Home > nVent > nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual

nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual

E507S-LS  
Line-Sensing Thermostat for Hazardous Locations  
Installation Instructions  
DESCRIPTION  
The nVent RAYCHEM E507S-LS thermostat is designed for controlling  
heat-tracing systems in hazardous locations. The E507S-LS can be  
used to control heat-tracing circuits in a pipe-sensing mode (see  
Figure 1 on back page), to indicate low-temperature (see Figure 2) or  
high-temperature (see Figure 3) alarm conditions, or to control the coil  
on a contactor (see Figure 4).  
entair  
P
APPROVALS  
Hazardous locations  
Class I, Div. 1 and 2, Groups B, C, D  
Class II, Div. 1 and 2, Groups E, F, G  
Class III  
SPECIFICATIONS  
Ø.28 in. (7 mm)  
mounting hole  
(4X)  
4.5 in. (114 mm)  
4.0 in. (102 mm)  
Enclosure  
NEMA 4, 7, 9, lacquer-coated cast-aluminum  
housing, stainless-steel hardware  
Entries  
One 3/4 in. NPT conduit hub  
25°F to 325°F (–4°C to 163°C)  
4.0 in.  
(102 mm)  
4.5 in.  
(114 mm)  
Pentair  
Set point range  
8.0 in.  
(202 mm)  
Sensor exposure –40°F to 420°F (–40°C to 215°C)  
limits  
6.6 in.  
(168 mm)  
Housing exposure –40°F to 140°F (–40°C to 60°C)  
limits  
Switch  
SPDT  
Electrical rating  
22 A at 125/250/480 Vac  
Adjusting knob  
Removable knob cover  
Accuracy  
±6°F (±3.3°C)  
4.0 in. (102 mm)  
Deadband  
2°F to 12°F (1.1°C to 6.7°C) above actuation  
temperature  
1.2 in. (30 mm)  
0.3 in. (9 mm)  
Terminal  
block  
Set point  
±3°F (±1.7°C)  
repeatability  
2.0 in.  
(50 mm)  
Sensor type  
Fluid-filled (silicone) bulb and 9 ft (2.7 m)  
capillary  
Sensor material  
300 series stainless steel  
2
Connection  
terminals  
Screw terminals, 10–14 AWG (2–5 mm )  
3⁄4 in. NPT conduit entry  
WARNING:  
This component is an electrical device. It must be installed correctly to ensure  
proper operation and to prevent shock or fire. Read these important warnings  
and carefully follow all the installation instructions.  
Component approvals and performance are based on the use of specified parts  
only. Do not use substitute parts or vinyl electrical tape to make connections.  
GeneralDetails
NamenVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual
MakenVent
LanguageEnglish
FiletypePDF (Download)
File size0.31 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
nVent GM-TA Thermostat User Manual
nVent GM-TA Thermostat User Manual

nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual
Get the free PDF manual for the nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual Overview

Summary of Contents

  • Page 1: Line-sensing thermostat for hazardous locations The nVent RAYCHEM E507S-LS thermostat is designed for controlling heat-tracing systems in hazardous locations. The E507S-LS can control heat-tracing circuits in a pipe-sensing mode, indicate low-temperature or high-temperature alarm conditions, or control the coil on a contactor. Approvals include hazardous locations Class I, Div. 1 and 2, Groups B, C, D; Class II, Div. 1 and 2, Groups E, F, G; and Class III. Enclosure is NEMA 4, 7, 9, lacquer-coated cast-aluminum housing with stainless-steel hardware. Set point range is 25°F to 325°F (–4°C to 163°C). Sensor exposure limits are –40°F to 420°F (–40°C to 215°C). Electrical rating is 22 A at 125/250/480 Vac. This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Component approvals and performance are based on the use of specified parts only.
  • Page 2: Tape the bulb firmly to the pipe with A T-180 aluminum tape, making sure there is no air space between the bulb and pipe. For metal-tank-wall sensing, use the BCK-35 bulb clamp and install the clamp per the instructions provided. Verify that the thermostat is suitable for the area where it is to be installed. Check the line voltage and the heat-tracing load to ensure that the thermostat ratings are not exceeded. Mount the unit using unistrut or the RAYCHEM universal mounting bracket in a position that prevents condensation from draining into the enclosure. Set the thermostat dial to the desired temperature, then finish wiring. Complete insulating. Do not turn the system on until the bulb is covered with thermal insulation. Once the thermostat has begun to cycle, check the fluid temperature with an immersed thermostat or an accurate temperature indicator. Position the bulb in the lower quadrant of the pipe as shown in the diagrams. Protect the capillary from kinks or bends less than 1⁄2 inch in radius.