SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions

Technical Instructions  
Document Number 155-016P25  
April 12, 2018  
Low Temperature Detection Cut-out and Alarm Thermostat  
Prerequisites  
WARNING:  
This low temperature detection thermostat is designed for use only as  
an operating control. Where an operating control failure would result  
in personal injury and/or loss of property, it is the installer’s  
responsibility to add devices (safety, limit controls) or systems (alarm,  
supervisory systems) that protect against, or warn of control failure.  
CAUTION:  
The switch contact position (LINE-M2) may be in either an open or  
closed state upon receipt due to possible exposure to freezing  
temperatures during shipping. It is strongly recommended that the  
reset button be manually pressed down and released before initial use  
to restore the switch position to a normal operating state before  
proceeding to installation; otherwise, the unit could remain in the  
tripped state.  
Specifications  
Switch Action  
Range  
Main (LINE-M2) contacts open on  
temperature drop, simultaneously auxiliary  
contacts close  
15 to 55°F (-9 to 13°C)  
Maximum bulb temperature  
Minimum differential  
Sensing element  
Bulb length  
400°F (204°C)  
5°F (2.8°C) Non-adjustable  
Vapor filled  
1/8-inch OD × 20 feet (6 m)  
Manual  
Reset action  
Electrical rating  
Weight  
See Table 1  
2.4 lb (1.1 kg)  
Dimensions  
See Figures 2 and 5  
Approvals  
UL file SA 10816  
CSA file LR948  
Operation  
This thermostat incorporates a temperature sensing element of the vapor-filled type  
which actuates a heavy duty contact through a rugged link mechanism.  
Any one-foot length of the element subjected to temperatures below the  
temperature setting of the thermostat will actuate the thermostat switch mechanism  
regardless of the temperature being sensed by the remainder of the element. This  
makes the thermostats ideal for protecting large coils where air stratification could  
cause freezing conditions in a localized area.  
The thermostat has a main and auxiliary contact unit. The main load circuit  
(LINE-M2) opens on temperature drop and simultaneously, an auxiliary or alarm  
circuit (LINE-Ml) closes on temperature drop.  
NOTE: The reset button must be manually pressed down and released to resume  
normal fan system operation.  
Page 2  
Siemens Industry, Inc.  
GeneralDetails
NameSIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.1 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions