2 = Ext. Temp sensor (NTC10K)  
3 = Temperature Limiter  
Restore to factory default value:  
Input password “999” to restore to factory default value ,if the user forget the passwords and reset the passwords ,as well the parameters .  
Modbus communication Register:  
Input Register  
Step 2.change the mode by rotation the first ring  
Wake up  
In normal mode, without any operation, the thermostat will access in screen saver mode after the backlight delay time , you can  
wake up the thermostat by pressing the touch panel ,by rotation the ring , by APP ,or by motion sensor .  
Address Access  
Description  
Resolution / Unit  
0
1
2
0x0000  
0x0001  
0x0002  
Read-only Bandary Model identification  
0xFF10 = 5DO 0xFF11 = 3AO2DO 0xFF12 = 2AO3DO  
Read-only Firmware-Version  
e.g. 0x100 = 1.0.0  
Read-only Back-Box type  
05 = DO5R  
Motion sensor: when thermostat detects the specific distance of hand waving ,thermostat will be  
wake up, and the touch panel will be lighted .  
23=2AO3DO  
32=3AO2DO  
3
4
0x0003  
0x0004  
Read-only Value of the integrated temperature sensor °C  
0,1  
°C  
Parameter Setting  
0…500 -> 0…50,0°C  
Enter into Parameter Setting  
Read-only fan status  
0x00 = Manual OFF  
0x01 = Manual low  
0x02 = Manual medium  
0x04 = Manual high  
0x08 = Auto OFF  
Long press the touch panel for more than 6- second in Stand-By mode, then you are asked to enter the passwords (Factory  
default:987).Please follow up with below steps to set:  
0x09 = Auto low  
0x0A = Auto medium  
0x0C = Auto high  
5
6
0x0005  
0x0006  
Read-only VA1 status  
Standbymode  
Step 1 Long press the touch panel for more than 6-second in Stand-By mode, then you are asked to  
0-100 0 = 0 (Off) …100% (On), e.g. 693 = 69,3% of PWM  
cycle time ON  
enter the passwords (Factory default:987).  
Read-only VA2 status  
Step 2 Rotate first ring to input first digit value(9) of the password and short press the panel to confirm ,and then input second digital  
value (8),then the last value (7),and short press the panel to confirm.  
0-100 0 = 0 (Off) …100% (On), e.g. 693 = 69,3% of PWM  
cycle time ON  
7
8
9
0x0007  
0x0008  
0x0009  
Read-only electrical heating status  
0-100 = 0 …100%  
Read-only External temperature sensor °C  
0.1  
°C  
Code 3  
0…500 -> 0…50,0°C  
Read-only failure status  
0x00=no failure  
0x01= control loop temperature sensor alarm  
0x02=external temperature sensor high limit Alarm  
0x04=external temperature sensor low limit Alarm  
0x08= change over sensor missing alarm  
Code 1  
Code 2  
Step 3 If password is correct, it will access in parameter setting interface.if the password is wrong ,you need to re-input correctly  
passwords to access in parameter setting interface.  
Step 4 access in parameter setting interface ,the first low of digit indicates the parameter value, the second low of digit indicates the  
parameter No.  
GeneralDetails
NameFC610 Bandary Smart Thermostat Owner’s Manual
Makebandary
LanguageEnglish
FiletypePDF (Download)
File size1.24 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
bandary FC660 Smart Thermostat User Guide
bandary FC660 Smart Thermostat User Guide

FC610 Bandary Smart Thermostat Owner’s Manual