SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions
Technical Instructions
Document Number 155-016P25
April 12, 2018
Low Temperature Detection Cut-out and Alarm Thermostat
Mounting and
Installation, Continued
Figure 1. Typical Mounting in Walk-in Duct.
Limited Access Ducts
(Figure 2)
1. Attach the mounting bracket to the thermostat with the two round head screws
provided.
2. Attach a mounting flange (Part Number 808-412) on the opposite side of the
duct (near the bottom) from where the thermostat will be mounted.
3. Mount a second flange on an 8-inch by 4-inch sheet metal plate. Cut an access
opening for the bulb on the duct diagonally across from the duct-mounted
flange. Drill mounting screw holes for the sheet metal plate.
4. Cut a length of copper tubing to fit diagonally across the duct. Stretch out the
bulb and wrap it around the tubing. See Figure 2.
5. Insert the tubing and bulb through the access hole and into the duct-mounted
flange. Fasten the 8-inch by 4-inch sheet metal plate to the duct.
6. Mount the thermostat on the outside of duct.
Page 4
Siemens Industry, Inc.
| General | Details |
|---|---|
| Name | SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.1 MB |

SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual

SIEMENS M3182 Room Thermostat Instruction Manual

SIEMENS RDS120-B Smart Thermostat Instructions

SIEMENS RDG400 Room Thermostat Instruction Manual

SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual

SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual

SIEMENS RDH100RF/SET Room Thermostat Instruction Manual

SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide

SIEMENS RS485 Flush Mounted Room Thermostat User Manual

SIEMENS RDG260KN Room Thermostat Instruction Manual