FRESH AIR DAMPER OPERATION  
(K/H/D OR K2)  
When set to 'Damper', the relay will control a 2-position (power open, spring  
return) damper for fresh air ventilation.  
K/H/D RELAY - GENERAL  
The K/H/D relay can be configured to function as any one of the  
following controls:  
Humidification; with or without independent equipment  
Dehumidification; with or without independent equipment  
Fresh Air Damper  
The ‘When Occupied’ setting will open the damper and turn on the fan  
during occupied schedule periods from the thermostats normal 7-day  
schedules.  
NetX™ X7-Series  
Thermostat  
The ‘x min/hr’ setting will open the damper and turn on the fan for the set  
number of minutes selected.  
Manual Relay Operation  
K/H/D & K2 INSTALLATION ADDENDUM  
Programmable Schedule *  
Outdoor Temperature and Humidity Limits allow the setting of the  
boundaries for energizing the damper, between 120°F (49°C) and -40°F (-  
40°C), and 0% RH to 100% RH.  
Indoor Air Quality Control *  
* Can be configured for use on K/H/D or K2, but not both  
SCHEDULE RELAY OPERATION  
(K/H/D OR K2)  
When set to 'Schedule', the relay can be configured to turn on, off, or pulse  
up to 4 times per day, 7 days a week. The pulsed on option can be  
configured from 0.2sec to 2.0sec in 0.1sec increments.  
K2 RELAY - GENERAL  
The K2 relay can be configured to function as any one of the  
following controls:  
Fresh Air Damper  
Manual Relay Operation  
Programmable Schedule *  
Indoor Air Quality Control *  
MANUAL RELAY OPERATION  
(K/H/D AND K2)  
When set to 'Manual', the relay can turned on or off using any of the remote  
connection options.  
* Can be configured for use on K/H/D or K2, but not both  
HUMIDITY OPERATION  
(K/H/D RELAY ONLY)  
Humidification:  
When set to 'Humidification', this feature allows selection of a  
humidification call only when the heat is running, or independent of a  
heating call.  
INDOOR AIR QUALITY (IAQ) OPERATION  
(K/H/D OR K2)  
When set to 'IAQ', the relay can control multiple types of IAQ equipment,  
with either manual or automatic operation.  
WWW.NETWORKTHERMOSTAT.COM  
TABLE OF CONTENTS  
Before You Start  
Introduction  
K/H/D Relay - General  
K2 Relay - General  
Humidity Operation  
Fresh Air Damper Operation  
Programmable Schedule Operation  
Manual Relay Operation  
Indoor Air Quality (IAQ) Operation  
Accessory Port  
1
1
1
1
1
1
1
1
1
1
Integrated HVAC - Occupied  
Use when IAQ equipment is located inside the HVAC equipment or  
ductwork. This setting will turn on the IAQ equipment and the HVAC fan  
during occupied schedule periods from the thermostats normal 7-day  
schedules.  
The relay energizes a humidification call when the indoor relative  
humidity drops below the value selected, with programmable variance of  
+/- 2%, 3% or 5% RH.  
Stand Alone - Occupied  
Example: With Humidify at 35% and a Variance of 5%, a call for  
humidification would start at 30% and turn off when the humidity level  
reached 40%  
Use when IAQ equipment is located inside the HVAC equipment or  
ductwork. This setting will turn on the IAQ equipment during occupied  
schedule periods from the thermostats normal 7-day schedules.  
Dehumidification:  
Integrated HVAC - Manual  
When set to 'Dehumidification', this feature allows selection of a  
dehumidification call only when the cooling is running, or independent of  
a cooling call.  
Use when IAQ equipment is located inside the HVAC equipment or  
ductwork. This setting will allow the manual turning on or off of the IAQ  
equipment and the HVAC fan. Use this setting for extended occupied or  
unoccupied periods.  
BEFORE YOU START  
Please read the entire addendum. The thermostat will need  
to be correctly wired and configured for proper operation.  
Basic HVAC configuration can be performed from the  
thermostat touchscreen and advanced settings can be  
accessed on the embedded web pages and/or the Internet.  
When "With Cooling Only" is selected, and there is no dedicated  
dehumidification function integrated within the equipment, cooling will  
be initiated and the cooling set point will automatically be lowered by 2  
degrees from the scheduled cooling set point to allow increased  
equipment run time and decreased space humidity levels.  
Stand Alone - Manual  
Use when IAQ equipment is located inside the HVAC equipment or  
ductwork. This setting will allow the manual turning on or off of the IAQ  
equipment. Use this setting for extended occupied or unoccupied periods  
.
INTRODUCTION  
The relay energizes a dehumidification call when the indoor relative  
humidity rises above the value selected, with a programmable variance of  
+/- 2%, 3% or 5% RH  
This addendum addresses the special controls available using  
the K/H/D and K2 terminals on the X7 Series thermostats.  
This includes control of humidity, fresh air damper, 7-day / 4-  
event relay scheduling, manual relay operation and Indoor Air  
Quality (IAQ) Control  
ACCESSORY PORT  
Example: With Humidify at 55% and a Variance of 5%, a call for  
dehumidification would start at 60% and turn off when the humidity level  
drops to 50%.  
The accessory port allows connection of various NetX options,  
including the NT-MOD-ULE wireless sensor coordinator, the NT-  
CO2 carbon dioxide sensor, or other future accessories.  
240282-00  
age 1  
GeneralDetails
NameNetwork Thermostat X7-Series Thermostat Installation Guide
MakeNetwork Thermostat
LanguageEnglish
FiletypePDF (Download)
File size0.62 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual
Network Thermostat NetXTM X-Series Thermostat Installation Guide
Network Thermostat NetXTM X-Series Thermostat Installation Guide
network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual
network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual
network thermostat NetX X Series Thermostat Instruction Manual
network thermostat NetX X Series Thermostat Instruction Manual
network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual
network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual
network thermostat X-Series Ethernet Thermostat Instruction Manual
network thermostat X-Series Ethernet Thermostat Instruction Manual
Network Thermostat NetX X7 Series Thermostat Instruction Manual
Network Thermostat NetX X7 Series Thermostat Instruction Manual
network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions
network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions

Network Thermostat X7-Series Thermostat Installation Guide
Get the free PDF manual for the Network Thermostat X7-Series Thermostat Installation Guide and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Network Thermostat X7-Series Thermostat Installation Guide Overview

Summary of Contents

  • Page 1: Fresh air damper operation controls a 2-position damper for ventilation. The K/H/D relay can be configured for various controls including humidification and dehumidification. The 'When Occupied' setting opens the damper and activates the fan during scheduled periods. Outdoor temperature and humidity limits set boundaries for energizing the damper. The relay can be configured to turn on, off, or pulse multiple times per day. The K2 relay functions similarly to the K/H/D relay with various control options. Humidity operation allows for humidification calls based on heating status. Indoor air quality operation controls multiple types of IAQ equipment. The accessory port connects various NetX options for enhanced functionality. This addendum details special controls available using K/H/D and K2 terminals on X7 Series thermostats.