Configuration  
STEP 11 Occupied Cool Setpoint D: Set the cooling setpoint for this  
OCCUPIED COOL  
occupied period.  
SETPOINT D: 75F  
STEP 12 Unoccupied Cool Setpoint: Set the Unoccupied Mode’s  
UNOCCUPIED COOL  
cooling setpoint.  
SETPOINT:  
80F  
STEP 13 User Setpoint Limit: Enter the amount a user is allowed the  
LIMIT SETPOINT  
to adjust the preset occupied setpoints  
ADJUST +/- 05F  
STEP 14 Override Time: The number of minutes (0 – 255) the  
SET OVERRIDE  
SuperSTAT will maintain overridden occupied setpoints.  
TIME 180 MINUTES  
Heat/Cool Digital Outputs  
STEP 1 Stage Output: Select whether stages 1 and 2 perform heating  
or cooling, or whether both are disabled.  
STAGE OUTPUT 1&2  
AS:  
COOL  
00F  
01F  
00F  
01F  
P
STEP 2 Stage 1 Offset: Enter a stage 1 offset value (normally 0).  
NOTE: This screen will only display if Stage Output (Step 1)  
is enabled.  
STAGE 1  
OFFSET:  
STEP 3 Stage 2 Differential: Enter a stage 1 differential value. NOTE:  
This screen will only display if Stage Output (Step 1) is  
enabled.  
STAGE 1  
DIFF:  
STEP 4 Stage 2 Offset: Enter a stage 2 offset value (normally 0).  
NOTE: This screen will only display if Stage Output (Step 1)  
is enabled.  
STAGE 2  
OFFSET:  
STEP 5 Stage 2 Differential: Enter a stage 2 differential value. NOTE:  
This screen will only display if Stage Output (Step 1) is  
enabled  
STAGE 2  
DIFF:  
STEP 6 Control Mode: Select whether to control both Stage Outputs  
SET CONTROL  
MODE:  
by temperature only (P) or whether to add a time factor (P+I).  
7
2800 Laura Lane Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com  
GeneralDetails
NameTCS SZ1051 Communicating Thermostat User Guide
MakeTCS
LanguageEnglish
FiletypePDF (Download)
File size0.28 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

TCS SZ1051 Communicating Thermostat User Guide