VIVE TP-S-955WH Programmable Thermostat Instruction Manual
Wiring
Wiring
Terminal Designations on the Base Module
Power supply
Factory-installed jumper. Remove only when installing on 2-transformer systems
Use either O or B terminals for changeover valve
This thermostat is shipped from the factory to operate a conventional heating
and cooling system. This thermostat may also be configured for a heat pump
system. See the “heat pump”configuration step on page 23 of this manual to
configure the thermostat for heat pump applications.
If DEHUM relay requires a normally-energized input, set dehumidity relay to NC in
technician setup.
2 Heat 2 Cool
Conventional
System
2 Heat 2 Cool
Heat Pump
System
3 Heat 2 Cool
Heat Pump
System
Terminal
RC
Typical 2H/2C System: 1 Transformer
Transformer power
(cooling)
Transformer power
(cooling)
Transformer power
(cooling)
C
L2
L1(HOT)
Transformer power
(heating)
Transformer power
(heating)
Transformer power
(heating)
RH
C
RC
RH
Y
Transformer common
Transformer common
Transformer common
R
COMPRESSOR
RELAY
Heat pump changeover
Heat pump changeover
Energized in heating
B
C
valve energized in heating valve energized in heating
Heat pump changeover Heat pump changeover
valve energized in cooling valve energized in cooling
W/E
G
HEAT RELAY
FAN RELAY
Energized in cooling
Fan relay
O
G
W2
Y2
Fan relay
Fan relay
HEAT RELAY 2
First stage of
First stage of
First stage of heat
First stage of cool
Second stage of cool
W/E
emergency heat
emergency heat
COMPRESSOR
RELAY 2
First stage of heat & cool First stage of heat & cool
Y
Second stage of cool
Second stage of cool
Y2
& second stage of heat
Typical 3H/2C or 2H/1C Heat Pump System
Auxiliary heat relay,
second stage of heat
Auxiliary heat relay,
third stage of heat
Second stage of heat
W2
C
Humidify
Humidify
Humidify
H
D
L2
L1(HOT)
Dehumidify
Dehumidify
Dehumidify
RC
RH
R
Terminal Designations on the Master Thermostat
COMPRESSOR
RELAY
Y
C
2 Heat 2 Cool
Conventional
System
2 Heat 2 Cool
Heat Pump
System
3 Heat 2 Cool
Heat Pump
System
COOL CHANGE
OVER VALVE
EMERGENCY
HEAT
O
B
W/E
G
Terminal
HEAT CHANGE
OVER VALVE
W2
Y2
FAN RELAY
24 VAC
transformer power
24 VAC
transformer power
24 VAC transformer power
transformer common
R
C
AUXILIARY
HEAT
transformer common
transformer common
COMPRESSOR
RELAY 2
Powering the Master Thermostat
If you add indoor or outdoor remote sensors to this wireless system
you must hardwire the master thermostat.
15
16
Technician Setup
Technician Setup
This thermostat has a technician setup menu for easy installer
configuration. To set up the thermostat for your particular application:
Tech Setup Steps
LCD Will Show Adjustment Options
Default
The compressor short cycle delay
protects the compressor from
“short cycling”. This feature will
not allow the compressor to be
turned on for 5 minutes after it
was last turned off.
Selecting “ON”will not allow
the compressor to be turned
on for 5 minutes after the
last time the compressor was
on. Select “OF”to remove
this delay.
ON OF
Compressor
Short Cycle
Delay
1. Press the MENU button.
2. Press and hold the technician setup button for 3 seconds. This 3
second delay is designed so that homeowners do not accidentally
access the installer settings.
ON
CO
3. Configure the installer options as desired using the table below.
The swing setting often called
“cycle rate”, “differential”or
“anticipation”is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
The cooling swing setting
is adjustable from 0.2˚ to
2˚. For example: A swing
setting of 0.5˚ will turn the
cooling on at approximately
0.5˚ above the setpoint
and turn the cooling off at
approximately 0.5˚ below
the setpoint.
dF
0.5
Use the
or
keys to change settings and the next step
or previous step key to move from one step to another. Note: Only
press the DONE key when you want to exit the Technician Setup
options.
Cooling
Swing
0.5˚
CO
4. Press the DONE key to exit.
Tech Setup Steps
LCD Will Show Adjustment Options
Default
The swing setting often called
“cycle rate”, “differential”, or
“anticipation”is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
The heating swing setting is
adjustable from 0.2˚ to 2˚.
For example: A swing setting
of 0.5˚ will turn the heating
on at approximately 0.5˚
below the setpoint and turn
the heating off at 0.5˚ above
the setpoint.
dF
0.5
This feature will flash a reminder
You can adjust the filter
OFF
change reminder from “OFF”
after the elapsed run time to
remind the user to change the
filter. A setting of “OFF”will
disable this feature.
to 2000 hours of fan runtime
in 50 hour increments.
Heating
Swing
Filter Change
Reminder
0.4˚
PA
OFF
HE
PA
This feature allows the installer
to change the calibration of the
room temperature display. For
example, if the thermostat reads
70˚ and you would like it to read
72˚ then select +2.
You can adjust the room
temperature display to read
up to 4˚above or below the
factory calibrated reading.
0
Keypad lockout allows you to
configure the thermostat so that
some or all of the keys don’t
function.
PA= partial keypad lockout,
which locks all the keys except
Room
Temperature
Calibration
the
FU= full keypad lockout,
or
keys.
0˚F
Keypad
Lockout
which locks out all the keys.
CALIbRATE
This feature allows the installer
to select the minimum run
time for the compressor. For
example, a setting of 4 will force
the compressor to run for at
least 4 minutes every time the
compressor turns on, regardless
of the room temperature.
You can set the minimum
OFF
See Keypad Lockout Note
compressor run time to“OFF”,
“3”, “4”, or “5”minutes. If 3,4
or 5 is selected, the
Minimum
Compressor
On Time
compressor will run for
at least the selected time
before turning off.
Swing Setting Tip
OFF
The second stage will turn on at 2x the swing setting. The second stage
will turn off when 1x the swing is reached. For example, if the swing
setting is .5 degrees for heating and the thermostat is set at 70˚F, the first
stage will turn on at approximately 69.5˚F. The second stage will turn on
at 69˚F. The second stage will turn off at 69.5˚F and the first will turn off
at 70.5˚F. If the third stage is used, it will turn on at 68.5˚F and turn off at
approximately 69˚F.
Keypad Lockout Note: The selected keypad lockout functionality must
be activated after exiting tech setup. If you do not perform this
procedure, all keys will function freely. To lock the keypad hold down
the
unlock the display hold down the
and
keys for 3 seconds. You will see a lock in the display. To
and keys for 3 seconds.
20
19
| General | Details |
|---|---|
| Name | VIVE TP-S-955WH Programmable Thermostat Instruction Manual |
| Make | Vive |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.67 MB |

VIVE TP-N-751 Programmable Thermostat Installation Guide

VIVE TP-S-855C Digital Programmable Thermostat Instruction Manual






















