Home > EcoNet > EcoNet RETST800SYS Smart Thermostat User Guide

EcoNet RETST800SYS Smart Thermostat User Guide

AC/HP Settings  
Installer Settings  
Go to Menu > Settings > Installer (tap and hold) > AC/HP.  
Thermostat  
Furnace  
AC/HP  
Air Handler  
Defaults  
Warning! These settings are to be used  
by a qualified HVACcontractor ONLY  
BACK  
Outside Unit Selection – Chooses outdoor unit type:  
AC/HP Settings  
Outside Unit Selection  
EcoNet (locked)  
Var-Speed Clamp  
7000  
None  
No  
• Non-communicating – Allows you to manually enter settings for your  
outdoor unit. If “non-communicating” outdoor unit is selected, change  
the type (AC or HP), number of stages (1 or 2) and size (Tons) to match  
the Outdoor Unit information.  
Cool Airflow Adjust  
Utility Input Enabled?  
Heat Source  
No  
Furnace Lock Out Above  
Disabled  
Heat Pump Locked Out Below Disabled  
BACK  
• EcoNet (locked) – Displays “EcoNet” if a communicating EcoNet Enabled  
outdoor unit is discovered. The selection cannot be changed (locked).  
• None – Lets the system know that there is no outdoor unit present.  
Note: Outside Unit Selection is only applicable for furnace installations.  
Var-Speed RPM Clamp - Allows reduction of the maximum compressor  
speed. Can be used to reduce outdoor unit operating noise or indoor blower  
airflow. This will also reduce the operating capacity.  
Cool/Heat Airflow Adjust – Controls airflow adjustment in cooling and heat  
pump heating, None (default), High (+10%), Low (-10%).  
Utility Input Enabled? – If the system is using a “load shedding” device  
provided by the utility company set to ‘Yes’. The device must be connected  
to terminal U2 & U on the VSODU. Once the dry contacts are connected  
(non-powered) between U2 and U, change the setting to ‘Yes’. When set to  
Yes’ the system will not start the condenser when the connection from U2 to  
U is open.  
Heat Source – Allows selection of using just the furnace, or heat pump, as the  
sole heat source in a dual-fuel installation. If “Both” is selected, the system will  
stage up and down normally using the heat pump for initial heat stages, and  
then the furnace as auxiliary heat.  
Furnace Locked Out Above – Select the outside temperature above which  
the furnace or supplemental electric heat will not run when matched with  
a heat pump. The default is disabled and the temperature can be adjusted  
between 0-55°F.  
Heat Pump Locked Out Below – Selects the outside temperature below  
which the Heat Pump will not operate and your system will rely exclusively on  
the furnace or auxiliary heat source. This should be determined by evaluating  
the regions Heat Pump Balance point. If a non-communicating outdoor unit  
is paired with a Econet enabled furnace an OAT sensor (RXGY-J02) or the  
Econet internet sensor option must be used to lock out the heat pump when  
only furnace operation is desired.  
Note: A difference of two degrees will be enforced between the furnace and heat pump. Lockout  
temperatures will be based off the outdoor temperature sensor connected to the outdoor unit and  
NOT off the temperature provided under weather. In some instances internet connections may be  
intermittent and an OAT sensor would be the most valid option.  
> Return to Table of Contents  
EcoNet® Smart Thermostat User Guide 30  
GeneralDetails
NameEcoNet RETST800SYS Smart Thermostat User Guide
MakeEcoNet
LanguageEnglish
FiletypePDF (Download)
File size6.45 MB
Download PDF