TCS SZ1051 Communicating Thermostat User Guide
Configuration
STEP 11 Occupied Cool Setpoint D: Set the cooling setpoint for this
OCCUPIED COOL
occupied period.
SETPOINT D: 75F
STEP 12 Unoccupied Cool Setpoint: Set the Unoccupied Mode’s
UNOCCUPIED COOL
cooling setpoint.
SETPOINT:
80F
STEP 13 User Setpoint Limit: Enter the amount a user is allowed the
LIMIT SETPOINT
to adjust the preset occupied setpoints
ADJUST +/- 05F
STEP 14 Override Time: The number of minutes (0 – 255) the
SET OVERRIDE
SuperSTAT will maintain overridden occupied setpoints.
TIME 180 MINUTES
Heat/Cool Digital Outputs
STEP 1 Stage Output: Select whether stages 1 and 2 perform heating
or cooling, or whether both are disabled.
STAGE OUTPUT 1&2
AS:
COOL
00F
01F
00F
01F
P
STEP 2 Stage 1 Offset: Enter a stage 1 offset value (normally 0).
NOTE: This screen will only display if Stage Output (Step 1)
is enabled.
STAGE 1
OFFSET:
STEP 3 Stage 2 Differential: Enter a stage 1 differential value. NOTE:
This screen will only display if Stage Output (Step 1) is
enabled.
STAGE 1
DIFF:
STEP 4 Stage 2 Offset: Enter a stage 2 offset value (normally 0).
NOTE: This screen will only display if Stage Output (Step 1)
is enabled.
STAGE 2
OFFSET:
STEP 5 Stage 2 Differential: Enter a stage 2 differential value. NOTE:
This screen will only display if Stage Output (Step 1) is
enabled
STAGE 2
DIFF:
STEP 6 Control Mode: Select whether to control both Stage Outputs
SET CONTROL
MODE:
by temperature only (P) or whether to add a time factor (P+I).