Milesight WT30x Smart Fan Coil Thermostat User Guide
Set Temperature
Keycard Status
06
07
08
09
0f
5e
5f
Configuration Mode
External Server Temperature
All Data
60
61
67
Examples:
1. Enquiry the room temperature.
55 02 0001 05 5d
Start
55
ID
Data Length
00 01=1 Byte
Data Type
05=Room Temperature
Checksum
5d
02
Reply:
55 01 0002 05 33 90
Start
55
ID
Data Length
00 02=2 Bytes
Data Type
05
Data Content
Checksum
90
01
33=>51/2=25.5°C
2. Enquiry all data.
55 02 0001 0f 67
Start
55
ID
02
Data Length
00 01=1 Byte
Enquiry Type
0f=All data
Checksum
67
Reply: the same as periodic packet.
Appendix
Default Frequency
Supported Freq
Channel/MHz
CN470
EU868
IN865
RU864
AU915
US915
KR920
471.9, 472.1, 472.3, 472.5, 472.7,472.9, 473.1, 473.3 (8~15)
868.1, 868.3, 868.5
865.0625, 865.4025, 865.985
868.9, 869.1
916.8, 917, 917.2, 917.4, 917.6, 917.8, 918, 918.2 (8~15)
903.9, 904.1, 904.3, 904.5, 904.7, 904.9,905.1, 905.3 (8~15)
922.1, 922.3, 922.5