9 = Dew Point Sensor (Open = Dewpoint crossed,  
disable cooling)  
FC610 2AO3DO wiring diagram  
10 = Dew Point Sensor (Closed = Dewpoint crossed,  
disable cooling)  
RS485  
B
A
337  
0x0151  
Read-write Configuration external input 2  
0 = No function  
1 = Occupancy sensor (Open = Occupied)  
2= Occupancy sensor (Closed =Occupied)  
3 = Window contact (Open = Window Open)  
4 = Window contact (Closed = Window Open)  
5 = Disable heating (Open = Heating disabled)  
6 = Disable heating (Closed = Heating Disabled)  
7 = Disable cooling (Open = Disable Cooling)  
8 = Disable cooling (Closed = Disable Cooling)  
9 = Dew Point Sensor (Open = Dewpoint crossed,  
disable cooling)  
24V  
~
(+)  
AC/DC 24V  
COM1  
(-)  
B
A
ESI  
0CC  
NTC  
NTC 10K  
0
LO  
ME  
HI  
LO  
ME  
FAN  
N
AO  
AO  
AO  
HI  
COM2  
L
GND  
10 = Dew Point Sensor (Closed = Dewpoint crossed,  
disable cooling)  
338  
0x0152  
Read-write Configuration Sensor Input  
0= none  
1 = Change Over Temp sensor (NTC10K)  
2 = Ext. Temp sensor (NTC10K)  
3 = Temperature Limiter  
0
FC610 3AO2DO wiring diagram  
339  
340  
0x0153  
0x0154  
Read-write ESI (Energy Savings Input) - ON delay  
1.0  
1.0  
s
s
0
ON delay for ESI. Delays Energy stop by n seconds  
Read-write OCC input - OFF delay  
RS485  
B
1800  
A
0…65535 -> 0…65535 seconds  
Timer  
Address  
0x0190  
0x0191  
0x0192  
Access Description  
Read-write reserved  
Read-write reserved  
Resolution / Unit  
Default  
400  
401  
402  
0
0
24V  
~
(+)  
(-)  
AC/DC 24V  
COM1  
Read-write Automatic Summer/winter time  
B
A
ESI  
0=OFF  
1=EU automatic (last Sunday in March (+1h)  
Sunday in October (-1h)  
-
last  
1st  
0CC  
NTC  
NTC 10K  
LO  
ME  
2=US automatic (2nd Sunday in March (+1h)  
Sunday in November (-1h)  
-
AO  
M
M
N
AO  
AO  
HI  
3=AUS automatic (First Sunday in October (+1h) - 1st  
Sunday in April (-1h)  
0
L
COM2  
GND  
4=BR aurtomatic (First Sunday in November (+1h) -  
Third Sunday in February (-1h)  
5=CHL automatic (Second Sunday in August (+1h) -  
Second Sunday May (-1h)  
6=ISR (Friday before last Sunday in March + 1h) - Last  
GeneralDetails
NameFC610 Bandary Smart Thermostat Owner’s Manual
Makebandary
LanguageEnglish
FiletypePDF (Download)
File size1.24 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
bandary FC660 Smart Thermostat User Guide
bandary FC660 Smart Thermostat User Guide

FC610 Bandary Smart Thermostat Owner’s Manual