Milesight WT30x Smart Fan Coil Thermostat User Guide
INT8/2, Unit: °C
External Server
Temperature
07
0f
Note: this only takes effect when advanced
setting-Room Temp. Sensor is set as 01.
Send all above commands in order
All Commands
Checksum Calculation: sum of bytes % 256
Examples:
1. Turn on the device.
55 01 0002 0101 5a
Start
55
ID
Command Length
00 02=2 Bytes
Data Type
01
Command
Checksum
5a
01
01=Turn On
2. Set all configurations:
55 01 0008 0f 010000012a0034 cd
Start
55
ID
Data Length Data Type
Command
01=Turn On
Checksum
00=Button Lock Disable
00=Cooling
00 08=8
Bytes
01
0f
01=High
cd
2a=>42/2=21°C (Set Temp.)
00=Programme Mode
34=>52/2=26°C (External Temp.)
6.3 Downlink Enquiry Commands
WT30x supports downlink commands to enquiry the device information. The application port is
85 by default. The command is based on following format (HEX):
Start
55
ID
Command Length
0001
Data Type
1 Byte
Checksum
1 Byte
02
Item
Data Type
Checksum
Turn On/Off
Button Lock
01
02
03
04
05
59
5a
5b
5c
5d
System Mode
Fan Mode
Room Temperature
17
| General | Details |
|---|---|
| Name | Milesight WT30x Smart Fan Coil Thermostat User Guide |
| Make | Milesight |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.31 MB |

Milesight WT201-868M Smart Thermostat User Guide

Milesight WT201 Airteq Smart Thermostat User Guide

Milesight WT101 Smart Radiator Thermostat User Guide

Milesight WT201 Smart Thermostat User Guide