Milesight WT30x Smart Fan Coil Thermostat User Guide
(Set Temp.
Tolerance)
The valve will start cooling when room temp. > (set temp. +
dead zone temp.); start heating when room temp. < (set
temp. – dead zone temp.).
15
16
Report Interval
1~60 minutes
1 minute
00
00: SerialNet
LoRaWAN® Mode
01: AT MODE
00: Off
17
18
Keycard Function
Time Zone
01
12
01: On
0~24: the corresponding time zone -12~12
12 means time zone is UTC+0
00: Use internal NTC or external NTC input sensor
01: Use external temperature data via downlink command
Room Temp.
Sensor
19
20
00
U7
Version Number
WT302 Only
14
15
16
Report Interval
1~60 minutes
1 minute
P Value
I Value
1-10
2
1-60s
40s
00: SerialNet
17
18
19
LoRaWAN® Mode
Keycard Function
Time Zone
00
01
12
01: AT MODE
00: Off
01: On
0~24: the corresponding time zone -12~12
12 means time zone is UTC+0
00: Use internal NTC or external NTC input sensor
01: Use external temperature data via downlink command
Room Temp.
Sensor
20
21
00
U7
Version Number
Definition of P Value
The proportional band is the amount of change required by the ambient temperature for the
output to go from 0 to 100%. It can be adjusted from 1~10. Factory default is 2.
The larger the P value, the greater the change in valve output; the smaller the P value, the smaller
the change in valve output.
For example, when P=2, the temperature difference between ambient temperature and
setpoint is 5°C, the valve will open about 10%; when P=4, the temperature difference between
ambient temperature and setpoint is 5°C, the valve will open 20%.
13
| General | Details |
|---|---|
| Name | Milesight WT30x Smart Fan Coil Thermostat User Guide |
| Make | Milesight |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.31 MB |

Milesight WT201-868M Smart Thermostat User Guide

Milesight WT201 Airteq Smart Thermostat User Guide

Milesight WT101 Smart Radiator Thermostat User Guide

Milesight WT201 Smart Thermostat User Guide