Example: With Humidify at 55% and a Variance of 5%, a call for
dehumidification would start at 60% and turn off when the
humidity level drops to 50%.
INTRODUCTION
ACCESSORY PORT
This addendum addresses the special controls available using
the K/H/D and K2 terminals on the X7 Series thermostats. This
includes control of humidity, fresh air damper, 7-day / 4-event
relay scheduling, manual relay operation, and Indoor Air
Quality (IAQ) Control
The accessory port allows the connection of various NetX
options, including the NT-MOD-ULE wireless sensor
coordinator, the NT-CO2 carbon dioxide sensor, or other future
accessories.
FRESH AIR DAMPER OPERATION (K/H/D OR K2)
When set to 'Damper', the relay will control a 2-position (power
open, spring return) damper for fresh air ventilation.
NetX™ X7 Series
Thermostat
K/H/D RELAY - GENERAL
The K/H/D relay can be configured to function as any one of
the following controls:
The ‘When Occupied’ setting will open the damper and turn on
the fan during occupied schedule periods from the thermostat’s
normal 7-day schedule.
K/H/D & K2 INSTALLATION ADDENDUM
The ‘x min/hr’ setting will open the damper and turn on the fan
for the set number of minutes selected. Outdoor Temperature
and Humidity Limits allow the setting of the boundaries for
energizing the damper, between 120°F (49°C) and -40°F (-40°C),
and 0% RH to 100% RH.
● Humidification; with or without independent equipment
● Dehumidification; with or without independent equipment
● Fresh Air Damper
CO2: 944ppm
●
M
a
n
u
a
l
R
e
l
a
y
O
p
e
r
a
t
i
o
n
● Programmable Schedule *
● Indoor Air Quality Control *
SCHEDULE RELAY OPERATION (K/H/D OR K2)
* Can be configured for use on K/H/D or K2, but not both
When set to 'Schedule', the relay can be configured to turn on,
off, or pulse up to 4 times per day, 7 days a week. The pulsed-on
option can be configured from 0.2sec to 2.0sec in 0.1sec
increments.
K2 RELAY - GENERAL
The K2 relay can be configured to function as any one of the
following controls:
MANUAL RELAY OPERATION (K/H/D AND K2)
When set to 'Manual', the relay can be turned on or off using any
of the remote connection options.
●
F
r
e
s
h
A
i
r
D
a
m
p
e
r
● Manual Relay Operation
● Programmable Schedule *
● Indoor Air Quality Control *
* Can be configured for use on K/H/D or K2, but not both
INDOOR AIR QUALITY (IAQ) OPERATION(K/H/D
OR K2)
When set to 'IAQ', the relay can control multiple types of IAQ
equipment, with either manual or automatic operation.
HUMIDITY OPERATION (K/H/D RELAY ONLY)
Humidification:
TABLE OF CONTENTS
Before You Start
Introduction
K/H/D Relay - General
K2 Relay - General
Humidity Operation (K/H/D Relay Only)
Fresh Air Damper Operation (K/H/D or K2)
Schedule Relay Operation (K/H/D or K2)
Manual Relay Operation (K/H/D and K2)
Indoor Air Quality (IAQ) Operation(K/H/D or K2)
Accessory port
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
When set to 'Humidification', this feature allows the selection
of a humidification call only when the heat is running, or
independent of a heating call.
Integrated HVAC - Occupied
Use when IAQ equipment is located inside the HVAC equipment
or ductwork. This setting will turn on the IAQ equipment and the
HVAC fan during occupied schedule periods from the
thermostat’s normal 7-day schedules.
The relay energizes a humidification call when the indoor
relative humidity drops below the value selected, with a
programmable variance of ± 2%, 3%, or 5% RH.
Stand Alone - Occupied
Example: With Humidify at 35% and a Variance of 5%, a call for
humidification would start at 30% and turn off when the
humidity level reached 40%
Use when IAQ equipment is located inside the HVAC equipment
or ductwork. This setting will turn on the IAQ equipment during
occupied schedule periods from the thermostat’s normal 7-day
schedules.
Dehumidification:
CO2 Introduction
When set to 'Dehumidification', this feature allows the
selection of a dehumidification call only when the cooling is
running, or independent of a cooling call.
Integrated HVAC - Manual
Access the Installer Menu
Access the First CO2 Settings
Setting the CO2 Display
Setting the CO2 Alert Setting
Clear CO2 Max Setting
Use when IAQ equipment is located inside the HVAC equipment
or ductwork. This setting will allow the manual turning on or off
of the IAQ equipment and the HVAC fan. Use this setting for
extended occupied or unoccupied periods.
When "With Cooling Only" is selected, and there is no
dedicated dehumidification function integrated within the
equipment, cooling will be initiated and the cooling set point
will automatically be lowered by 2 degrees from the scheduled
cooling set point to allow increased equipment run time and
decreased space humidity levels.
Stand Alone - Manual
Use when IAQ equipment is located inside the HVAC equipment
or ductwork. This setting will allow the manual turning on or off
of the IAQ equipment. Use this setting for extended occupied or
unoccupied periods.
BEFORE YOU START
Please read the entire addendum. The thermostat will need
to be correctly wired and configured for proper operation.
Basic HVAC configuration can be performed from the
thermostat touchscreen and advanced settings can be
accessed on the embedded web pages and the Internet.
The relay energizes a dehumidification call when the indoor
relative humidity rises above the value selected, with a
programmable variance of ± 2%, 3%, or 5% RH
240282-03
| General | Details |
|---|---|
| Name | Network Thermostat NetX X7 Series Thermostat Instruction Manual |
| Make | Network Thermostat |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.14 MB |

Network Thermostat X7-Series Thermostat Installation Guide

Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat NetXTM X-Series Thermostat Installation Guide

network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual

network thermostat NetX X Series Thermostat Instruction Manual

network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual

network thermostat X-Series Ethernet Thermostat Instruction Manual

network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions

Network Thermostat NetX X7 Manual: Questions and Answers
What is the difference between humidification and dehumidification on the Network Thermostat NetX X7?
Humidification energizes when humidity drops below a set point; dehumidification energizes when humidity rises above it. Instruction Manual, p. 1
How do I configure the K/H/D relay on the Network Thermostat NetX X7?
Access the thermostat touchscreen for basic configuration or embedded web pages and the Internet for advanced settings.
- Read the entire addendum before starting.
- Ensure the thermostat is correctly wired.
- Choose the desired function: humidification, dehumidification, fresh air damper, manual relay operation, programmable schedule, or IAQ control. Instruction Manual, p. 1
What does the 'When Occupied' setting do on the Network Thermostat NetX X7 damper?
It opens the fresh air damper and turns on the fan during occupied schedule periods from the thermostat's 7-day schedule. Instruction Manual, p. 1
Can I set outdoor temperature limits for the damper on the Network Thermostat NetX X7?
Yes, outdoor temperature limits can be set between 120°F (49°C) and -40°F (-40°C), and humidity limits between 0% RH and 100% RH. Instruction Manual, p. 1