2 = Ext. Temp sensor (NTC10K)
3 = Temperature Limiter
Restore to factory default value:
Input password “999” to restore to factory default value ,if the user forget the passwords and reset the passwords ,as well the parameters .
Modbus communication Register:
Input Register
Step 2.change the mode by rotation the first ring
Wake up
In normal mode, without any operation, the thermostat will access in screen saver mode after the backlight delay time , you can
wake up the thermostat by pressing the touch panel ,by rotation the ring , by APP ,or by motion sensor .
Address Access
Description
Resolution / Unit
0
1
2
0x0000
0x0001
0x0002
Read-only Bandary Model identification
0xFF10 = 5DO 0xFF11 = 3AO2DO 0xFF12 = 2AO3DO
Read-only Firmware-Version
e.g. 0x100 = 1.0.0
Read-only Back-Box type
05 = DO5R
Motion sensor: when thermostat detects the specific distance of hand waving ,thermostat will be
wake up, and the touch panel will be lighted .
23=2AO3DO
32=3AO2DO
3
4
0x0003
0x0004
Read-only Value of the integrated temperature sensor °C
0,1
°C
Parameter Setting
0…500 -> 0…50,0°C
Enter into Parameter Setting
Read-only fan status
0x00 = Manual OFF
0x01 = Manual low
0x02 = Manual medium
0x04 = Manual high
0x08 = Auto OFF
Long press the touch panel for more than 6- second in Stand-By mode, then you are asked to enter the passwords (Factory
default:987).Please follow up with below steps to set:
0x09 = Auto low
0x0A = Auto medium
0x0C = Auto high
5
6
0x0005
0x0006
Read-only VA1 status
Standbymode
Step 1 Long press the touch panel for more than 6-second in Stand-By mode, then you are asked to
0-100 0 = 0 (Off) …100% (On), e.g. 693 = 69,3% of PWM
cycle time ON
enter the passwords (Factory default:987).
Read-only VA2 status
Step 2 Rotate first ring to input first digit value(9) of the password and short press the panel to confirm ,and then input second digital
value (8),then the last value (7),and short press the panel to confirm.
0-100 0 = 0 (Off) …100% (On), e.g. 693 = 69,3% of PWM
cycle time ON
7
8
9
0x0007
0x0008
0x0009
Read-only electrical heating status
0-100 = 0 …100%
Read-only External temperature sensor °C
0.1
°C
Code 3
0…500 -> 0…50,0°C
Read-only failure status
0x00=no failure
0x01= control loop temperature sensor alarm
0x02=external temperature sensor high limit Alarm
0x04=external temperature sensor low limit Alarm
0x08= change over sensor missing alarm
Code 1
Code 2
Step 3 If password is correct, it will access in parameter setting interface.if the password is wrong ,you need to re-input correctly
passwords to access in parameter setting interface.
Step 4 access in parameter setting interface ,the first low of digit indicates the parameter value, the second low of digit indicates the
parameter No.