Milesight WT30x Smart Fan Coil Thermostat User Guide
Heat mode (P-band: 2)
When the ambient temperature is below the set point the output is somewhere between
0~100%.
Cool mode (P-band: 2)
When the ambient temperature is above the set point the output is somewhere between
0~100%.
Definition of I Value
This feature allows you to set the integral action time for the integral to run from 0 to 100%. The
value required depends on the reaction time of the control loop. If the time is chosen too short,
the control loop will become instable and oscillate. If the time is chosen too long, the control
loop will become sluggish. It can be adjusted from 1s-60s. The default value is 40s.
5.3 LoRaWAN® Settings
WT30x does not support to configure LoRaWAN® information. Please contact Milesight to
customize the LoRaWAN® settings before purchase.
Parameters
Device EUI
App EUI
Description
Unique ID of the device.
The default App EUI is 24E124C0002A0001.
Default
On the label
24E124C0002A0001
85
Application Port The port is used for sending and receiving data.
Join Type OTAA and ABP modes are available.