This completes the CO2 settings that can be controlled from
the Installer Menu. Additional advanced settings can be
accessed on the embedded web pages and/or the Internet via
our NetX CloudConnect software. For more information go to
ACCESS THE FIRST CO2 SETTINGS
SETTING THE CO2 ALERT SETTING
After the display of the Faceplate and backplate firmware, the
By default, the CO2 Alert setting is set to trigger when the X7
thermostat detects a CO2 reading above the 1100 ppm (parts
per million) of CO2. When triggered, the alert can activate a relay
to open a fresh air damper to decrease the level of CO2 in the
menu will shift to the first setting Conventional/HP Use the
Right Arrow
button to navigate through the Installer Menu.
M
The first menu setting to adjust is CO2 Display
NetX™ X7 Series
Thermostat
control area. To adjust the alert level, use the Up
and Down
J
buttons. The level is changed in increments of 50 ppm (parts
K
per million). The range is from 500 ppm to 2000 ppm. Once the
desired level is set, press the Right Arrow
proceed to the Clear CO2 Max Setting.
button to save and
CO2 Display: On
M
CO2 INSTALLATION ADDENDUM
CO2 INTRODUCTION
This addendum addresses the installation and configuration
of the CO2 sensor for the X7C and X7 Series thermostats.
CO2 Alert @1100ppm
This includes the display options, alert levels, and resetting
the maximum level recorded.
NOTE: This addendum only applies to X7C Thermostats
A
or X7 thermostats with the optional NT-MOD-CO2 module
installed.
ACCESS THE INSTALLER MENU
SETTING THE CO2 DISPLAY
Press and hold the Menu Button
on the bottom left side of
D
The default CO Display setting is On. This means the CO2
setting will be v2isible on the upper left corner of the display
when the thermostat is in normal mode. The CO2 display can
also be turned off or set to display only when a high CO alert
the faceplate. Once in the Installer section, you will see the
Faceplate and Backplate firmware versions in the dot matrix
display.
is active. Use the Up
selection.
and Down
buttons to change2the
J
K
CLEAR CO2 MAX SETTING
By default, the Clear CO2 Max setting is set to No which means
the maximum recorded CO level will not reset until user
intervention. This setting ca2n be changed from No (does not
reset) to 12 midnight (resets automatically at 12 midnight), or Yes
(resets now). To adjust the Clear CO2 Max setting, use the
To accept the settings, press the Right Arrow button. This will
M
CO2: 944ppm
accept the setting and move you to the next setting CO2 Alert.
Up
and Down
buttons. To accept the new setting, press
J
K
button.
the Right Arrow
M
CO2 Display: On
Clear CO2 Max: No
Page 2
| General | Details |
|---|---|
| Name | Network Thermostat NetX X7 Series Thermostat Instruction Manual |
| Make | Network Thermostat |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.14 MB |

Network Thermostat X7-Series Thermostat Installation Guide

Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat NetXTM X-Series Thermostat Installation Guide

network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual

network thermostat NetX X Series Thermostat Instruction Manual

network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual

network thermostat X-Series Ethernet Thermostat Instruction Manual

network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions