Set TIME  
Press button  
programming mode TIME.  
once and then turn the rotary knob or press and hold button  
to select  
Press button once and then turn the rotary knob to select time format.  
Press button once and then turn the rotary knob to select AM or PM.  
Press button once and enter the hour setting.  
The hour value flashes and can be changed by turning the rotary knob.  
Press button once to confirm the adjusted value and enter the minutes setting.  
Repeat the steps as for the hour.  
Set DATE  
Press button  
programming mode DATE.  
once and then turn the rotary knob or press and hold button  
to select  
Press button once to enter date setting.  
Turn the rotary knob to select month / weekday / year, then press button once.  
For example, enter the year setting. The Year value flashes and can be changed by turning the  
rotary knob.  
Press button to confirm the adjusted value, or (Esc) to cancel the change.  
Repeat steps for month and weekday settings.  
Set AWAY (Holiday mode)  
Press button  
once and then turn the rotary knob or press and hold button  
to select  
programming mode AWAY. Holiday mode  
is displayed.  
Press button once to enter scheduler mode  
Turn the rotary knob to adjust the holidays, then press button once.  
Set the start time (AWAY): Set the month (MON) and then press button Set the day (DATE)  
Press button once to confirm the adjusted value; the idle page for Holiday mode is displayed.  
.
Button lock  
If the button lock function is enabled (parameter P028 = 2), pressing the right  
button for 3 seconds locks or unlocks the buttons respectively.  
Locked buttons are indicated by the key symbol  
.
If “Auto lock” is configured (P028 = 1), the thermostat automatically locks the  
buttons 10 seconds after the last adjustment.  
Commissioning (by qualified HVAC installer)  
To adapt the thermostat to your system and optimize control performance, a number of control  
parameters can be adjusted. This can be done during operation, either via the buttons on the  
thermostat or via a commissioning tool.  
Control parameters  
To change control parameters, proceed as follows:  
1. Press left and right buttons simultaneously for 3 seconds or until device beeps if buzzer function is  
enabled (P030).  
2. Service level: Release and within 0.5…4 seconds, press the right button again until “P001” is  
displayed.  
Expert level: Release and within 0.5…4 seconds, press the left button again until the temperature  
disappears. Turn the rotary knob counterclockwise minimum ½ rotation. P050 displays.  
3. Select the required parameter by turning the rotary knob.  
4. Press button (OK). The current value of the selected parameter flashes and can be changed by  
turning the rotary knob.  
5. Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.  
To adjust additional parameters, repeat steps 3 through 5, or press (Esc) to quit parameter setting  
mode.  
Note: If password protection (needs to be done by HVAC installer) is enabled, users must enter the password to open  
parameter setting mode. If the password is mistyped 5 times, the thermostat is locked and the password cannot be  
entered for 5 minutes. Symbols  
and  
are displayed.  
Parameter list  
Adj.  
No.  
Description  
Factory setting  
Setting range  
2-pipe:  
1 = Cooling only  
0 = Heating only  
1 = Cooling only  
P001  
2 = H/C changeover auto  
3 = H/C changeover manual  
4 = Heating and cooling  
Control sequence  
4-pipe:  
4 = Heating and  
cooling  
1 = Auto *** - Protection / Auto - Comfort –  
Protection (when there is local scheduler)  
2 = Auto *** - Comfort - Economy - Protection  
3 = Auto *** (Comfort) - Protection Hospitality  
0 = Auto - Manual  
Operation via room operating mode  
selector  
P002  
P003  
1
1 = Manual  
0
Operation via fan operating selector  
2 = Auto - Manual - Protection  
3 = Auto – Protection  
0 = °C (parameter in °C)  
P004  
P005  
0
Unit  
1 = °F (parameter in °F)  
ON = Enabled  
OFF  
Scheduler  
OFF = Disabled  
P006  
P007  
0 K  
0
-5…5 K  
-10…0…10 %  
Measured value correction  
Humidity value correction  
0 = Room temperature  
P008  
0
Standard display  
1 = Setpoint  
0 = --- (No display)  
1 = °C and °F  
2 = Outside temperature  
3 = Time of day (12 h)  
4 = Time of day (24 h)  
5 = Humidity  
P009  
0
Additional display information  
1 = Comfort concept  
P010  
P011  
P013  
1
Setpoint concept  
2 = Energy saving concept  
5…40 °C (41…104 °F)  
(P010 = 1): 5 °C (41 °F)...P016-1 K  
(P010 = 2): 5 °C (41 °F)...P014-1 K  
21 °C (70 °F)  
5 °C (41 °F)  
Comfort basic setpoint  
Comfort setpoint minimum  
P014  
P015  
21 °C (70 °F)  
25 °C (77 °F)  
P013+1 K…P015-1 K  
P014+1 K…P016-1 K  
Comfort setpoint maximum heating  
Comfort setpoint minimum cooling  
(P010 = 1): P013+1 K...40 °C (104 °F)  
(P010 = 2): P015+1 K...40 °C (104 °F)  
--- (0), 5 °C…P020 (41 °F…P020)  
P020 = 40 °C max. (P020 = 104 °F max.)  
--- (0), P019…40 °C (P019…104 °F)  
P019 = 5 °C min. (P019 = 41 °F min.)  
P016  
P019  
P020  
35 °C (95 °F)  
15 °C (59 °F)  
30 °C (86 °F)  
Comfort setpoint maximum  
Economy heating setpoint  
Economy cooling setpoint  
P024  
P026  
50  
---  
--- (0), P026 or 20…90 %  
--- (0), 20…90 % or P024  
Humidity setpoint high  
Humidity setpoint low  
P027  
****  
ON = Enabled  
OFF = Disabled  
0 = Unlocked  
ON  
Electric heater when cooling  
1 = Auto lock  
means function locked  
2 = Manual lock  
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
P028  
P029  
0
Keypad  
0 = Fan disable  
1 = Low speed (Heat and Cool)  
2 = Low speed (Cooling only)  
3 = Fan disable Auto & Manual  
4 = Low speed Auto & Manual  
0
Fan: Dead zone Comfort mode  
Buzzer function  
5 = Low speed Auto & Manual Cooling  
ON = Enabled  
OFF = Disabled  
P030  
***  
ON  
When no time schedule via KNX exists, Auto equals Comfort.  
**** Parameter P027 is displayed only for application 2-pipe with electric heater.  
All temperature settings are in increments of 0.5 °C.  
Remember to record all changes!  
© Siemens Switzerland Ltd, 2020  
Issued by  
Technical specifications and availability subject to change without notice.  
Siemens Switzerland Ltd  
Smart Infrastructure  
Global Headquarters  
Theilerstrasse 1a  
CH-6300 Zug  
Tel. +41 58 724 2424  
A6V11545973_en--_b  
A5W00031435A-AB  
2021-07-14  
Siemens Smart Infrastructure  
 
GeneralDetails
NameSIEMENS RDG200KN Room Thermostat Instruction Manual
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.24 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS RDG200KN Room Thermostat Instruction Manual