Rev. A
TF
Frost protection thermostat
Frost protection thermostat for use in cooling,
heating and ventilation systems.
•
•
•
•
Easy installation and wiring
Manual or automatic reset
Protection class IP65
C
a
p
i
l
l
a
r
l
e
n
g
t
h
1
,
8
-
3
-
6
-
1
5
m
...............................................................................
Application
Appearance
TF…(R) is a device with the task of controlling the
The device consists of an ABS base and a transparent
polycarbonate self-extinguishing cover, V0 class. The internal
parts are made of technopolymer and stainless steel to
guarantee its mechanical stability. The sensitive element is in
copper filled with gas.
temperature of heating and cooling batteries, ventilation
ducts and all those applications where frost damage can be
prevented. The 15 (8) A switching contact (SPDT) allows use
in a variety of functions such as controlling a fan, a shutter,
an electric resistance, open or close a heating circuit or
cooling circuit, start or stop a circuit pump ror heating or
cooling, switch off a refrigerator unit or a humidifier, signal
an alarm condition through a visual or acoustic device.
Function
The thermostat TF switches when the temperature sensed by
capillary for a minimum length of 50 cm drops below the
temperature set on the knob. When temperature increases,
the contact returns automatically to the initial position. For R
versions it is necessary a manual reset from user to allow the
contact to return to the initial position. The gas inside the
sensible element increases his volume and with a
mechanism acts on the microswitch. The capillary is sensible
to temperature for the whole length. The models with range
under the cover for setting the setpoint avoids any
involuntary change of the set.
...............................................................................
TF
MAIN OFFICE BRESSANONE
I-39042 Bressanone (BZ) tel: +39 0472 830626
via Julius-Durst-Str. 50
VAT No. IT02748450216
fax: +39 0472 831840
1 (3)
| General | Details |
|---|---|
| Name | industrie technik TF Frost Protection Thermostat Instruction Manual |
| Make | industrie technik |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.15 MB |

industrie technik TF Frost Protection Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Frost protection thermostat for use in cooling, heating and ventilation systems. Easy installation and wiring. Manual or automatic reset. Protection class IP65. The device consists of an ABS base and a transparent polycarbonate self-extinguishing cover. The sensitive element is in copper filled with gas. The thermostat TF switches when the temperature sensed by capillary drops below the temperature set on the knob. The gas inside the sensible element increases its volume and acts on the microswitch. The models with range under the cover for setting the setpoint avoids any involuntary change of the set.
- Page 2: Technical data Sensitive element: Copper capillar filled with gas Contact: SPDT microswitch Breaking capacity: 15 (8) A, 24…250 V AC Accuracy: ± 1K Ambient temperature: Max. 55 °C Ambient humidity: 10…90 % UR (non-condensing) Storage temperature: -30…+60 °C Storage humidity: 95 % UR Protection class: IP65 Isolation class: I Models: TF18, TF18R, TF30, TF30R, TF60, TF60R, TF150, TF150R Accessories: DBZ-01, DBZ-02, DBZ-05 This product carries the CE-mark. Low Voltage Directive (LVD) & EMC emissions & immunity standards: This product conforms to the requirements of the European Low Voltage Directive (LVD) 2006/95/EC and to the requirements of the EMC Directive 2004/108/EC through product standard EN 60335-1. RoHS: This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council.
- Page 3: Dimensions are provided in millimeters. For heating, connect to the red and blue terminal; the contact will open when the temperature rises. For cooling, connect to the red and white terminal; the contact will open when the temperature drops. For service functions, connect a signal lamp to the corresponding opposite contact, which will close simultaneously acting as a signal contact. All documentation can be downloaded from the company website.