Technical Data  
0b0000 0011=  
controller cooling mode only, Comfort Mode  
Measuring values  
temperature  
0b0000 0100=  
ventilating (PI loop controls fan stages only, valves  
closed)  
Output switch contact  
terminal 5 | 6  
terminal 2 | 3 | 4 – LO | ME | HI  
2 normally open contacts, 250 V load max 3 A  
(heating & cooling via 2-point control )  
3x normally open contact, 250 V load max. 3 A,  
Fan  
0b0001 0000=  
Output voltage  
terminal 16 | 17  
terminal 15  
FC610 off (Frost protection active), ECO Mode  
0b0001 0001=  
2x 0..10 V for heating and cooling  
1x 0..10 V for fan  
controller auto mode (heating&cooling), ECO Mode  
0b0001 0010=  
terminal 14  
terminal 12– ESI | DP  
input for external sensor  
NTC10K  
input digital for floating contact,  
window contact, dew point sensor  
controller heating mode only, ECO Mode  
0b0001 0011=  
Inputs  
controller cooling mode only, ECO Mode  
0b0001 0100=  
terminal 13 - OCC  
input digital for floating contact,  
occupancy sensor, key card switch  
ventilating (PI loop controls fan stages only, valves  
closed)  
Network technology  
RS485 Modbus, RTU, half-duplex, baud rate 4.800, 9.600, 19.200 or 38.400, parity: non (2 stopbits),  
HMI mode  
0b1xxx xxxx=HMI mode ,controller OFF  
0b1xxx xx01=show symbol “ventilating “  
0b1xxx xx10=show symbol “heating “  
0b1xxx xx11=show symbol “cooling”  
0b1xxx x110=show AUTO+ heating symbol  
0b1xxx x111=show AUTO+ cooling symbol  
0b1xxx x101= show AUTO+ ventilating symbol  
0b1xxx1xxx=reserved  
even or odd (1 stopbit)  
WIFI 2.4G wifi communication  
Power supply  
24 DC/AC 50/60Hz  
Power consumption  
Max load current  
Measuring range temp.  
Accuracy temperature  
Control functions  
Display  
Max 3w  
<3A  
+1..+50 °C  
515  
0x0203  
Read-write Active Symbols  
0x00= show none  
±1 K (typ. at 21 °C)  
0x01= show Leaf  
0x02= show dew point  
0x04= show frost protect ON  
0x08= show open window  
0x10= show Attention!  
0x20= show hourglass  
0x40= show lock  
set point adjustment +1..+50 °C, (default +16..+30 °C)  
LCD Ø49 mm, black background white lighting  
Power unit :Fire proof PC+ABC  
0
Enclosure  
Display unit : Aluminum Alloy + High strength 3D Curved tempered glass  
IP20 according to EN 60529  
Protection  
0x80= show ECO  
516  
517  
0x0204  
0x0205  
Read-write Control variable y%(HMI MODE)  
0.1  
0.1  
%
%
Cable entry  
rear entry  
0-100%  
0
0
Connection electrical  
Ambient condition  
Mounting  
terminal block max. 1,5 mm²  
-10..+50 °C, max. 95% rH non-condensing  
flush mounted with standard 86*86 wall box (Ø=60 mm)  
86*86*61mm  
If output is 2-point ,output will be ON for control variable  
>5%  
Read-write Room temperature on LCD (HMI mode)  
0….500=0…50°C  
Dimension(L*W*H)  
GeneralDetails
NameFC610 Bandary Smart Thermostat Owner’s Manual
Makebandary
LanguageEnglish
FiletypePDF (Download)
File size1.24 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
bandary FC660 Smart Thermostat User Guide
bandary FC660 Smart Thermostat User Guide

FC610 Bandary Smart Thermostat Owner’s Manual