VIVE TP-S-955WH Programmable Thermostat Instruction Manual

Technician Setup  
Technician Setup  
Tech Setup Steps  
LCD Will Show Adjustment Options  
Default Tech Setup Steps  
LCD Will Show Adjustment Options  
Default  
When turned on the thermostat  
OFF configures the thermostat  
for non heat pump systems.  
Enables the use of an outdoor  
When NO is selected the  
thermostat is unable to  
connect to an outdoor  
remote sensor. When YES  
is selected the thermostat  
is able to connect to an  
outdoor remote sensor. Press  
and hold connect button  
on outdoor sensor until the  
OFF  
will operate a heat pump.  
1. EM. Heat will show as an option  
in the system switch.  
2. Y will be first stage of heat  
& cool, W/E will be emergency  
heat relay & W2 will be auxiliary  
heat relay.  
sensor. Connecting an outdoor  
sensor allows for a balance point  
setting. Selecting YES requires the  
master thermostat to be powered  
with 24V on C and R terminals.  
See the outdoor sensor guide for  
more information.  
ON configures the thermostat  
for heat pump systems.  
Heat Pump  
System Set  
OFF  
Outdoor  
Sensor  
NO  
OUTDOOR  
SENSOR  
master thermostat says  
FOUND OUTDOOR on display.  
Use the or key until  
the desired application is  
flashing.  
You can configure the system  
switch for the particular appli-  
cation.  
Heat - Off - Cool, Heat - Off, Cool -  
Off, Heat - Off - Cool - Auto  
Note: EM. Heat will show if in  
heat pump mode.  
HEAT  
OFF  
COOL  
When NO is selected the  
thermostat is unable to  
Enables the use of up to four  
indoor sensors.  
Selecting YES requires the master  
thermostat to be powered with  
24V on C and R terminals.  
SYSTEM  
AUTO - Auto Changeover  
SET  
connect to an indoor remote  
sensor. When YES is selected  
the thermostat is able to  
connect to up to four indoor  
remote sensors. Go to the  
next step FINDING SENSOR to  
connect remote sensors.  
Remote  
Sensor  
NO  
GAS  
Select GAS for systems that  
control the fan during a call for  
heat.  
REMOTE  
SENSOR  
GAS  
or  
Fan  
Operation  
Select ELEC to have the  
thermostat control the fan during  
a call for heat. Will not appear if  
Heat Pump is “ON.  
GAS  
ELEC  
This step connects the indoor  
sensor with the master  
thermostat. The previous step  
remote sensor must be set to  
YES in order to connect an indoor  
sensor.  
The number shown  
represents the zone.  
1
Use or to select the  
zone you wish to connect.  
The zone setting on the  
master and the indoor  
sensors must be the same to  
connect. See indoor sensors  
user guide for detailed  
connection information.  
See note below for more  
information.  
Finding  
Sensor  
For Dual Fuel applications (Gas/  
Fossil fuel Auxiliary Heat), turn  
this setting ON to LOCKOUT the  
Heat Pump (Y) when Auxiliary  
Heat (W2) is on. If desired - This  
can also be used with Electric  
Auxiliary.  
OFF Will allow Y(1st stage of  
Heat) and W2 (Aux Heat) to  
run together if called for.  
OFF  
1
Dual Fuel  
Auxiliary for  
Heat  
ON Will de-energize Y termi-  
nal 45 seconds after a call for  
Auxiliary Heat (W2).  
FINDING  
SENSOR  
Pump  
A6  
OFF  
OFF  
Will only appear  
if Heat pump  
setting is turned  
ON.  
Disable the sensor on the master.  
At least one indoor remote sensor  
must be connected to disable the  
local sensor.  
YES enables local sensor.  
NO disables local sensor.  
YES  
Local Temp  
Sensor  
LOCAL  
TEMP  
SENSOR  
YES  
The cooling fan delay setting will  
delay the fan from coming on in  
cool mode and keep it running  
after the compressor shuts off  
for a short time to save energy in  
some systems.  
You can set the cooling fan  
OFF  
Turns on the heat for 10 minutes  
each hour if unable to communi-  
cate with the master thermostat  
if there has been a call for heat in  
the last 24 hours.  
YES enables freeze protection.  
NO disables freeze protection.  
delay to OFF, 15, 30, 60 or 90  
seconds. If 15, 30, 60, or 90 is  
selected the fan will not turn  
on for that many seconds  
Cooling Fan  
Delay  
Freeze  
Protection  
COOL  
FAN  
DELAY  
YES  
when there is a call for cool  
and will run for that many  
seconds after satisfying a call  
for cool.  
FREEZE  
PROTECTION  
23  
24  
Technician Setup  
Technician Setup  
Tech Setup Steps  
LCD Will Show Adjustment Options  
Default  
Note:  
Up to four indoor temperature sensors can be connected to one  
Option for how DHM terminal  
energizes.  
Use the or key to  
select the one of the four  
options.  
3
thermostat. This allows for 5 sensing points (zones). For example: the  
local (thermostat) plus four indoor sensors enables 5 sensing points.  
To connect an indoor sensor to a thermostat, select 1 on the FINDING  
SENSOR technician setup step. Then hold down the light button on the  
indoor sensor until it beeps, while in ZONE technician setup step on the  
indoor sensor. To connect a second indoor sensor change the  
thermostat to read 2 and change the indoor sensor to zone 2. The zone  
setting must match between the thermostat and the indoor sensor to  
connect. When the connection is established the thermostat will show  
FOUND + NAME of the indoor sensor in the system information area of  
display.  
DHM  
Terminal  
Note: Set as option 1 if DEHUM  
with AC is set to YES.  
1
View the DEHUM terminal  
chart below for an  
explanation of these options.  
dHM  
TERMINAL  
You can configure the D Terminal  
as normally-open or normally  
closed.  
NO= Normally Open  
NC= Normally Closed  
See Note Below  
Use the or key to  
select NO or NC.  
If NO is selected, D will  
energize to dehumidify. If  
NC is selected, D will be  
normally energized. D will  
de-energize to dehumidify.  
Dehumidify  
Relay  
NO  
dEHUMIDIFY  
dELAY  
This feature allows the ther-  
mostat to keep multiple stages  
of heat or cool energized until  
setpoint is satisfied.  
Use the or key to  
turn on or off.  
OFF  
Satisfy  
Setpoint  
Balance Point:  
OFF  
OFF  
The system operates differently when a balance point is used. On a dual  
fuel system, the balance point outdoor temperature setting will be the  
outdoor temperature at which the thermostat chooses either the heat  
pump or gas furnace. For example: A balance point setting of 30°F will  
turn on only the heat pump above 30°F and only the gas furnace below  
30°F. Y1 will be stage one above 30°F and W2 will be stage one below  
30°F. A heat pump with electric auciliary will energize the heat pump  
above and below balance point. The electric auxiliary will only energize  
below balance point. For Example: A balance point setting of 40°F, will  
turn on the heat pump above 40°F and turn on the heat pump and  
electric auxiliary below 40°F.  
SS STAGING  
OFF  
This feature allows a delay to  
occur when a second and third  
stage is needed. This allows the  
previous stage extra time to  
satisfy setpoint.  
Use the or key to se-  
lect the number of minutes  
to delay each stage.  
Staging  
Delay  
OFF 5, 10, 15, 30, 45, 60, 90  
delay minutes.  
STAGING  
DELAY  
Note: When the dehumidify terminal is configured as normally-closed,  
the base module D terminal LED indicator will be lit when the relay is  
closed. When the thermostat calls for dehumidification, the D terminal  
LED indicator will turn off.  
Reminders  
DHM Terminal  
HUM Terminal  
Once a reminder has been turned on and set, the elapsed time can be  
checked by navigating to its tech setup step. The elapsed time will then  
appear in the text field. It can also be reset at that time by holding down  
the set CLEAN button for 3 seconds. Resetting an expired  
reminder can be done without entering tech setup, by holding down  
the set CLEAN button for 3 seconds from the home screen.  
HUM terminal energizes when the ambient  
humidity is...  
DUM terminal energizes when the ambient  
humidity is...  
OPTIONS  
1
OPTIONS  
1
Below the humidity setpoint and heat or  
fan is energized.  
Above the humidity setpoint and cool or fan  
is energized.  
Below the humidity setpoint and heat is  
energized.  
Above the humidity setpoint. It will also  
energize the fan during a call for dehumidity.  
2
3
2
3
Below the humidity setpoint. It will also  
energize the fan during a call for humidity.  
Above the humidity setpoint.  
Above the humidity setpoint and the  
compressor is not running.  
4
Below the humidity setpoint.  
4
27  
28  
GeneralDetails
NameVIVE TP-S-955WH Programmable Thermostat Instruction Manual
MakeVive
LanguageEnglish
FiletypePDF (Download)
File size0.67 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
VIVE TP-N-751 Programmable Thermostat Installation Guide
VIVE TP-N-751 Programmable Thermostat Installation Guide
VIVE TP-S-855C Digital Programmable Thermostat Instruction Manual
VIVE TP-S-855C Digital Programmable Thermostat Instruction Manual

VIVE TP-S-955WH Programmable Thermostat Instruction Manual