Home > TCS > TCS SZ1051 Communicating Thermostat User Guide

TCS SZ1051 Communicating Thermostat User Guide

Configuration  
Program Setup Mode  
Before entering PROGRAM SETUP Mode, ensure that the temperature sensor dip switch settings match your intended  
use (see the SZ1051/1053 SuperSTAT Installation Manual). If the dip switch settings do not match the configuration  
settings in this section, the SuperSTAT will not function properly.  
NOTE: PROGRAM SETUP Mode can be disabled via dip switch settings (see “Programming Keypad Access” on page  
4, or access can be restricted by requiring an access code (see “Keypad Access Code” on page 10).  
The main screen displays when not in PROGRAM SETUP Mode or  
CLOCK SETUP Mode. The SuperSTAT will revert to this screen if no  
entries are made after 10 minutes.  
TUE  
07-04-23  
72F  
From the main screen, press the PROGRAM SETUP button on the  
keypad to configure the settings.  
9:00 AM  
If the SuperSTAT has been configured to require an access code to  
enter PROGRAM SETUP Mode, this screen will appear (see “Keypad  
Access Code” on page 10). If you enter the wrong code, the screen  
will revert to the main screen.  
ENTER ACCESS  
CODE  
000  
Basic Setup  
STEP 1 Controller Address: Select a unique address between 0 and  
255, excluding 248 (each controller on a network must have a  
unique address).  
SET ADDRESS:  
SET BAUD RATE  
TEMP SHOWN IN:  
000  
STEP 2 Communication Baud Rate: Choose a baud rate between  
2.4K, 4.8K, 9.6K, and 19.2K (each controller on network must  
have the same baud rate).  
9.6K  
STEP 3 Temperature Scale: Choose between Celsius or Fahrenheit  
for temperature display.  
FAHRENHEIT  
System Mode  
STEP 1 System Access: Select whether to enable or disable user  
access to the System Mode settings.  
USER ACCESS TO  
SYSTEM MODE? YES  
STEP 2 Set System Mode: Select AUTO, HEAT, COOL, or OFF mode.  
SET SYSTEM  
MODE:  
AUTO  
STEP 3 User Access to Fan Mode: Select whether to allow user  
USER ACCESS TO  
FAN MODE?  
access to FAN MODE.  
YES  
5
2800 Laura Lane Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com  
GeneralDetails
NameTCS SZ1051 Communicating Thermostat User Guide
MakeTCS
LanguageEnglish
FiletypePDF (Download)
File size0.28 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

TCS SZ1051 Communicating Thermostat User Guide