nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual
E507S-LS
Line-Sensing Thermostat for Hazardous Locations
Installation Instructions
DESCRIPTION
The nVent RAYCHEM E507S-LS thermostat is designed for controlling
heat-tracing systems in hazardous locations. The E507S-LS can be
used to control heat-tracing circuits in a pipe-sensing mode (see
Figure 1 on back page), to indicate low-temperature (see Figure 2) or
high-temperature (see Figure 3) alarm conditions, or to control the coil
on a contactor (see Figure 4).
entair
P
APPROVALS
Hazardous locations
Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
SPECIFICATIONS
Ø.28 in. (7 mm)
mounting hole
(4X)
4.5 in. (114 mm)
4.0 in. (102 mm)
Enclosure
NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware
Entries
One 3/4 in. NPT conduit hub
25°F to 325°F (–4°C to 163°C)
4.0 in.
(102 mm)
4.5 in.
(114 mm)
Pentair
Set point range
8.0 in.
(202 mm)
Sensor exposure –40°F to 420°F (–40°C to 215°C)
limits
6.6 in.
(168 mm)
Housing exposure –40°F to 140°F (–40°C to 60°C)
limits
Switch
SPDT
Electrical rating
22 A at 125/250/480 Vac
Adjusting knob
Removable knob cover
Accuracy
±6°F (±3.3°C)
4.0 in. (102 mm)
Deadband
2°F to 12°F (1.1°C to 6.7°C) above actuation
temperature
1.2 in. (30 mm)
0.3 in. (9 mm)
Terminal
block
Set point
±3°F (±1.7°C)
repeatability
2.0 in.
(50 mm)
Sensor type
Fluid-filled (silicone) bulb and 9 ft (2.7 m)
capillary
Sensor material
300 series stainless steel
2
Connection
terminals
Screw terminals, 10–14 AWG (2–5 mm )
3⁄4 in. NPT conduit entry
WARNING:
This component is an electrical device. It must be installed correctly to ensure
proper operation and to prevent shock or fire. Read these important warnings
and carefully follow all the installation instructions.
Component approvals and performance are based on the use of specified parts
only. Do not use substitute parts or vinyl electrical tape to make connections.
| General | Details |
|---|---|
| Name | nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual |
| Make | nVent |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.31 MB |

nVent GM-TA Thermostat User Manual

nVent RAYCHEM E507S-LS Sensing Manual: Questions and Answers
nVent RAYCHEM E507S-LS Sensing specifications
| Power supply | 22 A at 125/250/480 Vac |
| Setpoint range | 25°F to 325°F (–4°C to 163°C) |
| Accuracy | ±6°F (±3.3°C) |
| Differential | 2°F to 12°F (1.1°C to 6.7°C) above actuation |
How do I set the temperature on the nVent RAYCHEM E507S-LS Sensing thermostat?
Turn the adjusting knob to your desired temperature.
- Set the thermostat dial to the desired temperature before finishing wiring Instruction Manual, p. 2
Can the nVent RAYCHEM E507S-LS Sensing thermostat switch loads greater than 22 A?
No. For loads greater than 22 A or multiple circuits, use the contactor control configuration shown in Figure 4. Instruction Manual, p. 2
What is the set point range for the nVent RAYCHEM thermostat?
25°F to 325°F (-4°C to 163°C). Instruction Manual, p. 1
nVent RAYCHEM E507S-LS Sensing compared with other nVent thermostats
| Specification | nVent RAYCHEM E507S-LS Sensing | nVent GM-TA |
|---|---|---|
| Power supply | 22 A at 125/250/480 Vac | 230 Vac, +10%/–10%, 50 Hz |
| Setpoint range | 25°F to 325°F (–4°C to 163°C) | Set point: 0°C to 6°C / 2°C |
| Accuracy | ±6°F (±3.3°C) | +/– 1,5 K incl. sensor accuracy |