SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions
Low Temperature Detection Cut-out and Alarm Thermostat
Technical Instructions
Document Number 155-016P25
April 12, 2018
Figure 2. Bulb Mounting for Limited Access Ducts with 808-412 Mounting Flange.
WARNING:
Wiring
Disconnect the power supply before wiring connections are made to
avoid possible electrical shock or damage to the equipment.
Make all wiring connections using copper conductors only and in accordance with the
National Electrical Code and local regulations. Loads exceeding the rating of the
thermostat should be handled by means of a relay or motor starter.
An opening for 1/2-inch conduit is provided in the bottom of the thermostat enclosure.
See Figure 3 for a typical wiring diagram.
Figure 3. Typical Wiring Diagram.
CAUTION:
Use terminal screws furnished (#8-32 × 1/4-inch binder head screw).
Longer terminal screws can interfere with switch mechanism and
damage the switch.
Siemens Industry, Inc.
Page 5
| General | Details |
|---|---|
| Name | SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.1 MB |

SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual

SIEMENS RDG400 Room Thermostat Instruction Manual

SIEMENS M3182 Room Thermostat Instruction Manual

SIEMENS RDS120-B Smart Thermostat Instructions

SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual

SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual

SIEMENS RDH100RF/SET Room Thermostat Instruction Manual

SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide

SIEMENS RS485 Flush Mounted Room Thermostat User Manual

SIEMENS RDG260KN Room Thermostat Instruction Manual