HEATIT Z-TRM6 Matt Z-Wave Thermostat User Guide
STATEMENT REGARDING PRODUCTS FROM MULTIPLE
MANUFACTURERS
Please read this before installation
5. Set the primary controller in add mode (security/non
security).
FACTORY RESET
TECHNICAL DATA
Enter the menu by holding the Center button for about 5
seconds, navigate in the menu with the ”+” button til you see
FACT. Press the Center button until you see “-- --” blinking in
the display, then hold for about 5 seconds to perform a reset.
You may also initiate a reset by holding the Right and Center
buttons for 60 seconds.
HEATIT
Protocol
Chip
Z-Wave Plus, 868.4MHz
Z-Wave 800 chip
230VAC 50Hz
3600W 16A (resistive load)
Contactor recommended for
loads above 13A
16A
6. Hold the Center button until “OFF” is shown in the display
(approx. 5 seconds).
This device may be used with all devices certified with the
Z-Wave Plus™ certificate and should be compatible with
such devices produced by any manufacturer. Every primary
controller is different depending on the manufacturer, their
target audience and intended use/application. Please review
the functionalities implemented by the primary controller you
intend to use with our Z-Wave Plus certified device to ensure
that it provides the necessary controls to take full advantage of
our product’s capabilities.
Rated voltage
Max load
Z-TRM6
Quick Guide
7. Press the ”+” button once to reach “CON”, and hold until the
display shows a rotating light pattern.
TO PRODUCT
DOCUMENTS
8. The thermostat will display “INCL” when the thermostat is
successfully added. NB! If adding/removing fails, Err (error)
will appear.
Max current
Power consumption
Power regulator
Article no.
Doc. version
Doc. date
When either of these procedures has been performed, the
thermostat will perform a complete factory reset. The device
will display “RES” for 5 seconds while performing a factory reset.
When “RES” is no longer displayed, the thermostat has been
reset.
<2W
54 305 66
54 305 68
2023-A
01.07.2023
Time cycle 0 to 30 min.
Ambient temperature 5°C to 40°C
Temperature range 5°C to 40°C
Storage temperature -30°C to 70°C
Hysteresis
Humidity
ADD/REMOVE
The primary controller/gateway has a mode for adding or
removing devices. Please refer to your primary controller
manual on how to set the primary controller in add/remove
mode. The device may only be added or removed from the
network if the primary controller is in add/remove mode. When
the device is removed from the network, it will NOT revert to
factory settings.
INSTALLATION
0.3°C to 3.0°C (default 0.5°C)
10% to 85% RH
Please use this procedure only when the network primary
controller is missing or otherwise inoperable.
Installation must be done by a qualified electrician in
accordance with national building codes. Before installation,
disconnect the power to the device from the mains. During
installation of the device, power to the device must be
disconnected AT ALL TIMES!
Compatible with NTC-
sensor with values
Range RF
6.8, 10, 12, 15, 22, 33, 47 or 100kΩ @ 25°C
Min. 40 meter
Max. 2.5mm2 2Nm
IP21
CHOICE OF SENSOR
The thermostat has multiple sensors and sensor modes. This
lets you configure the thermostat to work correctly in most
installations.
Screw terminals
IP Code
Size (LxWxH)
CONNECTIONS
Max tightening torque terminal screws: 2Nm.
84 x 84 x 45.5mm
An always listening node must be powered continuously and
reside in a fixed position in the installation to secure the routing
table. Adding the device within a 2 meter range from the
gateway can minimize faults during the Interview process.
Available temperature sensors:
Approvals
Z-Wave Plus v2, CE, Nemko
White RAL 9003
54 305 66
Black matt
54 305 68
To access the terminal screws, hold the sides of the display and
gently pull outwards to detach the front piece.
F
Floor sensor
MAINTENANCE
A
Internal room sensor
There are two ways to add the device to a Z-Wave network.
AF
A2
A2F
Internal room sensor + Floor sensor
External room sensor
The product is maintenance-free.
Indoor use only.
INTRODUCTION
Standard (Manual)
Heatit Z-TRM6 is an electronic thermostat designed for
electrical heating. The thermostat can be controlled through
your Z-Wave™ network or via the buttons on the front. The
thermostat has a user friendly interface.
External room sensor + Floor sensor
Add/remove mode is indicated on the device by rotating
LED segments on the display. It indicates this for 90 seconds
until a timeout occurs, or until the device has been added to/
removed from the network. Configuration mode can also be
cancelled by performing the same procedure used for starting
Configuration mode.
45.5mm
PWER Power regulator mode (no sensor used)
22mm 23.5mm
50mm
NOTE: Some types of floor require that a floor sensor is
connected in order to limit the floor temperature to a maximum
of 27°C (check the manual from the floor manufacturer). When
the thermostat is used in AF or A2F the floor limiter FHI is
automatically set to 27°C. When using any other sensor type
(A, F or A2) the minimum and maximum limits are 5°C and 40°C
respectively.
Heatit Z-TRM6 has 3 modes; Heat - Cool and Eco.
The thermostat fits in standard European junction boxes and
may be used with most System 55 frames. It has a sturdy metal
frame for secure fastening on the junction box. The thermostat
has one built-in room temperature sensor. Two additional
external temperature sensors may also be connected.
1. Hold the Center button for 5 seconds.
The display will show “OFF”.
Floor sensor
NTC type 6.8, 10, 12, 15, 22, 33, 47 or 100kΩ.
Default 10kΩ.
2. Press the ”+” button once to see “CON” in the display.
3. Start the add/remove device process in your primary
controller.
External sensor NTC type 6.8, 10, 12, 15, 22, 33, 47 or 100kΩ.
DISPLAY ICONS
Default 10kΩ.
Heatit Z-TRM6 has active power metering and it gives you real
time information about your power consumption. It also allows
you to set the power metering value manually in case of
connection with a contactor.
N
Power connection (Neutral) 230VAC.
Heating cable N connection.
ICON
DESCRIPTION
4. Start the configuration mode on the thermostat by holding
the Center button for approximately 2 seconds.
Heating N
L
This icon will be displayed while the relay is on and
the thermostat is in either Heating or Eco mode.
Power connection (Live) 230VAC.
Heating cable L connection.
Heating L
The device is now ready for use with default settings.
This icon will be displayed while the relay is on and
the thermostat is in Cooling mode.
The thermostat can be set up with multiple associations
and can be used as a master thermostat. It can also control
external relays and wall plugs.
Next, position the thermostat and mount it into the junction
box using 2 screws. Position the thermostat front over the part
mounted in the junction box, then carefully press the front until
it clicks into place. In order to get power metering values, the
load needs to be connected to both heating L + N.
NB! When the device is removed from the gateway, the
parameters are not reset. To reset the parameters, see
”Factory reset”.
This icon shows the current signal strength.
We develop and design our products according in accordance with our strict quality
requirements (ISO 9001) and environmental requirements (ISO 14001). All electrical
installations must be carried out by an authorized electrical installer. The product
must be installed in accordance with our installers manual and national building
codes. Any wrongful installation, misuse, damage of the product, is not covered
documents.heatit.com. Heatit Controls AB can not be held liable for any type of
errors or omittances in our product information. Product specifications may change
without further notice.
The thermostat can withstand a load of max. 16A/3600W at
230VAC. We recommend a contactor for loads above 13A.
If inclusion fails, please perform a ”remove device” process and
try again. If inclusion fails again, please see “Factory reset”.
QUICK START
1. Switch off the mains voltage (disable the fuse).
2. Open the junction box.
SmartStart (Automatic)
SmartStart enabled products may be added to a Z-Wave
network by scanning the Z-Wave QR-Code on the product
if your primary controller supports SmartStart inclusion. No
further action is required and the SmartStart product will be
added automatically after being powered on within range of the
primary controller.
3. Connect the wires according to the description above
Optional: Connect external wired sensors.
4. After verifying the connections, switch on the mains voltage.
Org. doc. 01.07.2023
Heatit Controls AB
l
Läkarvägen 4, 454 31 BRASTAD, SWEDEN
| General | Details |
|---|---|
| Name | HEATIT Z-TRM6 Matt Z-Wave Thermostat User Guide |
| Make | HEATIT |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.27 MB |

heatit Z-TRM6 DC Z Wave Electronic Thermostat Instruction Manual

HEATIT Z-TRM3 Thermostat User Guide

Heatit Z-TEMP2 Thermostat Installation Guide

heatit Z-TRM3 WiFi Thermostat Instruction Manual

HEATIT Z-Temp3 is a Battery Operated Thermostat Instruction Manual

4512673 Heatit ZM Thermostat 16A User Guide

HEATIT 54 304 59 DIN Smart Thermostat Installation Guide

HEATIT 54 305 41 WiFi6 Thermostat Installation Guide

HEATIT Z-TEMP3 Thermostat User Guide

heatit ET-7AW Touchscreen Programmable Thermostat User Manual

HEATIT Z-TRM6 Matt Z-Wave Thermostat User Guide Overview
Summary of Contents
- Page 1: statement regarding products from multiple manufacturers please read this before installation set the primary controller in add mode (security/non security) factory reset technical data the device may be used with all devices certified with the Z-Wave Plus™ certificate and should be compatible with such devices produced by any manufacturer. installation must be done by a qualified electrician in accordance with national building codes. the thermostat has multiple sensors and sensor modes. the product is maintenance-free. the thermostat can withstand a load of max. 16A/3600W at 230VAC.
- Page 2: Erklæring vedrørende produkter fra ulike produsenter Les dette før installasjon Denne enheten kan brukes sammen med andre enheter sertifisert med Z-Wave Plus™-sertifikatet. Hver gateway er forskjellig avhengig av produsent, målgruppe og tiltenkt bruk/applikasjon. Hold midtknappen inne til du ser OFF i displayet (ca. 5 sek.). Trykk på + knappen. CON vises i displayet. Gå inn i menyen ved å holde midtknappen inne i ca. 5 sekunder. Displayet vil vise INCL når termostaten har blitt inkludert. Når en av disse prosedyrene er utført, vil termostaten utføre en fullstendig tilbakestilling til fabrikkinnstillinger. Produktet skal installeres av autorisert installatør i henhold til norske byggforskrifter. Heatit Z-TRM6 er en elektronisk termostat designet for elektrisk gulvvarme.