FC610 Bandary Smart Thermostat Owner’s Manual
Stand:
Seite 12 / 23
Stand:
Seite 13 / 23
Please find the example as below figure:
Backlight intensity
for screen saver
25
25
12
13
0...25
03 indicates parameter No.(03- memo after power failure),001 indicates the parameter value(restore last status before power failure)
Individual password
Temperature format
Communication ID
Baud rate(bps)
Parity
0-998
987
0
0 0
0
0=℃ 1=°F
14
15
16
17
18
19
20
21
1…247
1
1=4800 2=9600 3=19200 4=38400
0=none,1=odd 2=even
2
0
Stop Bits
1 = 1 Stopbit 2= 2 Stopbits
2
Shift to next parameter No. by rotation the first ring ,and short press panel to confirm ,rotation the first ring to change the parameter
value which you want to set ,and short pressing the panel to confirm. If finish the parameter setting ,long pressing panel for 3-second
to exit the parameter setting interface .
Winter/summer time
Power box type
Fan coil type
0=OFF 1=EU 2=US 3=AUS 4=BR 5=CHL 6=ISR 7=MEX
0
05=5DO 23=2AO3DO 32=3AO2DO
05
1
Time setting:
If thermostat is connecting to the internet ,the Real time will be updated . If fail to Wifi connection, the user can manual set the date
by parameter No.10 . please follow up with orders to set Year/ Month /Date/ Hour& Minute.
0=2pipe cool&heat 1=4-pipe cool&heat
depending on back-box type:
Parameter table:
DO5R:
No.
Name of parameter
Parameter definition
Factory default
0= ON-OFF (ON = Valve Open, OFF = Valve Closed)
1=PWM (0%= 0%PWM .. 100% = 100% PWM)
2= OFF-ON (OFF = Valve Open, ON = Valve Closed)
3= inverted PWM (0%= 100%PWM .. 100% = 0% PWM)
AO2V-DO3R, AO3V_DO2R:
Internal Temperature
offset
1
-5.0 ℃~5.0℃/23°F ~41°F
0℃/32°F
External temperature
offset
2
3
-5.0 ℃~5.0℃/23°F ~41°F
0℃/32°F
Upper temperature
limited
0℃~50℃ / 32°F ~99°F
30℃/86°F
4= proportional (0V = 0% ..10V = 100%)
5=invers proportional (0V = 100% ..10V = 0%)
6: proportional Belimo 6 way
DO5R:0
22
Valve type
2AO3DO:4
3AO2DO:4
Down temperature
limited
4
0℃~50℃ / 32°F ~99°F
16℃/60°F
7: proportional Sauter 6 way with Ø15mm
8: proportional Sauter 6 way with Ø20mm
9: proportional Belimo 6 way, counter direction
10: proportional Sauter 6 way with Ø15mm, counter direction
11: proportional Sauter 6 way with Ø20mm, counter direction
DO5R,AO2V-DO3R, AO3V_DO2R:
5
6
7
8
5℃~15℃/ 41°F ~59°F
Frost protection
Lock
7℃/44°F
0=deactivated 1=activated
0
Screen saver mode
Backlight delay off
0= display panel off 1=temp+humidity 2=temp+clock
10-255 seconds
1
2
15
0=stay off after power on 1=restore last status before
power failure 2=stay on after power on
0=deactivated 1=activated
9
Power failure
1
12: no valve
0
10
11
Time
0
0
0= 0= none
1 = Change Over Temp sensor (NTC10K)
000
Schudler
0=deactivated 1=activated
23
changeover
0