micro-air EasyTouch RV 356 True Air RV Thermostat User Manual
EasyTouch RV 356
Auto Gas Changeover
Note: See section Auto Gas Changeover Type in section Initial Setup Instructions to configure this feature.
Auto Gas Changeover operation mirrors the OEM thermostat’s operation for additional stages of heat when
the thermostat determines more are needed. The three escalating stages are shown in Table 8. All three
stages may not be available based on your system, but EasyTouch will output the same logic. Stage 2 heating
is available in every system.
Staging
Stage 1
Stage 2
Stage 3
Heat Source
Heat Pump
Furnace 1
Furnace 2
Table 8 - Heat Staging
The below tables are based on “Version A” type of Auto Gas Changeover, which is the default selection
and should be adjusted as described in the Auto Gas Changeover Type section. “DISABLED” will turn this
behavior off. Other version changes are noted within the below tables.
The temperature and runtime values can also be adjusted from the same setup screens where “Type” is set.
Heat Pump and Auto Cool/Heat Pump Changeover Behavior
Table 9 shows how Auto Gas Changeover affects the Heat Pump operational modes when enabled.
Environment (°F)
Operation
Inside 4° Or Less Below Setpoint Normal Heat Pump Operation (Stage 1)
Stage 1 and Stage 2 Run Until Setpoint is Satisfied
(VERSION C TURNS OFF STAGE 1 ABOVE 4°)
Inside 5° Or 6° Below Setpoint
Inside 7° Or More Below Setpoint Stage 1, Stage 2, and Stage 3 Run Until Setpoint is Satisfied
or
Any Stage Runs 20 Minutes
Stage Escalates to the Next Highest Available Stage
(VERSION A AND D ONLY)
3 Cycles in a Row Call for
Escalation
Table 9 - Heat Pump AGC Operation
Furance and Auto Cool/Furnace Changeover Behavior
Table 10 shows how Auto Gas Changeover affects the Furnace operational modes when enabled.
Environment (°F)
Operation
Inside 4° Or Less Below Setpoint Normal Furnace Operation (Stage 2) (Stage 1 Never Runs)
Inside 5° Or More Below Setpoint Stage 2 and Stage 3 Run Until Setpoint is Satisfied
or
Any Stage Runs 20 Minutes
Stage Escalates to the Next Highest Available Stage
(VERSION A AND D ONLY)
3 Cycles in a Row Call for
Stage 2 and Stage 3 will Start Together for Next Two Hours
Escalation
Table 10 - Furnace AGC Operation
13
©2023 Micro-Air LLC
Revision 2.1
| General | Details |
|---|---|
| Name | micro-air EasyTouch RV 356 True Air RV Thermostat User Manual |
| Make | Micro-Air |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.48 MB |

micro-air EasyTouch 357 Multi Zone Replacement Thermostat Instruction Manual

Micro-Air EasyTouch RV 353 Touch Screen Thermostat Instruction Manual

Micro-Air 359 Touchscreen Thermostat Instruction Manual

Micro-Air EasyTouch RV 353 Thermostat Instruction Manual

micro-Air EasyTouch RV 351 Thermostat User Manual

Micro Air ETRV EasyTouch RV Thermostat Instruction Manual

micro-Air ASY-357-X02 EasyTouch 357 Touchscreen Thermostat User Manual

micro-Air EasyTouch 352 Thermostat User Manual

Micro-Air EasyTouch 355 Touch Screen Thermostat User Manual

Micro-Air 351 Air Conditioner Digital Thermostat User Guide