FRESH AIR DAMPER OPERATION
(K/H/D OR K2)
When set to 'Damper', the relay will control a 2-position (power open, spring
return) damper for fresh air ventilation.
K/H/D RELAY - GENERAL
The K/H/D relay can be configured to function as any one of the
following controls:
•
•
•
•
•
•
Humidification; with or without independent equipment
Dehumidification; with or without independent equipment
Fresh Air Damper
The ‘When Occupied’ setting will open the damper and turn on the fan
during occupied schedule periods from the thermostat’s normal 7-day
schedules.
NetX™ X7-Series
Thermostat
The ‘x min/hr’ setting will open the damper and turn on the fan for the set
number of minutes selected.
Manual Relay Operation
K/H/D & K2 INSTALLATION ADDENDUM
Programmable Schedule *
Outdoor Temperature and Humidity Limits allow the setting of the
boundaries for energizing the damper, between 120°F (49°C) and -40°F (-
40°C), and 0% RH to 100% RH.
Indoor Air Quality Control *
* Can be configured for use on K/H/D or K2, but not both
SCHEDULE RELAY OPERATION
(K/H/D OR K2)
When set to 'Schedule', the relay can be configured to turn on, off, or pulse
up to 4 times per day, 7 days a week. The pulsed on option can be
configured from 0.2sec to 2.0sec in 0.1sec increments.
K2 RELAY - GENERAL
The K2 relay can be configured to function as any one of the
following controls:
•
•
•
•
Fresh Air Damper
Manual Relay Operation
Programmable Schedule *
Indoor Air Quality Control *
MANUAL RELAY OPERATION
(K/H/D AND K2)
When set to 'Manual', the relay can turned on or off using any of the remote
connection options.
* Can be configured for use on K/H/D or K2, but not both
HUMIDITY OPERATION
(K/H/D RELAY ONLY)
Humidification:
When set to 'Humidification', this feature allows selection of a
humidification call only when the heat is running, or independent of a
heating call.
INDOOR AIR QUALITY (IAQ) OPERATION
(K/H/D OR K2)
When set to 'IAQ', the relay can control multiple types of IAQ equipment,
with either manual or automatic operation.
WWW.NETWORKTHERMOSTAT.COM
TABLE OF CONTENTS
•
•
•
•
•
•
•
•
•
•
Before You Start
Introduction
K/H/D Relay - General
K2 Relay - General
Humidity Operation
Fresh Air Damper Operation
Programmable Schedule Operation
Manual Relay Operation
Indoor Air Quality (IAQ) Operation
Accessory Port
1
1
1
1
1
1
1
1
1
1
Integrated HVAC - Occupied
Use when IAQ equipment is located inside the HVAC equipment or
ductwork. This setting will turn on the IAQ equipment and the HVAC fan
during occupied schedule periods from the thermostat’s normal 7-day
schedules.
The relay energizes a humidification call when the indoor relative
humidity drops below the value selected, with programmable variance of
+/- 2%, 3% or 5% RH.
Stand Alone - Occupied
Example: With Humidify at 35% and a Variance of 5%, a call for
humidification would start at 30% and turn off when the humidity level
reached 40%
Use when IAQ equipment is located inside the HVAC equipment or
ductwork. This setting will turn on the IAQ equipment during occupied
schedule periods from the thermostat’s normal 7-day schedules.
Dehumidification:
Integrated HVAC - Manual
When set to 'Dehumidification', this feature allows selection of a
dehumidification call only when the cooling is running, or independent of
a cooling call.
Use when IAQ equipment is located inside the HVAC equipment or
ductwork. This setting will allow the manual turning on or off of the IAQ
equipment and the HVAC fan. Use this setting for extended occupied or
unoccupied periods.
BEFORE YOU START
Please read the entire addendum. The thermostat will need
to be correctly wired and configured for proper operation.
Basic HVAC configuration can be performed from the
thermostat touchscreen and advanced settings can be
accessed on the embedded web pages and/or the Internet.
When "With Cooling Only" is selected, and there is no dedicated
dehumidification function integrated within the equipment, cooling will
be initiated and the cooling set point will automatically be lowered by 2
degrees from the scheduled cooling set point to allow increased
equipment run time and decreased space humidity levels.
Stand Alone - Manual
Use when IAQ equipment is located inside the HVAC equipment or
ductwork. This setting will allow the manual turning on or off of the IAQ
equipment. Use this setting for extended occupied or unoccupied periods
.
INTRODUCTION
The relay energizes a dehumidification call when the indoor relative
humidity rises above the value selected, with a programmable variance of
+/- 2%, 3% or 5% RH
This addendum addresses the special controls available using
the K/H/D and K2 terminals on the X7 Series thermostats.
This includes control of humidity, fresh air damper, 7-day / 4-
event relay scheduling, manual relay operation and Indoor Air
Quality (IAQ) Control
ACCESSORY PORT
Example: With Humidify at 55% and a Variance of 5%, a call for
dehumidification would start at 60% and turn off when the humidity level
drops to 50%.
The accessory port allows connection of various NetX options,
including the NT-MOD-ULE wireless sensor coordinator, the NT-
CO2 carbon dioxide sensor, or other future accessories.
240282-00
| General | Details |
|---|---|
| Name | Network Thermostat X7-Series Thermostat Installation Guide |
| Make | Network Thermostat |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.62 MB |

Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat NetXTM X-Series Thermostat Installation Guide

network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual

network thermostat NetX X Series Thermostat Instruction Manual

network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual

network thermostat X-Series Ethernet Thermostat Instruction Manual

Network Thermostat NetX X7 Series Thermostat Instruction Manual

network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions

Network Thermostat X7-Series Thermostat Installation Guide Overview
Summary of Contents
- Page 1: Fresh air damper operation controls a 2-position damper for ventilation. The K/H/D relay can be configured for various controls including humidification and dehumidification. The 'When Occupied' setting opens the damper and activates the fan during scheduled periods. Outdoor temperature and humidity limits set boundaries for energizing the damper. The relay can be configured to turn on, off, or pulse multiple times per day. The K2 relay functions similarly to the K/H/D relay with various control options. Humidity operation allows for humidification calls based on heating status. Indoor air quality operation controls multiple types of IAQ equipment. The accessory port connects various NetX options for enhanced functionality. This addendum details special controls available using K/H/D and K2 terminals on X7 Series thermostats.