Technical data
Technical data GM-TA (PCN 1244-017783)
EN
DE
FR
SV
Supply voltage
230 Vac, +10%/–10%, 50 Hz
Relay control
heating cable
Potential-free (max 230 Vac +10%),
max 16 A (resistive load)
Potential-free (max 230 Vac +10%),
switch-over contact, max 8 A
Relay alarm
Power consumption
Terminal size
Max 5 VA
Max. 2,5 mm2, screwed
Storage temperature
–20°C to +50°C
Operation ambient
temperature range
–25°C to +40°C
Switching hysteresis
Accuracy
+/– 1 K
+/– 1,5 K incl. sensor accuracy
Programmable parameters
Temperature setting range
Lower temperature range
Post heating time
Default
Set point: 0°C to 6°C
–5°C to –25°C
0 to 3 hours
2°C
–10°C
0,5 h
On: normal operation
Off: relay off (open)
Test: relay On (30 minutes)
Operating modus
Enclosure thermostat
Installation
DIN-rail-mounted
IP rating
IP 20
Ambient sensor GM-TA-AS (PCN 1244-017965) included
IP rating
IP 65
Installation
Wall mounted / outdoors
Ambient sensor type
Approvals
202AT +/–1% NTC 2.0 K @ 25°C
CE, UKCA, RoHS, REACH
Error codes
Ambient sensor open circuit or
short circuit / Check connections
and resistance
E1
E2
Internal error / Replace GM-TA
nVent.com/RAYCHEM
|
9
| General | Details |
|---|---|
| Name | nVent RAYCHEM GM-TA Thermostat Instruction Manual |
| Make | nVent RAYCHEM |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.31 MB |

nVent RAYCHEM ETS-05 Electronic Thermostat Instruction Manual

nVent RAYCHEM RAYSTAT-EX-02 Mechanical Thermostat Installation Guide

nVent RAYCHEM Elexant 3500i Electronic Thermostat Installation Guide

nVent RAYCHEM RayStat-M2 Thermostat Instruction Manual

nVent RAYCHEM Green Leaf Programmable Thermostat Instruction Manual

nVent RAYCHEM AT-TS-13 Surface Sensing Thermostat Instruction Manual

nVent RAYCHEM SENZ Wifi Programmable Floor Heating Thermostat User Guide