Configuration  
STEP 10 Discharge Air Low Limit: Enter a discharge air low limit value.  
NOTE: This screen appears only if the discharge air sensor  
function is enabled (Step 7).  
DSCHRGE AIR ECON  
LOW LIMIT  
040F  
STEP 11 Economizer Proportional Band: Set the discharge air  
proportional band or throttling range.  
DSCHRGE AIR ECON  
PROP BAND: 010F  
NOTE: This screen appears only if the discharge air sensor  
function is enabled (Step 7).  
STEP 12 Outdoor Air Damper Minimum Position: Set the minumum  
damper position.  
OUTDOOR DAMPER  
NOTE: This screen appears only if the discharge air sensor  
function is enabled (Step 7).  
MIN POSITION 20%  
STEP 13 Economizer Output Range: Select whether the economizer  
output range will be 0 – 20 mA or 4 – 20 mA.  
ECON OUTPUT  
NOTE: This screen appears only if the discharge air sensor  
function is enabled (Step 7).  
RANGE:  
4-20 MA  
STEP 14 Economizer Control Action: Select whether the economizer  
control action will be direct or reversing.  
ECON CONTROL  
NOTE: This screen appears only if the discharge air sensor  
function is enabled (Step 7).  
ACTION:  
DIRECT  
STEP 15 Outdoor Air Sensor Function: Select whether you are using  
an outdoor air sensor. To monitor only, select NO.  
ENABLE OUTDOOR  
NOTE: Refer to the SZ1051/1053 SuperSTAT Installation  
Manual for dip switch settings, which must also be set.  
AIR FUNCT? YES  
STEP 16 Cooling Lockout: Enter an outdoor air cooling lockout  
temperature.  
COOLING LOCKOUT  
NOTE: This screen appears only if the outdoor air sensor  
function is enabled (Step 15).  
TEMP  
60F  
STEP 17 Heating Lockout: Enter an outdoor air heating lockout  
temperature.  
HEATING LOCKOUT  
NOTE: This screen appears only if the outdoor air sensor  
function is enabled (Step 15).  
TEMP  
70F  
Digital Inputs  
STEP 1 DI1: Select either FAN PROVING or MONITOR. If DI1 is unused,  
select MONITOR.  
DI1 USED FOR  
MONITOR  
STEP 2 DI2: Select SERVICE, AQUASTAT, or MONITOR. If DI2 is  
DI2 USED FOR  
MONITOR  
unused, select MONITOR.  
9
2800 Laura Lane Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com  
GeneralDetails
NameTCS SZ1051 Communicating Thermostat User Guide
MakeTCS
LanguageEnglish
FiletypePDF (Download)
File size0.28 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

TCS SZ1051 Communicating Thermostat User Guide