INSTALLER/CONFIGURATION MENU  
Skip this step and continue through the remainder of the  
configuration menu if you require an Air Filter Change  
out indicator or Humidifier Pad Change out indicator by  
pump system versus your auxiliary system relative to the  
thermostat adjustment. The higher the number the sooner  
the auxiliary stage energizes for better comfort. The lower  
the number the longer period of time before auxiliary is  
energized for more economy.  
pressing the  
key to advance.  
Return to this point when you are ready to start your  
selected lock-out and continue by:  
Note: This setting is not minutes or degrees. It is numeric set-  
ting that will influence the internal thermostat calculation  
for staging.  
35. Select Compressor Delay (Cd) – After the auxiliary heat  
is turned on, the compressor(s) shut down is delayed for  
the time selected (in seconds). This delay is factory set to  
60, but can be set in the range of 0 to 99.  
36. Select Auxiliary Off (AO) – Applicable with HP1 or HP2  
selected with outdoor sensor. Select the temperature  
that will inhibit the auxiliary heating stage. As long as the  
outdoor temperature is above the selected temperature,  
the auxiliary heat will not turn on. The default setting is  
80°(disabled), but can be set in the range of -5° to 79°.  
Thermostat will not allow a setting at or below the (dF)  
dual fuel setting.  
Pressing  
or  
keys to select your keypad lockout  
combination number. Note: "000" is not a valid combina-  
tion choice.  
Record the number you select for future use.  
Press  
to exit the menu. The security feature you select  
will start in 10 seconds. The system key will remain active  
for 10 seconds to allow setting Heat, Off, Cool or Auto.  
To unlock the keypad, press Menu, then press Installer  
Config. Display will show "000" and keypad lock. Enter  
the code used to lock the keypad and press  
27 & 28. Select Fast Second Stage, ON or OFF – Not  
.
available if configured for SS1. Selecting FA ON forces  
additional heat stages to come on quickly when  
is  
used to raise the temperature a few degrees above the  
room. Select this setting if you want the heat to increase  
quickly when you manually raise the temperature.  
Selecting FA OFF allows the thermostat to calculate an  
optimal time to bring on additional stages of heat. When  
If indoor temperature drops below 45° because of a pos-  
sible heat pump malfunction, the thermostat will turn off  
the pump and switch to Auxiliary heat. "Call for Service"  
will display on screen.  
the  
is used to raise the setting above the room tem-  
There are two ways the thermostat will return to normal  
heat pump operation:  
•฀ Press฀any฀key฀to฀retry฀the฀pump฀and฀erase฀the฀"call฀for฀  
service icon.  
•฀ When฀setpoint฀is฀achieved฀on฀Auxiliary,฀system฀will฀  
return to heat pump operation on next call for heat.  
perature additional heat stages may come on very quickly  
or very slowly (up to 30 minutes later) depending on  
recent system performance. Select this setting if you do  
not require the additional heat stages to come on quickly  
when you manually raise the setting and want to allow the  
thermostat to stage based on recent system performance. 37. Select Programmable Blower Balance Point (bP) –  
The Fast Cool feature operates the cooling stages in the  
same manner as Fast Heat, On or Off when the tempera-  
ture is lowered below the room setting.  
Applicable with HP1 or HP2 selected, dF On with outdoor  
sensor. Requires DHM connection from thermostat to  
heat pump system. This feature de-energizes the DHM  
terminal to operate the blower at a slower speed for first  
stage heat when the outdoor temperature is below the  
temperature selected. This circulates warmer air than the  
higher fan speed. The default is 80° (disabled), but can be  
set from 20° to 79°. Select an outdoor temperature where  
the air coming out of the ducts begins to feel cool and the  
thermostat will lower the fan speed to circulate warmer air.  
38. Humidity Display (Hd) – Selecting HD On enables the  
display to alternately show the current time and the hu-  
midity. If HD is selected OFF, the display will not show the  
humidity. (See page 10 for Humidity setpoint range)  
39. Adjustable Humidity Display – The display will show  
the ambient humidity and 00 (default). The setting can  
be changed from -20 and LO to 20 and HI. The displayed  
humidity will change as the offset is changed. In Run  
mode, the displayed humidity will be the ambient humidity  
adjusted by the setting selected.  
40. Auto Humidity Reduction (HR) – This feature au-  
tomatically lowers humidity setting when the outside  
temperature drops to prevent the interior windows/walls  
from reaching the dew point where water condenses on  
surfaces. This feature default is OFF. It can be changed  
to select LO (low humidity reduction) or HI. To achieve  
automatic humidity reduction, the thermostat lowers the  
humidity when furnace cycles are long. When the outside  
temperature rises, it increases humidity. "LO" indicates a  
low amount of humidity reduction.  
29. Select Remote Temperature Sensor Enabled – ON  
enables a remote sensor connected to thermostat and dis-  
plays the sensor temperature in the clock digits. OFF (de-  
fault) indicates no remote sensor connected or enabled.  
30. Select Remote Sensor as Indoor or Outdoor – If 30  
is enabled, select the remote to be Remote In (Indoor,  
F145-1328) or Outdoor Remote (Outdoor, F145-1378).  
Default is Remote In.  
31. Select Local Sensor Disable – If 31 is selected Indoor,  
the thermostat Local Sensor can be disabled so the  
displayed temperature will be from the Remote Sensor.  
Default is On LS. To disable the Local Sensor, change  
selection to OFF LS.  
32. Select Dual Fuel Feature (dF) – This feature is appli-  
cable only in heat pump modes (HP1, HP2). Enables (On)  
or disables (Off) dual fuel feature of thermostat.  
33. Select Dual Fuel Temperature – With dF selected On  
and outdoor remote sensor available, select the outdoor  
temperature the thermostat will use to determine when to  
switch to gas heat and shut down the compressor. When  
the outdoor temperature falls below the selected tem-  
perature the gas heat will begin. Default is 35°, but can be  
set in the range of -5 to 50°. A lower setting will delay the  
start of gas heat allowing cooler temperature in the home.  
34. Select Dual Fuel Setting – With DF selected On and no  
outdoor sensor, select the dF setting from 01-09. Fac-  
tory default is 05. The dF setting influences when second  
stage comes on. The factory default creates a separation  
of approximately 1°F between stages. Increasing the set-  
ting decreases the separation between stages. Decreas-  
ing the value increases stage separation. This adjust-  
ment allows a small change in the operation of your heat  
41. Automatic Humidification (AH) – This feature if enabled  
allows for humidification independent of a call for heating  
– useful in arid climates where addition humidification in  
heating and/or cooling is desired. If enabled, will energize  
the humidifier and circulator blower (“G” terminal and the  
9
GeneralDetails
NameOH-1202H Universal Humidity Touchscreen Thermostat Instruction Manual
MakeOH
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

OH-1202H Universal Humidity Touchscreen Thermostat Instruction Manual