Home > Network Thermostat > Network Thermostat NetX X7 Series Thermostat Instruction Manual

Network Thermostat NetX X7 Series Thermostat Instruction Manual

Example: With Humidify at 55% and a Variance of 5%, a call for  
dehumidification would start at 60% and turn off when the  
humidity level drops to 50%.  
INTRODUCTION  
ACCESSORY PORT  
This addendum addresses the special controls available using  
the K/H/D and K2 terminals on the X7 Series thermostats. This  
includes control of humidity, fresh air damper, 7-day / 4-event  
relay scheduling, manual relay operation, and Indoor Air  
Quality (IAQ) Control  
The accessory port allows the connection of various NetX  
options, including the NT-MOD-ULE wireless sensor  
coordinator, the NT-CO2 carbon dioxide sensor, or other future  
accessories.  
FRESH AIR DAMPER OPERATION (K/H/D OR K2)  
When set to 'Damper', the relay will control a 2-position (power  
open, spring return) damper for fresh air ventilation.  
NetX™ X7 Series  
Thermostat  
K/H/D RELAY - GENERAL  
The K/H/D relay can be configured to function as any one of  
the following controls:  
The ‘When Occupied’ setting will open the damper and turn on  
the fan during occupied schedule periods from the thermostat’s  
normal 7-day schedule.  
K/H/D & K2 INSTALLATION ADDENDUM  
The ‘x min/hr’ setting will open the damper and turn on the fan  
for the set number of minutes selected. Outdoor Temperature  
and Humidity Limits allow the setting of the boundaries for  
energizing the damper, between 120°F (49°C) and -40°F (-40°C),  
and 0% RH to 100% RH.  
● Humidification; with or without independent equipment  
● Dehumidification; with or without independent equipment  
● Fresh Air Damper  
CO2: 944ppm  
●
M
a
n
u
a
l
R
e
l
a
y
O
p
e
r
a
t
i
o
n
● Programmable Schedule *  
● Indoor Air Quality Control *  
SCHEDULE RELAY OPERATION (K/H/D OR K2)  
* Can be configured for use on K/H/D or K2, but not both  
When set to 'Schedule', the relay can be configured to turn on,  
off, or pulse up to 4 times per day, 7 days a week. The pulsed-on  
option can be configured from 0.2sec to 2.0sec in 0.1sec  
increments.  
K2 RELAY - GENERAL  
The K2 relay can be configured to function as any one of the  
following controls:  
MANUAL RELAY OPERATION (K/H/D AND K2)  
When set to 'Manual', the relay can be turned on or off using any  
of the remote connection options.  
●
F
r
e
s
h
A
i
r
D
a
m
p
e
r
● Manual Relay Operation  
● Programmable Schedule *  
● Indoor Air Quality Control *  
* Can be configured for use on K/H/D or K2, but not both  
INDOOR AIR QUALITY (IAQ) OPERATION(K/H/D  
OR K2)  
When set to 'IAQ', the relay can control multiple types of IAQ  
equipment, with either manual or automatic operation.  
HUMIDITY OPERATION (K/H/D RELAY ONLY)  
Humidification:  
TABLE OF CONTENTS  
Before You Start  
Introduction  
K/H/D Relay - General  
K2 Relay - General  
Humidity Operation (K/H/D Relay Only)  
Fresh Air Damper Operation (K/H/D or K2)  
Schedule Relay Operation (K/H/D or K2)  
Manual Relay Operation (K/H/D and K2)  
Indoor Air Quality (IAQ) Operation(K/H/D or K2)  
Accessory port  
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
When set to 'Humidification', this feature allows the selection  
of a humidification call only when the heat is running, or  
independent of a heating call.  
Integrated HVAC - Occupied  
Use when IAQ equipment is located inside the HVAC equipment  
or ductwork. This setting will turn on the IAQ equipment and the  
HVAC fan during occupied schedule periods from the  
thermostat’s normal 7-day schedules.  
The relay energizes a humidification call when the indoor  
relative humidity drops below the value selected, with a  
programmable variance of ± 2%, 3%, or 5% RH.  
Stand Alone - Occupied  
Example: With Humidify at 35% and a Variance of 5%, a call for  
humidification would start at 30% and turn off when the  
humidity level reached 40%  
Use when IAQ equipment is located inside the HVAC equipment  
or ductwork. This setting will turn on the IAQ equipment during  
occupied schedule periods from the thermostat’s normal 7-day  
schedules.  
Dehumidification:  
CO2 Introduction  
When set to 'Dehumidification', this feature allows the  
selection of a dehumidification call only when the cooling is  
running, or independent of a cooling call.  
Integrated HVAC - Manual  
Access the Installer Menu  
Access the First CO2 Settings  
Setting the CO2 Display  
Setting the CO2 Alert Setting  
Clear CO2 Max Setting  
Use when IAQ equipment is located inside the HVAC equipment  
or ductwork. This setting will allow the manual turning on or off  
of the IAQ equipment and the HVAC fan. Use this setting for  
extended occupied or unoccupied periods.  
When "With Cooling Only" is selected, and there is no  
dedicated dehumidification function integrated within the  
equipment, cooling will be initiated and the cooling set point  
will automatically be lowered by 2 degrees from the scheduled  
cooling set point to allow increased equipment run time and  
decreased space humidity levels.  
Stand Alone - Manual  
Use when IAQ equipment is located inside the HVAC equipment  
or ductwork. This setting will allow the manual turning on or off  
of the IAQ equipment. Use this setting for extended occupied or  
unoccupied periods.  
BEFORE YOU START  
Please read the entire addendum. The thermostat will need  
to be correctly wired and configured for proper operation.  
Basic HVAC configuration can be performed from the  
thermostat touchscreen and advanced settings can be  
accessed on the embedded web pages and the Internet.  
The relay energizes a dehumidification call when the indoor  
relative humidity rises above the value selected, with a  
programmable variance of ± 2%, 3%, or 5% RH  
240282-03  
age 1  
GeneralDetails
NameNetwork Thermostat NetX X7 Series Thermostat Instruction Manual
MakeNetwork Thermostat
LanguageEnglish
FiletypePDF (Download)
File size0.14 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Network Thermostat X7-Series Thermostat Installation Guide
Network Thermostat X7-Series Thermostat Installation Guide
Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat NetXTM X-Series Thermostat Installation Guide
Network Thermostat NetXTM X-Series Thermostat Installation Guide
network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual
network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual
network thermostat NetX X Series Thermostat Instruction Manual
network thermostat NetX X Series Thermostat Instruction Manual
network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual
network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual
network thermostat X-Series Ethernet Thermostat Instruction Manual
network thermostat X-Series Ethernet Thermostat Instruction Manual
network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions
network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions

Network Thermostat NetX X7 Series Thermostat Instruction Manual
Get the free PDF manual for the Network Thermostat NetX X7 Series Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Network Thermostat NetX X7 Manual: Questions and Answers

What is the difference between humidification and dehumidification on the Network Thermostat NetX X7?

Humidification energizes when humidity drops below a set point; dehumidification energizes when humidity rises above it. Instruction Manual, p. 1

How do I configure the K/H/D relay on the Network Thermostat NetX X7?

Access the thermostat touchscreen for basic configuration or embedded web pages and the Internet for advanced settings.

  1. Read the entire addendum before starting.
  2. Ensure the thermostat is correctly wired.
  3. Choose the desired function: humidification, dehumidification, fresh air damper, manual relay operation, programmable schedule, or IAQ control. Instruction Manual, p. 1

What does the 'When Occupied' setting do on the Network Thermostat NetX X7 damper?

It opens the fresh air damper and turns on the fan during occupied schedule periods from the thermostat's 7-day schedule. Instruction Manual, p. 1

Can I set outdoor temperature limits for the damper on the Network Thermostat NetX X7?

Yes, outdoor temperature limits can be set between 120°F (49°C) and -40°F (-40°C), and humidity limits between 0% RH and 100% RH. Instruction Manual, p. 1

More Network Thermostat thermostat manuals