Set Temperature  
Keycard Status  
06  
07  
08  
09  
0f  
5e  
5f  
Configuration Mode  
External Server Temperature  
All Data  
60  
61  
67  
Examples:  
1. Enquiry the room temperature.  
55 02 0001 05 5d  
Start  
55  
ID  
Data Length  
00 01=1 Byte  
Data Type  
05=Room Temperature  
Checksum  
5d  
02  
Reply:  
55 01 0002 05 33 90  
Start  
55  
ID  
Data Length  
00 02=2 Bytes  
Data Type  
05  
Data Content  
Checksum  
90  
01  
33=>51/2=25.5°C  
2. Enquiry all data.  
55 02 0001 0f 67  
Start  
55  
ID  
02  
Data Length  
00 01=1 Byte  
Enquiry Type  
0f=All data  
Checksum  
67  
Reply: the same as periodic packet.  
Appendix  
Default Frequency  
Supported Freq  
Channel/MHz  
CN470  
EU868  
IN865  
RU864  
AU915  
US915  
KR920  
471.9, 472.1, 472.3, 472.5, 472.7,472.9, 473.1, 473.3 (8~15)  
868.1, 868.3, 868.5  
865.0625, 865.4025, 865.985  
868.9, 869.1  
916.8, 917, 917.2, 917.4, 917.6, 917.8, 918, 918.2 (8~15)  
903.9, 904.1, 904.3, 904.5, 904.7, 904.9,905.1, 905.3 (8~15)  
922.1, 922.3, 922.5  
18  
   
GeneralDetails
NameMilesight WT30x Smart Fan Coil Thermostat User Guide
MakeMilesight
LanguageEnglish
FiletypePDF (Download)
File size0.31 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Milesight WT201-868M Smart Thermostat User Guide
Milesight WT201-868M Smart Thermostat User Guide
Milesight WT201 Airteq Smart Thermostat User Guide
Milesight WT201 Airteq Smart Thermostat User Guide
Milesight WT101 Smart Radiator Thermostat User Guide
Milesight WT101 Smart Radiator Thermostat User Guide
Milesight WT201 Smart Thermostat User Guide
Milesight WT201 Smart Thermostat User Guide

Milesight WT30x Smart Fan Coil Thermostat User Guide