namron 4512737 Touch Zigbee 16A Thermostat Instruction Manual

ACVoltageDivisor  
int16U,  
Used together with above attributes, the real displayed voltage =  
RMSVoltage* ACVoltageMultiplier  
/ ACVoltageDivisor  
0x0601  
0x0602  
0x0603  
0x0604  
0x0605  
read-only  
int16U,  
ACCurrentMultiplier  
read-only  
ACCurrentDivisor  
int16U,  
Used together with above attributes, the real displayed current = RMSCurrent  
read-only  
* ACCurrentMultiplier  
/ ACCurrentDivisor  
int16U,  
ACPowerMultiplier  
read-only  
0x01  
ACPowerDivisor  
int16U,  
0x01  
Used together with above attributes, the real displayed power = Active Power *  
ACPowerMultiplie / ACPowerDivisor  
read-only  
ACAlarmsMask  
Specifies which configurable alarms may be generated, only  
Bit1: Current Overload is set, if set=0, then ACCurrentOverload=0, over  
current will not be detected  
0x0800  
0x0802  
int16U,  
ACCurrentOverload  
int16S ,  
Alarms when the current is over a certain value, 0, 10-16, unit is A, for the  
unit please refer to RMSCurrent, ACCurrentMultiplier, ACCurrent Divisor  
reportable  
read-only  
Proprietary Attributes:  
Attribute  
Type  
Manufacturer code  
Description  
OverCurrent  
Int8u,  
Over current value set by the user, range is 0, 10-16,  
ACCurrentOverload will change spontaneously if this  
value is modified.  
0x0000  
0x1224  
reportable  
5.2.7 Alarm-0x0009(Server)  
Please set a valid value for ACAlarmsMask of Electrical Measurement.  
The Alarm Server cluster can generate the following commands  
CmdID  
Description  
Alarm:  
0x00  
The alarm code of Electrical Measurement is 0,  
Proprietary command, Manufacturer code=0x1224  
CmdID  
Description  
Room air temperature over heat, not alarm code  
0x00  
5.2.8 Time-0x000A(server)  
The Time cluster is a general cluster for time it is based on a UTC time in seconds since 0 hrs 0 mins 0 sec on  
1st January 2000. Refer to [Z2] for ZigBee specification of the time cluster.  
The metering device will use this clusters as a client – provided that a suitable Time Server is available on the  
network (most likely on the Gateway/concentrator)  
If the device has bound TIME cluster, then the device will acquire the value of Local Time (0x0007)  
spontaneously.  
GeneralDetails
Namenamron 4512737 Touch Zigbee 16A Thermostat Instruction Manual
MakeNAMRON
LanguageEnglish
FiletypePDF (Download)
File size0.47 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
namron 1402746 Touch Thermostat Instruction Manual
namron 1402746 Touch Thermostat Instruction Manual
namron 4512738 Touch Zigbee 16A Thermostat Instruction Manual
namron 4512738 Touch Zigbee 16A Thermostat Instruction Manual
namron 16A 2.0 Zigbee Touch Thermostat Instruction Manual
namron 16A 2.0 Zigbee Touch Thermostat Instruction Manual
namron Touch Z Wave 16A Thermostat Instruction Manual
namron Touch Z Wave 16A Thermostat Instruction Manual

namron 4512737 Touch Zigbee 16A Thermostat Instruction Manual