary Sensor Thermostat User Manual

switched load listed in technical specifications! The manufacturer is  
not liable for inexpert installation.  
GB | Capillary Sensor Thermostat  
Putting the Device into Operation  
Connect the thermostat with pump according to instructions.  
Connect the thermostat to 230 V power supply.  
Short-press the button.  
The currently set mode and heating/cooling mode setting will flash  
on the display (e.g.: F1/C1).  
Properties  
capillary sensor thermostat (0.9 m, Ø 6 mm)  
5–90 °C temperature range (0.1 °C resolution)  
simple electrical connection via screwless terminals  
Specifications  
Then, the current temperature will be displayed.  
Switched load: max. 230 V AC; 5 A for resistive load;  
1.5 A for inductive load  
Temperature Setting  
Set your temperature of choice by repeatedly pressing the up  
Power supply: 230 V AC  
Temperature control range: 5–90 °C  
Temperature measurement: 5 °C to 90 °C with 0.1 °C resolution;  
accuracy 1.5 °C  
Temperature setting: 5 °C to 90 °C in 0.1 °C increments  
Hysteresis setting: 0.1 °C to 15 °C with 0.1 °C resolution  
Enclosure: IP40  
/down  
arrow.  
Holding the arrow adjusts value faster.  
Once temperature is set, wait several seconds until the value is  
automatically saved.  
The display will then automatically show the current measured  
temperature.  
To check your temperature setting, press the up or down arrow once.  
Example: with temperature set to 50 °C, press the up or down arrow  
once. The display will show C 50.0.  
Thermostat Description  
(see Fig. 1)  
1 – activation indicator LED  
2 – display  
3 – up arrow (increase value)  
4 – down arrow (decrease value)  
5 – on/off/function setting button  
6 – screws  
Selecting Heating or Cooling Mode  
Enter settings by long-pressing the down arrow  
mately 3 seconds.  
for approxi-  
Use the arrows to choose between heating mode (C1 on the display)  
or cooling mode (C2 on the display).  
7 – capillary sensor  
Once temperature is set, wait several seconds until the value is  
automatically saved.  
The display will then automatically show the current measured  
temperature.  
Installation  
Mount the thermostat onto any section of the pipe and secure the  
external sensor onto the surface of the water delivery system the  
sensor is to measure. Make sure the sensor is in direct and safe  
contact with the surface. (Before securing the sensor, it is necessary  
to remove all insulation from the spot where it will be installed.)  
Differences for cooling mode:  
Switching in cooling mode is reversed: The thermostat switches  
the system when the measured temperature is higher than the  
set temperature.  
Electrical Connection  
1. Remove the 2 screws on the front housing of the thermostat.  
2. Carefully remove the front housing.  
Hysteresis  
Hysteresis is the difference in temperature required for switching  
on and off.  
3. Connect in accordance with the following diagram (see Fig. 2):  
Pump  
Power – 230 V  
If, for example, you set the temperature in heating mode to 42.5 °C  
and the hysteresis value to 2.5 °C, the thermostat will activate your  
system as soon as the measured temperature drops to 40 °C and  
deactivate it when temperature reaches 42.5 °C.  
Jump – jumper  
PE – protective earth, prevents injury by electrical current  
4. The thermostat features a screwless conductor connection.  
Press downwards onto the top plastic connector with e.g. a  
screwdriver. The terminal contact will release. Plug in the  
conductor. Repeat the process for all conductors needed for  
connection. Replace the screws.  
Enter settings by long-pressing the up arrow  
3 seconds.  
for approximately  
Set your hysteresis value of choice by repeatedly pressing the up  
/down arrow.  
Holding the arrow adjusts value faster.  
Once the value of choice is set (e.g. 2.5 °C, displayed as d 2.5) wait a  
few seconds until the setting is automatically saved.  
The display will then automatically show the current measured  
temperature.  
The device may only be installed by a professional plumber in  
accordance with the connection diagram. In addition, the connection  
must meet up-to-date, valid standards and specifications of your  
energy provider. Installation must always be performed when power  
is turned off; follow safety specifications. Maintain the maximum  
3
GeneralDetails
Nameemos P5684 Capillary Sensor Thermostat User Manual
MakeEMOS
LanguageEnglish
FiletypePDF (Download)
File size0.3 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
EMOS P56201BUF Floor Heating Thermostat User Guide
EMOS P56201BUF Floor Heating Thermostat User Guide
emos P56201 Digital Room Thermostat User Manual
emos P56201 Digital Room Thermostat User Manual
EMOS P56201UF Floor Heating Thermostat Instruction Manual
EMOS P56201UF Floor Heating Thermostat Instruction Manual
emos P5604 Thermostat Instruction Manual
emos P5604 Thermostat Instruction Manual
emos P5686 Immersion Thermostat Instructions
emos P5686 Immersion Thermostat Instructions
EMOS P56211 Wireless Thermostat Instruction Manual
EMOS P56211 Wireless Thermostat Instruction Manual
emos P5616OT Wireless Thermostat Instruction Manual
emos P5616OT Wireless Thermostat Instruction Manual
emos P56201UF GoSmart Digital Room Thermostat Instruction Manual
emos P56201UF GoSmart Digital Room Thermostat Instruction Manual
EMOS P5601UF Floor Heating Thermostat User Manual
EMOS P5601UF Floor Heating Thermostat User Manual
emos P56211 Wireless Room Thermostat Instruction Manual
emos P56211 Wireless Room Thermostat Instruction Manual

emos P5684 Capillary Sensor Thermostat User Manual