Read-write Electrical Heater Stage 3 Threshold control variable
0..100%
1.0
%
Display panel
304
0x0130
Read-write
Valve type selection
5DO:
27.Fanstagesymbol
0= ON-OFF (ON = Valve Open, OFF = Valve Closed)
1=PWM (0%= 0%PWM .. 100% = 100% PWM)
2= OFF-ON (OFF = Valve Open, ON = Valve Closed)
3= inverted PWM (0%= 100%PWM .100% = 0% PWM)
AO2DO3R, AO3DO2R:
26.Thermostat address ID
25.ECOmode
24.Time delay
1.Modbus active
23.Wifisymbol
2.Coolingmode
22.Celsius
3.Ventilation mode
4.Heatingmode
21.Electricheating
4= proportional (0V = 0% ..10V = 100%)
5=invers proportional (0V = 100% ..10V = 0%)
6: proportional Belimo 6 way
20.Fahrenheit
19.Lock
18.ESI
5.Automode
5DO:0
6.Temperature display
17.Scheduler
AO2DO3R:4
AO3DO2R:4
7.Valve value
16.Frost Protection
15.Week
7: proportional Sauter 6 way with Ø15mm
8: proportional Sauter 6 way with Ø20mm
9: proportional Belimo 6 way, counter direction
10: proportional Sauter 6 way with Ø15mm,
counter direction
8.Function symbol
9.Time setting
14.Heatingvalve
13.Coolingvalve
12.Fault alarm
11.Humidity
10.TVOC
1 Modbus active – When the device is connected to BMS via to RS485 interface ,the Modbus symbol will active.
2 Cooling mode – when the set temperature is lower than room temperature ,the device will work in cooling mode.
3 Ventilation mode - Fan is working, water valve keeps off.
11: proportional Sauter 6 way with Ø20mm,
counter direction
4 Heating mode – when the set temperature is higher than room temperature ,the device will work in heating mode .
DO5R,AO2DO3R, AO3DO2R:
5 Auto mode –The thermostat switches automatically between cooling and heating according to the temperature difference between
set temperature and room temperature. A time delay of approx..1min between cooling /heating mode changes is implemented to
12: no valve
ensure safe and eco-friendly operation .Auto mode will be active in below types:
6 Temperature display – Normally ,the device displays room temperature .when the user change temperature ,it displays set
305
0x0131
Read-write reserved
0
temperature ,after 4 seconds ,display room temperature. (Factory default : ℃ display ),you can switch to Fahrenheit (°F) by APP or
Modbus.
Inputs
7 Valve value – valve value%
Address
0x0150
Access Description
Resolution / Unit
Default
8 Function symbol – Temperature setting, Mode adjustment or Parameter setting status
9 Time setting –Real time of Day
336
Read-write Configuration external input 1
0 = No function
10 TVOC – Room air quality
1 = Occupancy sensor (Open = Occupied)
2 = Occupancy sensor (Closed =Occupied)
3 = Window contact (Open = Window Open)
4 = Window contact (Closed = Window Open)
5 = Disable heating (Open = Heating disabled)
6 = Disable heating (Closed = Heating Disabled)
7 = Disable cooling (Open = Disable Cooling)
8 = Disable cooling (Closed = Disable Cooling)
11 Humidity – Relative room humidity
12 Fault alarm – ERROR alarm symbol and display ERROR code
13 Cooling valve – Cooling mode is active .
14 Heating valve – heating mode is active
15 week-week display
0