SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions
Technical Instructions
Document Number 155-016P25
April 12, 2018
Low Temperature Detection Cut-out and Alarm Thermostat
Prerequisites
WARNING:
This low temperature detection thermostat is designed for use only as
an operating control. Where an operating control failure would result
in personal injury and/or loss of property, it is the installer’s
responsibility to add devices (safety, limit controls) or systems (alarm,
supervisory systems) that protect against, or warn of control failure.
CAUTION:
The switch contact position (LINE-M2) may be in either an open or
closed state upon receipt due to possible exposure to freezing
temperatures during shipping. It is strongly recommended that the
reset button be manually pressed down and released before initial use
to restore the switch position to a normal operating state before
proceeding to installation; otherwise, the unit could remain in the
tripped state.
Specifications
Switch Action
Range
Main (LINE-M2) contacts open on
temperature drop, simultaneously auxiliary
contacts close
15 to 55°F (-9 to 13°C)
Maximum bulb temperature
Minimum differential
Sensing element
Bulb length
400°F (204°C)
5°F (2.8°C) Non-adjustable
Vapor filled
1/8-inch OD × 20 feet (6 m)
Manual
Reset action
Electrical rating
Weight
See Table 1
2.4 lb (1.1 kg)
Dimensions
See Figures 2 and 5
Approvals
UL file SA 10816
CSA file LR948
Operation
This thermostat incorporates a temperature sensing element of the vapor-filled type
which actuates a heavy duty contact through a rugged link mechanism.
Any one-foot length of the element subjected to temperatures below the
temperature setting of the thermostat will actuate the thermostat switch mechanism
regardless of the temperature being sensed by the remainder of the element. This
makes the thermostats ideal for protecting large coils where air stratification could
cause freezing conditions in a localized area.
The thermostat has a main and auxiliary contact unit. The main load circuit
(LINE-M2) opens on temperature drop and simultaneously, an auxiliary or alarm
circuit (LINE-Ml) closes on temperature drop.
NOTE: The reset button must be manually pressed down and released to resume
normal fan system operation.
Page 2
Siemens Industry, Inc.
| General | Details |
|---|---|
| Name | SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.1 MB |

SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual

SIEMENS RDG400 Room Thermostat Instruction Manual

SIEMENS M3182 Room Thermostat Instruction Manual

SIEMENS RDS120-B Smart Thermostat Instructions

SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual

SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual

SIEMENS RDH100RF/SET Room Thermostat Instruction Manual

SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide

SIEMENS RS485 Flush Mounted Room Thermostat User Manual

SIEMENS RDG260KN Room Thermostat Instruction Manual