SIEMENS RDG200KN Room Thermostat Instruction Manual
Operating Instructions en
RDG200KN
RDG260KN
RDG2..KN – Room thermostat with KNX communications allowing users to set both
ideal temperature and relative humidity. The thermostat offers the operating
modes Comfort, Economy and Protection.
In addition, it can operate in Auto mode as per a schedule via KNX bus or local.
The fan operates either in Auto mode or at the selected speed in Manual mode.
Users can either use the factory settings or adjust settings as desired.
Main display
Operating mode
Holiday mode
Operating mode selection *
Scheduler
Protection mode
Economy mode
Comfort mode
Fan speed selection
Escape
Delete schedule
Cooling mode
Confirm parameters
Electric heater active
Heating mode
Number of schedules or slave
alarms
Scheduler mode
Manual changeover
Outside temperature
Time bar for schedule
Auto mode
Additional user information, such as outside
temperature, time of day from KNX bus, relative humidity
Temporary timer
Morning: 12-hour format;
Afternoon: 12-hour format
Fault
Condensation in room
(dewpoint sensor active) or
humidity control active
Relative humidity
Degrees Celsius or Fahrenheit
Value with thermometer: Digits for room temperature
display
Button lock
Digits for setpoint display
Automatic fan
Fan speed I
Operating mode button *
Parameter
Fan mode button
Rotary knob
Fan Speed II
Fan Speed III
Green leaf
Protection hospitality mode button
* When P002 = 3 and P009 = 1, the icon is displayed as
and the button can be used to switch unit between °C and °F.
This function is available from product index C or a higher version (scan the above QR code for the latest version info).
Changing the room temperature
Turn the rotary knob clockwise to increase, or counterclockwise to decrease the
current room temperature setpoint.
Note: The setting range is 5...40 °C; it can be limited by parameters P013 and P016.
(for parameter settings, see Control parameters on page 2).
Adjusting the fan speed
Press the right button repeatedly until the desired fan mode is reached.
In Auto mode , the fan speed is automatically selected by the thermostat
depending on setpoint and current room temperature.
In Manual mode, the fan operates independently and runs at the speed set by
the user: speed I / speed II / speed III.
Speed
I
Speed Speed
II III
Changing the operating mode
1. Comfort mode
In Comfort mode, the thermostat maintains the room temperature at the setpoint
which can be adjusted with the rotary knob.
2. Economy mode
In Economy mode, the thermostat maintains the room temperature at a lower or
higher setpoint, thus saving energy and money.
The thermostat can be set to Economy mode either by pressing the operating
mode button if enabled (P002 = 2), or via an external signal (switch or KNX bus
command) such as keycard or presence detector.
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.
They can be adjusted via parameters P019 and P020 (for parameter settings, see
Control parameters on page 2).
3. Protection mode
In Protection mode, the thermostat stops operating. However, if the room
temperature drops below 8 °C, heating is switched on to protect the room against
frost.
The thermostat switches to Protection mode when the window contact (local or on
KNX) is activated.
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: Frost protection: _________ ˚C
Heating protection: __________˚C
4. Auto mode
In Auto mode, the thermostat automatically switches over between Comfort and
Economy mode as per the KNX bus or local schedule (enabled via P005).
If no schedule is available, Comfort replaces Auto.
Important: If setpoints are set to Off, there is no protective heating or cooling function. Risk of frost!
Green leaf indication
The green leaf indication is an energy-efficient setting and indicates the end user settings.
Red leaf: Settings exceed the preset
Green leaf: Settings are within the
preset energy-efficient range.
energy-efficient range.
End users can press the red leaf and
return to the energy-efficient range.
Reminder to clean filter, display of external faults
This message reminds you to clean the filter on your HVAC equipment.
It appears after _______ "fan operating hours" and disappears when the thermostat is
set to Protection.
These fault messages tell you an external fault has occurred **:
FIL **
AL1 **
AL2 **
AL3 **
AL1 : _______________________
AL2 : __________________________
AL3 : _______________________
** Needs to be configured by HVAC installer
Scheduler
Set schedule
Press button
programming mode PROG.
once and then turn the rotary knob or press button
continuously to select
Press button once to enter scheduler mode
.
Turn the rotary knob to select the weekday to be set, then press button once.
Turn the rotary knob to view existing schedules, then press button once to select the schedule
that need to be edited.
Comfort mode setting of selected schedule and icons
once. The start time for Comfort flashes and can be changed by turning the rotary knob.
Press button once to confirm the adjusted value and enter the Economy mode setting for the
and
are displayed, then press button
schedule. Icons
and
are displayed, then press button once. The start time for Economy
flashes and can be changed by turning the rotary knob.
Press button once to confirm the adjusted value. Then users can view other schedules by turning
the rotary knob and enter other schedule settings (same as edited schedule).
Note: User can press button
schedule is three per day.
to delete any schedule or
(Esc) to cancel the change. The maximum number of set
| General | Details |
|---|---|
| Name | SIEMENS RDG200KN Room Thermostat Instruction Manual |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.24 MB |

SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual

SIEMENS RDG400 Room Thermostat Instruction Manual

SIEMENS M3182 Room Thermostat Instruction Manual

SIEMENS RDS120-B Smart Thermostat Instructions

SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual

SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual

SIEMENS RDH100RF/SET Room Thermostat Instruction Manual

SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide

SIEMENS RS485 Flush Mounted Room Thermostat User Manual

SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS RDG200KN Room Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Operating instructions for RDG200KN and RDG260KN room thermostats with KNX communications allow users to set ideal temperature and relative humidity. The thermostat offers operating modes: Comfort, Economy, Protection, and Auto mode based on a schedule. Users can adjust settings or use factory settings. The main display includes information on operating modes, fan speed selection, and outside temperature. Changing the room temperature is done via a rotary knob with a range of 5 to 40 °C. In Comfort mode, the thermostat maintains the room temperature at the setpoint. Economy mode saves energy by maintaining a lower or higher setpoint. Protection mode activates heating if the room temperature drops below 8 °C to prevent frost. Auto mode switches between Comfort and Economy based on a schedule. The green leaf indication shows energy-efficient settings, while the red leaf indicates settings exceeding the preset range.
- Page 2: Set time by pressing the button to enter programming mode. Select time format and AM or PM using the rotary knob. Enter the hour setting, which flashes for adjustment. Confirm the hour value and proceed to set the minutes. Set date by entering programming mode and selecting month, weekday, and year. Adjust holiday mode by entering scheduler mode and setting start time. The button lock function can be enabled to lock or unlock buttons. Commissioning should be performed by a qualified HVAC installer to optimize control performance. Control parameters can be adjusted during operation via buttons or a commissioning tool. Password protection may be enabled for parameter setting mode, requiring a password to access.